Installation 

and

RENEWAL PARTS IDENTIFICATION

PE406-5

FEBRUARY, 1999

(Supersedes PE406-4)

161-048710-001

GENERAL

INSTALLATION

© 2010 Chromalox, Inc.

Type NWHO-3 Series Circulation Heaters

(for Regular and Fuel Oil Heating)

WARNING:

This heater is not intended for use in haz-

ardous atmospheres where flammable vapors, gases,
liquids or other combustible atmospheres are present
as defined in the National Electrical Code. Failure to
comply can result in explosion or fire.

The NWHO-3 series is a general-purpose regular and fuel oil solu-

tion circulation heater intended for use indoors. It is designed for 150
psig at 550˚F per ANSI standards.

The 3 steel-sheathed tubular elements are centered in a 3” diame-

ter steel heating chamber and welded to a removable steel flange. The
assembly is surrounded by 1-1/2” insulation and sheet metal jacket.

Depending upon the order specifications, the NWHO-3 may or

may not be factory equipped with AR or other Chromalox thermostat.
Such thermostats function to control outlet temperatures and to limit
internal temperatures under abnormal flow conditions. These controls
do not fail safe.

CAUTION: 

Users should install adequate back-up controls

and safety devices with their electric heating equipment.
Where the consequences of failure may be severe, back-
up controls are essential. Although the safety of installa-
tion is the responsibility of the user, Chromalox will be
glad to make equipment recommendations.

WARNING:

Hazard of Shock. Disconnect all power

before installing heater.

1. Vertical mounting

(Preferred) —

When the heater is vertically mounted, the terminal housing will be
at the top of the heater. The inlet pipe will be located on the side
near the bottom of the heater and the outlet pipe at the top.
The axis of the chamber will be in a vertical position as in the
photo above and as in Figure A.

Note:

A drain pipe located at the bottom of the heater should be

provided and enough room left, when mounting heater, to allow
draining the heater.

2. Horizontal 

Mounting

(Optional) —

When mounting heater horizontally, inlet and outlet pipes 

must

be

up. In any other position, heater cannot be purged of air, and ele-
ments may be seriously damaged. (See Figure B.)

Specifications — Table A

Incorrect

Correct

Figure A — Vertical Mounting

Figure B — Horizontal Mounting

Correct

Incorrect

Regular Oil Heaters

Dimensions (In.) 

Model Volts 

Phase 

kW 

W/In

2

A

B

C

NWHO-33015

3

32-15/16

22-1/2

16-1/2

NWHO-34515

4.5

32-15/16

22-1/2

16-1/2

NWHO-36015

240 or 480

1 or 3 

s

s

6

23

42-15/16

32-1/2

26-1/2

NWHO-37515

7.5

55-7/16

45

39

NWHO-39015

9

55-7/16

45

39

NWHO-30315

3

32-15/16

22-1/2

16-1/2

NWHO-30415

240 or 480

1 or 3 

s

s

4

15

42-15/16

32-1/2

26-1/2

NWHO-30615

6

55-7/16

45

39

Fuel Oil Heaters

A B

C

8-1/32”

12-5/16”

6-1/8”

Thermostat

Type AR

Mounting Lugs

3/8” - 16

Threaded Holes -

1-1/2” Deep

1-1/4” Centers

1-3/8” Conduit

Openings

1” Pipe

Outlet

1” Pipe

Inlet