background image

(Supersedes PF495)

PF495-1

H

161-304509-001

JANUARY, 2003

4

and

Installation, Operation

RENEWAL PARTS IDENTIFICATION

Industrial Wall Mounted Natural Convection 

Space Heater - Type H

© 2010 Chromalox, Inc.

Spe

cification

s

 

GENERAL INFORMATION

ELECTRIC SHOCK HAZARD. Disconnect all power
before installing or servicing heater. Failure to do
so could result in personal injury or property dam-
age. Heater must be installed by a qualified person
in accordance with the National Electrical Code,
NFPA 70.

1.

All wiring should be done in accordance with local codes and the
National Electrical Code by a qualified person.

2.

Connect air heaters to same line voltage as on heater nameplate.

3.

Check possibility of corrosion if heaters are operated in atmos-
pheres other than air.

4

. In general, locate heater approximately 1 foot from the floor, but

not less than 6 inches, for best overall results. Heater, however, can
be located anywhere to meet unique requirements of any particu-
lar application.

5.

Heaters are mounted directly on any type of noncombustible sur-
face—masonry, concrete, block, plastered walls, metal framework,
etc.— using appropriate hardware.

6.

Standard heaters are mounted in a horizontal position with the ter-
minal end on the left. 

The system designer is responsible for the safety
of this equipment and should install adequate
back-up controls and safety devices with their
electric heating equipment. Where the conse-
quences of failure could result in personal injury or
property damage, back-up controls are essential.

Mo

de

l

O

u

t

pu

t

Voltag

e

O

u

t

pu

t

Dim

e

n

s

ion

s

 

(

In.

)

Wt.

(

kW

)

(

Vac

)

(

BTUH

)

Wi

d

th

H

e

ight

D

ep

th

Lb

s

.

H-1801

1.0

120

2

20-3/4

7-1/2

4-1/2

28

H-1801

1.0

240

2

20-3/4

7-1/2

4-1/2

28

H-2405

1.5

120

2

26-1/2

7-1/2

4-1/2

30

H-2405

1.5

240

2

26-1/2

7-1/2

4-1/2

30

H-2405

1.5

480

2

26-1/2

7-1/2

4-1/2

30

H-2406

2.0

120

4

26-1/2

11-1/4

4-1/2

32

H-2406

2.0

240

4

26-1/2

11-1/4

4-1/2

32

H-2406

2.0

480

4

26-1/2

11-1/4

4-1/2

32

H-2407

3.0

240

4

26-1/2

11-1/4

4-1/2

32

H-2407

3.0

480

4

26-1/2

11-1/4

4-1/2

32

Отзывы: