INST No. INE-479-P0
Software version 1.0
-20-
6.2.2 Answer of an error message
In the case that there is no error of [6.2.1 In case of no answer] in the contents of the message from
the master and when the following faulty was detected, the code that shows the error contents is
answered as "an error message".
6.2.2-1) Format of an error message
Slave address
Function code
Function code + 80H
Function code + 80H
01
81H
Error code
03
83H
CRC (L)
04
84H
CRC (H)
05
85H
06
86H
08
88H
15
8FH
16
90H
6.2.2-2) Error code table
Error code Contents of error
Cause of an error
01H
Function code defective In case of receiving the no prescribed function code.
02H
Relative No. (Reference
No) defective
In case of receiving the no prescribed start No or setting
value No.
03H
The data number
defective
In case the number of the transmitting data that answers
to the received message is exceeding the number that
prescribed.
11H
Out of the setting value
range
In case of programming the numerical value other than
setting range that was prescribed in the reference table.
12H
Programming impossible In case of programming it, when it is not locked.
The format of the error message is as follows.
6. MODBUS protocol- Data interval/Answer at the time of abnormality
Reference