ELECTRIC SHOCK HAZARD. Disconnect all power
before installing or servicing heater. Failure to do
so could result in personal injury or property dam-
age. Heater must be installed by a qualified person
in accordance with the National Electrical Code,
NFPA 70.

ELECTRIC SHOCK HAZARD. Any installation involv-
ing electric heaters must be performed by a quali-
fied person and must be effectively grounded in
accordance with the National Electrical Code to
eliminate shock hazard.

1.

The power supply voltage should be the voltage as specified on the
heater nameplate located on the heater housing.

2.

Wiring should be run in flexible or rigid metal conduit and must be
installed in accordance with the requirements of the National
Electrical Code and such other local requirements as may be
applicable. 

Note:

High temperatures will oxidize copper. Do not

use copper wire in connecting this heater. Nickel-plated copper
wire, insulated in accordance with requirements for temperature
and voltage is recommended.

3.

A sufficient length of this wire (not less than 12”) should be used
to extend from each heater terminal into a connection box location
where the temperature does not exceed 300˚F.

4. ELECTRICAL CONNECTIONS

A. End Elements

Electrical connection to the heater end elements is made
through the 7/8” dia. opening in the end of the terminal cover
of the element assembly. A 1/2” flexible conduit connector is
provided with each element assembly for this purpose.

B. Center Elements

Electrical connection to the heater center element is made
through the 7/8” dia. opening in the 4” octagon conduit box for
the element assembly. A 1/2” flexible conduit connector is pro-
vided with each element assembly for this purpose.

5. ACCESS TO TERMINALS

A. End Elements

Access to the end element terminals is obtained by removing
the mounting bolt, nut and spacer (see Figure 9, items 9, 16 and
18) and sliding the terminal end of the element assembly out of
the housing.

B. Center Elements

Access to the center mounted element terminals is obtained by
removing the terminal box cover.

6. END ELEMENT TERMINAL ASSEMBLY

Assemble end terminal, screw and wire as shown in Figure 5. Hold
terminal with pliers and tighten the terminal screw securely with a
screwdriver.

7. CENTER ELEMENT TERMINAL ASSEMBLY

Assemble center terminal, washers, nut and wire as shown in
Figure 6. Hold terminal with pliers and tighten the terminal nut
securely with a wrench.

CAUTION:

Terminal clip is spot-welded to element terminal pin

and over-tightening terminal screw may break the weld or shear
off terminal pin. However, either the screw or nut should be suffi-
ciently tightened to eliminate arcing.

8. SERIES CONNECTION

of Radiant Heaters of equal volt and

watt rating is permitted in all line voltages up to 600 volts. In mak-
ing such series connections it is necessary to observe the “right”
(series-parallel) connection rather than the “wrong” (parallel-
series) connection both shown in Figure 7. If heaters are connect-
ed according to the “wrong” illustration, failure of any heater will
cause progressive failure of other heaters still operating.

9. DELTA CONNECTIONS

— When heaters occur in multiples of

three, they may be connected to, and balanced across, three-phase
lines. The most commonly used connection is the delta connection
illustrated in Figure 8.

Three phase Delta connections to minimize inductive effect in

conduits are made per this diagram. The rule: run all 3 three-phase
conductors in the same conduit as far as possible. For single-phase,
run only two conductors and follow the same rule.

3

WIRING

Wrong

Right

L1

L2

L2

L1

Radiant
Heaters

Wrong

Right

L1

L2

L2

L1

Radiant
Heaters

Figure 5 — End Element Terminal Assembly

Figure 7

Figure 8

Figure 6 — Center Element Terminal Assembly

Содержание DU-RAD-458 6.04 757

Страница 1: ...5 16 DU RAD 774 10 39 1231 4 1143 8 361 2 3815 16 DU RAD 782 10 77 1275 16 1187 16 409 16 3815 16 DU RAD 790 11 15 1317 16 1229 16 4411 16 3815 16 DU RAD 7102 208 240 11 72 1377 16 1289 16 5011 16 381...

Страница 2: ...ter element enters the terminal box through the connector furnished or through a right angle connector not furnished 3 Framing Where an extensive installation is being made the use of continuous slot...

Страница 3: ...lement terminals is obtained by removing the mounting bolt nut and spacer see Figure 9 items 9 16 and 18 and sliding the terminal end of the element assembly out of the housing B Center Elements Acces...

Страница 4: ...ases after heat up Typical insulation values are 5 megohm or greater on complete assemblies or 20 megohm on individual unsealed ele ments It is recommended that heaters with 1 megohm or less be dried...

Страница 5: ...ctor and Locknut 119 075454 005 200 075482 002 11 Terminal Screw 248 046044 002 4 12 Element Support Clip 059 014304 002 13 Insulating Bushing 032 013454 001 14 Bushing Retaining Clip 059 017175 001 1...

Страница 6: ...umber See Table B or Table C for variation in element catalog number depending upon voltage WIRING Welded Retaining Rings Type UTU Single Hairpin Elements Volts kW Model 120 or 240 0 8 UTU 2 208 or 27...

Страница 7: ...basic Model Number See Table B and C for variation in model number depending upon voltage Note Part Numbers suffixed by a number in indicates the number of parts of same part number used or supplied...

Страница 8: ...BLVD OGDEN UT 84404 Phone 1 800 368 2493 www chromalox com Limited Warranty Please refer to the Chromalox limited warranty applicable to this product at http www chromalox com customer service policie...

Отзывы: