WARNING: 

Hazard of Electric Shock. Any installation

involving electric heaters must be grounded to earth
to eliminate shock hazard.

1.

Be sure line voltage matches heater voltage (on nameplate).

2.

Electric wiring to heater must be installed in accordance with
local and National Electrical Codes.

3.

Power controllers 

must

be used when heaters are rated  3 phase

and when the heater amperage exceeds to rating of the thermostat.

4.

Refer to Wiring Diagram Table B, for the proper wiring diagram
for connecting heater.

Wiring Diagrams - Table B

WIRING

INSTALLATION

3.

Whether vertically or horizontally, the heater should be rigidly 

mounted so that vibration is at a minimum since excessive
vibration will result in erratic thermostat operation. The
NWHO-6 is provided with mounting lugs to support the heat-
ing chamber. (See photo.)

4.

By using a slotted mounting assembly on either of the lugs, 

the heater chamber will be permitted to expand with increas-
ing temperature.

5.

DANGER: 

Hazard of Fire.

Provide minimum of 6” spacing

from chamber and related piping to nearest combustible material.
Avoid operation of heater near combustible fluids or in com-
bustible vapor or gas laden atmosphere. NOTE: Contact factory
for heaters suitable for use in hazardous locations.

6.

Provide adequate space at terminal end to permit withdrawal

of the heater from chamber should servicing be required.

Model

240V, 240V,

480V, 

480V,

1ø Fig.

3ø    Fig.

1ø Fig.

3 ø

Fig.

NWHO-61215

2

5

NWHO-61515

2

5

NWHO-62015

3

5

NWHO-62515

3

5

NWHO-63015

3

5

NWHO-60825

1

2

4

5

NWHO-61025

2

5

NWHO-61225

2

5

NWHO-61525

2

5

NWHO-61825

2

5

Note:

Use wire size and type specified by N.E.C. 480V and 550V heaters require 600V wire,

per N.E.C. Contactors and wire supplied by customer.

Thermostat

Line

Contactor

120V, 240V

Contactor

Thermostat

120V, 240V

L1

L2

L3

Thermostat

Line

Contactor

120V, 240V

Contactor

Thermostat

L1

L3

L2

120V, 240V

Contactor

Contactor

Thermostat

1L1

1L2

1L3

2L1

2L2

2L3

120V 

or

240V

Figure 3 – NWHO6

240V, 2-3ø    

Figure 2 – NWHO6

240V, 3ø    

Figure 1 – NWHO

240V, 1ø

Figure 5 – NWHO6

480V, 3ø    

Figure 4 – NWHO6

480V, 1ø

Note:

Dotted lines indicate “customer furnished.” However, Thermostat could have been furnished by Chromalox if so specified on the order.