Chromalox LUH-TK1 Скачать руководство пользователя страница 3

Connect single pole thermostat blue lead
(BL) to heater lead C1 and black lead
(BLK) to C2 using wire nut provided.

Connect single pole thermostat blue lead
(BL) to heater lead C1 and black lead
(BLK) to C2 using wire nuts provided.

Connect single pole thermostat blue lead
(BL) to heater lead C1 and black lead
(BLK) to C2 using wire nuts provided.

Connect single pole thermostat blue lead
(BL) to heater lead C1 and black lead
(BLK) to C2 using wire nuts provided.

NOTE: One element is omitted on LUH-D-02

Connect single pole thermostat blue lead
(BL) to heater lead C1 using the wire nut
provided. Remove the C1 wire marker
from the heater lead and attach to thermo-
stat black lead (BLK).

Connect single pole thermostat blue lead
(BL) to heater lead C1 using the wire nut
provided. Remove the C1 wire marker
from the heater lead and attach to thermo-
stat black lead (BLK).

Motor

Heating

Elements

Overheat

Cutout

Contactor

C1

C2

BL

BLK

L1   L2   L3

LUH-TK-1
Single Pole
Thermostat

Ground

Motor

Heating

Elements

Overheat

Cutout

Contactor

C1

C2

BL

BLK

L1         L2

LUH-TK-1
Single Pole
Themostat

Ground

Motor

Heating

Elements

Overheat

Cutout

Contactor

C1

C2

BL

BLK

L1   L2   L3

LUH-TK-1
Single Pole
Thermostat

Transformer

Fuses

Ground

Figure 4

208, 240V — 3ø — 4, 5, 7.5, 10, 12.5 & 15 kW

240V — 3ø — 20 kW

Figure 5

208, 240, 277V — 1ø — 2.6, 4, 5, 7.5 & 10 kW

Figure 6

480V — 3ø — 4, 5, 7.5, 10, 12.5, 15,

20, 25, 30, 35, 40 & 45 kW

Motor

Heating

Elements

Overheat

Cutout

Contactor

C1

C2

BL

BLK

L1         L2

LUH-TK-1
Single Pole
Thermostat

Transformer

Fuses

Ground

Figure 7

1ø Heaters with Optional Control Transformer

Motor

Heating

Elements

Overheat

Cutout

Contactor

C1

BL

BLK

C2  L1          L2

LUH-TK-1
Single Pole
Thermostat

Remove C1
Tag from
Existing
Lead

Tag Lead
as C1

Ground

C1

Figure 8

1ø Heaters with Optional External 120 Volt Control

Motor

Heating

Elements

Overheat

Cutout

Contactor

C1

BL

BLK

C2  L1   L2   L3

LUH-TK-1
Single Pole
Thermostat

Remove C1
Tag from
Existing
Lead

Tag Lead
as C1

Ground

C1

Figure 9

3ø Heaters with Optional External 120 Volt Control

WIRING DIAGRAMS