Chromalox

®

(Supersedes PF412-6)

Installation, Operation

and

RENEWAL PARTS INDENTIFICATION

PF412-7

© 2010 Chromalox, Inc.

Type CAB and CABB

Forced Air Duct Heaters

Model

Dimensions (In.)

(Note 1)

(Note 2)

Weight

Volts

Phase

kW

No.

No.

(Lbs.)

Finstrips Ckts.

A

B

C

CAB-62

CAB-611

25

120, 208,

1 or 3

6

6

1

10-3/4

15-7/8 11-1/2

CABB-62

CABB-611

240 or 480

CAB-122

CAB-1211

35

208, 240 or 480 

1 or 3

12

9

1

15-3/8

18-1/2 14-1/8

CABB-122

CABB-1211

CAB-152

CAB-1511

40

208, 240 or 480

1 or 3

15

9

1

15-3/8

21-5/8 17-1/4

CABB-152

CABB-1511

CAB-202

CAB-2011

55

208 or 240

3

20

12

1

20-1/8

21-5/8 17-1/4

CABB-202

CABB-2011

480

1 or 3

CAB-252

CAB-2511

65

208 or 240

3

25

12

1

20-1/8

26-1/8 21-3/4

CABB-252

CABB-2511

480

1 or 3

——

CABB-3011

75

480

3

30

18

2

29-1/2

21-5/8 17-1/4

CAB-402

CAB-4011

90

208 or 240

3

40

18

2

29-1/2

27-3/8

23

CABB-402

CABB-4011

480

1 or 3

CAB-502

CAB-5011

110

208 or 240

3

50

18

2

29-1/2

33-1/8 28-3/4

CABB-502

CABB-5011

480

1 or 3

CAB-752

CAB-7511

200

208 or 240

3

75

27

3

44-7/16 42-1/8 37-3/4

CABB-752

CABB-7511

480

1 or 3

CAB-1002

CAB-10021

220

208 or 240

3

100

27

3

44-7/16 47-1/2 43-1/8

CABB-1002

CABB-10021

480

1 or 3

1. Iron sheath strip heaters — for sheath temperatures to 750˚F.
2. Chrome steel sheath strip heaters — for sheath temperatures to 950˚F.

Sensitive Bulb of
Thermostat

2 Holes 5/16-18 Tapped,
Each Side For Mounting

A

B

C

21/32

1-9/16”

2-1/4”

3-5/8”

Type CABB

Type CAB

3/4”

4-1/4”

2-1/4”

Special Cover for Side

or Bottom Terminals

Specifications –

Содержание CAB

Страница 1: ...2011 480 1 or 3 CAB 252 CAB 2511 65 208 or 240 3 25 12 1 20 1 8 26 1 8 21 3 4 CABB 252 CABB 2511 480 1 or 3 CABB 3011 75 480 3 30 18 2 29 1 2 21 5 8 17 1 4 CAB 402 CAB 4011 90 208 or 240 3 40 18 2 29 1 2 27 3 8 23 CABB 402 CABB 4011 480 1 or 3 CAB 502 CAB 5011 110 208 or 240 3 50 18 2 29 1 2 33 1 8 28 3 4 CABB 502 CABB 5011 480 1 or 3 CAB 752 CAB 7511 200 208 or 240 3 75 27 3 44 7 16 42 1 8 37 3 4...

Страница 2: ... all power before installing heater 1 Install heater into desired location in air duct with terminals on bottom 2 For installation where the duct heater is larger than the duct work the duct area must be increased by a sheet metal transi tion The slope of the transition piece on the upstream side is limited to 30 as indicated in Figure 2 On the leaving side the slope should not be more than 45 3 M...

Страница 3: ...ccuracy required reliability electrical rating of heater and economic considerations 5 Below is an example of standard CAB 122 480V 3P 12 kW wired with recommended back up controls Figure 3 OPERATION WARNING Users should install adequate back up controls and safety devices with their electric heating equipment Where the consequences of failure may be severe back up controls are essen tial Although...

Страница 4: ...15 12 117 013851 016 12 CABB 252 CAB 2511 117 013852 014 12 117 013852 015 12 117 013852 016 12 CABB 2511 CABB 3011 30 117 013852 012 18 CAB 402 40 117 013851 018 18 117 013851 019 18 117 013851 020 18 CABB 402 CAB 4011 117 013852 018 18 117 013852 019 18 117 013852 020 18 CABB 4011 CAB 502 50 117 013851 022 18 117 013851 023 18 117 013851 024 18 CABB 502 CAB 5011 117 013852 022 18 117 013852 023 ...

Отзывы: