Wiring

ELECTRIC SHOCK HAZARD. Disconnect all power 

before installing or servicing heater. Failure to do so 

could result in personal injury or property damage. 

Heater must be effectively grounded in accordance 

with the National Electrical Code, NFPA 70.

1.  Use heater only on the voltage and frequency specified 

on the nameplate.

2.  All wiring should be done in accordance with local codes 

and the National Electrical Code by a qualified person.

3  Branch circuit wire for connection to heater must be at 

least 90°C wire.

4.  The top access panel is secured by 4 screws that must 

be loosened to gain access.

5.  A ground terminal is provided near the power terminal 

board. The ground wire should be connected before oth-

er connections are made.

6.  Refer to Chart A for proper size “SO” grade cable.
7.  A proper strain relief must be used with “SO” grade ca-

ble.

8.  Dragon heaters are factory pre-wired for 3-phase delta 

operation. Some units can be converted to single phase 

operation by changing the wiring. Refer to Chart Afor 

those heaters that can be converted to single phase. The 

appropriate wiring diagram is also located on the back of 

the wiring compartment cover.

Table 1 - Specifications

Model

kW

Volts

Phase

Wiring Dia. 

No.

Amps

Wire Size

25’ Cord Set

PCN

Optonal Plugs

Locking Type

Non-Locking 

Type

DRA-07-83

7.5

208

1

1A

36.3

8/3

PLC-2508-3

———

PGN-6-50

DRA-07-83

7.5

208

3

1

21.0

10/4

PLC-2510-4

PGL-15-30

PGN-15-50

DRA-07-23

5.6

208

1

1A

27.1

10/3

PLC-2510-3

PGL-15-30

PGN-6-50

DRA-07-23

5.6

208

3

1

15.7

12/4

PLC-2512-4

PGL-15-20

PGN-15-20

DRA-07-23

7.5

240

1

1A

31.5

8/3

PLC-2508-3

———

PGN-6-50

DRA-07-23

7.5

240

3

1

18.2

12/4

PLC-2512-4

PGL-15-20

PGN-15-20

DRA-10-83

9.75

208

1

1A

47.1

6/3

PLC-2506-3

———

PGN-6-50

DRA-10-83

9.75

208

3

1

27.2

8/4

PLC-2508-4

PGL-15-30

PGN-15-50

DRA-10-23

7.3

208

1

1A

35.4

8/3

PLC-2508-3

———

PGN-6-50

DRA-10-23

7.3

208

3

1

20.4

10/4

PLC-2510-4

PGL-15-30

PGN-15-50

DRA-10-23

9.75

240

1

1A

40.8

6/3

PLC-2506-3

———

PGN-6-50

DRA-10-23

9.75

240

3

1

23.6

10/4

PLC-2510-4

———

PGN-15-50

DRA-15-83

15

208

3

1

41.8

6/4

PLC-2506-4

———

PGN-15-50

DRA-15-23

11.2

208

3

1

31.4

8/4

PLC-2508-4

———

PGN-15-50

DRA-15-23

15

240

3

1

38.3

6/4

PLC-2506-4

———

PGN-15-50

DRA-15-43

15

480

1

2A

31.5

8/3

PLC-2508-3

PGL-3763C

———

DRA-15-43

15

480

3

2

18.2

12/4

PLC-2512-4

PGL-16-30

———

DRA-15-93

15

600

1

2A

25.2

10/3

PLC-2510-3

PGL-3763C

———

DRA-15-93

15

600

3

2

14.6

14/4

PLC-2514-4

PGL-17-30

———

DRA-20-23

15

208

3

3

41.8

6/4

PLC-2506-4

———

PGN-15-50

DRA-20-23

20

240

3

3

48.3

4/4

PLC-2504-4

———

PGN-15-50

DRA-20-43

20

480

1

4A

41.9

6/3

PLC-2506-3

PGL-3763C

———

DRA-20-43

20

480

3

4

24.4

10/4

PLC-2510-4

PGL-17-30

———

DRA-20-93

20

600

1

4A

33.5

8/3

PLC-2508-3

PGL-3763C

———

DRA-20-93

20

600

3

4

19.4

12/4

PLC-2512-4

PGL-17-30

———

DRA-30-43

30

480

3

4

36.3

6/4

PLC-2506-4

PGL-3764C

———

DRA-30-93

30

600

3

4

29.1

8/4

PLC-2508-4

PGL-17-30

———

Power Cord based on 600V Hard Service Cord Rated 90°C
Plug selection is based on using Chromalox Cable Kits

Содержание DRA Series

Страница 1: ...1 PF497 2 161 304812 001 December 2018 Installation and Operation Instructions DRA Portable Industrial Unit Blower Air Heater ...

Страница 2: ...dth Depth DRA 07 83 208 7 5 1 and 3 36 3 21 0 25 590 34 25 27 5 25 DRA 07 23 240 208 7 5 5 6 1 and 3 31 5 18 3 25 590 34 25 27 5 25 DRA 10 83 208 9 75 1 and 3 47 1 27 3 33 267 34 25 27 5 25 DRA 10 23 240 208 9 75 7 3 1 and 3 40 8 23 7 33 267 34 25 27 5 25 DRA 15 83 208 15 3 41 8 51 180 34 25 27 5 25 DRA 15 23 240 208 15 11 2 3 36 3 51 180 34 25 27 5 25 DRA 15 43 480 15 1 and 3 31 4 18 2 51 180 34 ...

Страница 3: ...ting Do not cover cord with throw rugs runners or the like Arrange cord away from traffic area and where it will not be tripped over 9 To disconnect heater turn thermostat off then remove plug from outlet 10 Connect to properly grounded outlets only 11 Do not insert or allow foreign objects to enter any venti lation or exhaust opening as this may cause an electric shock fire or damage the heater 1...

Страница 4: ...50 DRA 07 83 7 5 208 3 1 21 0 10 4 PLC 2510 4 PGL 15 30 PGN 15 50 DRA 07 23 5 6 208 1 1A 27 1 10 3 PLC 2510 3 PGL 15 30 PGN 6 50 DRA 07 23 5 6 208 3 1 15 7 12 4 PLC 2512 4 PGL 15 20 PGN 15 20 DRA 07 23 7 5 240 1 1A 31 5 8 3 PLC 2508 3 PGN 6 50 DRA 07 23 7 5 240 3 1 18 2 12 4 PLC 2512 4 PGL 15 20 PGN 15 20 DRA 10 83 9 75 208 1 1A 47 1 6 3 PLC 2506 3 PGN 6 50 DRA 10 83 9 75 208 3 1 27 2 8 4 PLC 2508...

Страница 5: ...0 1 125 Locking PGL 3763C 2 Pole 4 Wire 600 50 G G W X Z G W X Z X G Y Z X G Y Z X G Y Z X G Y Z Y X G Y X Z 750 1 125 Locking PGL 3765C 3 Pole 4 Wire 600 50 G G W X Z G W X Z X G Y Z X G Y Z X G Y Z X G Y Z Y X G Y X Z 625 1 187 Non Locking PGN 6 50 2 Pole 3 Wire 250 50 G G W X Z G W X Z X G Y Z X G Y Z X G Y Z X G Y Z Y X G Y X Z 6 50 C73 53 390 775 Non Locking PGN 15 20 3 Pole 4 Wire 250 20 G G...

Страница 6: ...trical rating of cord 5 On opposite end of cord prepare end as directed by in structions that are provided with the plug 6 Attach cord assembly to heater as shown in Fig 2 below Run wire tie through slots in bracket and over cord Pull tab of wire tie to provide cord strain relief Power wires Ground wire 90 fitting Figure 2 Operation Thermostat Heaters include a bimetal thermostat for the automatic...

Страница 7: ... numbered wires to T2 All odd numbered wires to T1 Contactor Instructions 1 Loosen screws on load side of contactor Remove all lead wire 2 Insert lead wires numbers 1 3 and 5 into box lug connector T1 Tighten screws on box lug connector 3 Insert lead wires numbers 2 4 and 6 into box lug connector T2 Tighten screws on box lug connector 4 Examine wiring to make certain it is per above diagram T3 T2 ...

Страница 8: ...009 112 045422 007 072 304551 014 DRA 15 43 480 15 1 3 118 304793 009 193 302120 012 112 045422 007 072 304551 008 315 304252 001 DRA 15 93 600 15 1 3 118 304793 010 193 302120 015 112 045422 007 072 304551 008 315 304252 003 DRA 20 23 240 19 5 3 118 304793 004 193 302120 009 112 045422 007 072 304551 014 DRA 20 43 480 20 1 3 118 304793 005 193 302120 012 112 045422 007 072 304551 008 315 304252 0...

Отзывы: