background image

WIRING

WARNING: 

Hazard of Electric Shock. Any installation

involving electric heaters must be effectively ground-
ed in accordance with the National Electrical Code to
eliminate shock hazard.

1.

All wiring should be done in accordance with the National 
Electrical Code and with local codes by a qualified person. 

2.

Connect air heaters to same line voltage, phase and frequency 
as on heater nameplate.

3.

Teflon insulated nickel plated copper wire or buss bar is rec-
ommended for power connections to heater terminals and for

wiring runs in heated zones. When ambient temperature in
heated zone exceeds that for which insulated wire is recom-
mended use bare nickel-plated copper with porcelain beads,
tubing or buss bar. Consult local Chromalox representative.

4.

Users should install adequate back-up controls and safety
devices with their electric heating equipment. Selection of
controls, thermostat, SCR units, contactors and etc. depends
on the degree of accuracy required, reliability, electrical rating
of heater and economic considerations.

5.

Below is an example of standard CAB 122 480V 3P 12 kW
wired with recommended back-up controls (Figure 3).

OPERATION

WARNING:

Users should install adequate back-up

controls and safety devices with their electric
heating equipment. Where the consequences of
failure may be severe, back-up controls are essen-
tial. Although the safety of the installation is the
responsibility of the user, Chromalox will be glad
to assist in making equipment recommendations.

1.

Do not operate heaters at voltages in excess of that stamped
on the heater since excess voltage will shorten heater life.

MAINTENANCE

WARNING: 

Hazard of Severe Shock. Disconnect all

power to heater before servicing or replacing heaters.

1.

Periodically clean terminals and terminal covers of dust and 
corrosion to maintain good electrical connections and to per-
mit rapid heat dissipation. Use airblast, and be careful to avoid
damage to mica insulation.

2.

Check for loose terminal connections.

Fused Switch

480V

Power

Supply

Heater

Contactor

Thermal Cutout

Fan

Motor

120/240

Control

Circuit

Figure 3 - Wiring Diagram

Содержание CAB

Страница 1: ...2011 480 1 or 3 CAB 252 CAB 2511 65 208 or 240 3 25 12 1 20 1 8 26 1 8 21 3 4 CABB 252 CABB 2511 480 1 or 3 CABB 3011 75 480 3 30 18 2 29 1 2 21 5 8 17 1 4 CAB 402 CAB 4011 90 208 or 240 3 40 18 2 29 1 2 27 3 8 23 CABB 402 CABB 4011 480 1 or 3 CAB 502 CAB 5011 110 208 or 240 3 50 18 2 29 1 2 33 1 8 28 3 4 CABB 502 CABB 5011 480 1 or 3 CAB 752 CAB 7511 200 208 or 240 3 75 27 3 44 7 16 42 1 8 37 3 4...

Страница 2: ... all power before installing heater 1 Install heater into desired location in air duct with terminals on bottom 2 For installation where the duct heater is larger than the duct work the duct area must be increased by a sheet metal transi tion The slope of the transition piece on the upstream side is limited to 30 as indicated in Figure 2 On the leaving side the slope should not be more than 45 3 M...

Страница 3: ...ccuracy required reliability electrical rating of heater and economic considerations 5 Below is an example of standard CAB 122 480V 3P 12 kW wired with recommended back up controls Figure 3 OPERATION WARNING Users should install adequate back up controls and safety devices with their electric heating equipment Where the consequences of failure may be severe back up controls are essen tial Although...

Страница 4: ...15 12 117 013851 016 12 CABB 252 CAB 2511 117 013852 014 12 117 013852 015 12 117 013852 016 12 CABB 2511 CABB 3011 30 117 013852 012 18 CAB 402 40 117 013851 018 18 117 013851 019 18 117 013851 020 18 CABB 402 CAB 4011 117 013852 018 18 117 013852 019 18 117 013852 020 18 CABB 4011 CAB 502 50 117 013851 022 18 117 013851 023 18 117 013851 024 18 CABB 502 CAB 5011 117 013852 022 18 117 013852 023 ...

Отзывы: