TROUBLESHOOTING GUIDE 

 

TROUBLE

 

POSSIBLE  CAUSE

 

REMEDY

 

  

REFRIGERATION   SYSTEM 

 

 

 

 
 

A.  Compressor does not 
run. 

No electric power to outlet. 

Turn on electric power outlet. 

The thermostat is misadjusted or 
defective. 

Adjust or replace the thermostat, as 
necessary. 

The line voltage is low. 

Check the line voltage.  It must be 
at  least 90% of minimum voltage. 

The compressor is defective. 

Replace the compressor. 

 

 

B.  Water is 
adequately chilled, but 
Chiller runs  excessively 
or continuously. 

Poor ventilation. 

Minimum both sides clearance 5" 

The condensers are dirty or restricted. 

Clean both condensers using a vacuum with 
brush attachment or relocate the unit to 
prevent restricting airflow across the 
condensers 

The thermostat is defective.  (the  contacts are 
shorted or the control is not adjusted properly) 

Replace or adjust the thermostat as 
necessary. 

 

The ambient temperature is high. 

It is normal for the Chiller to run 
continuously at high ambient 
temperatures. 

C.  Water is not cold 
but the Chiller 
compressor runs 
continuously.  

There has been a substantial loss in  the 
sealed system’s charge of  refrigerant. 

If refrigerant leak is suspected, return  Chiller to 
authorized service center or  factory for repair. 

The compressor is defective. 

Same as above. 

 

 

 

 

D. Water is not 
cold enough 
but the Chiller 
runs 
excessively. 

The condensers are dirty or restricted.   

Clean the condensers with vacuum and brush 
attachment.  Confirm location to allow air flow 
across the condensers. 

The cold water thermostat is set high or the Chiller is 

in a high ambient environment. 

Check the thermostat setting and adjust as 

necessary.  Lower the ambient temperature. 

Usage of the cold water system is greater  than 
the Chiller capacity. 

Inform the users of the cold water system's 
maximum capacity.   

The temperature of the supply water is too high. 

Wait for a moment until cold water is made. 

The refrigeration system is overcharged or 
undercharged. 

 

Return Chiller to authorized service center for 
refr ig era nt r echa rg e or factory for repair. 

 

There is a partial restriction in the 
refrigeration system. 

 
E. The Chiller has a short 

Check wattage.  If wattage readings are normal, the 
thermostat may be defective. 

Replace the thermostat. 
 

Содержание CHL-501

Страница 1: ...Y COMPONENTS DIAGRAM 9 ADJUSTING THERMOSTAT 10 SPECIFICATIONS 11 TROUBLESHOOTING GUIDE 12 WARRANTY SERVICE ChillerDaddyLLC Huntington IN 46750USA www ChillerDaddy com For best use of your Chiller we a...

Страница 2: ...caused the drain plug to loosen 2 LOCATION REQUIREMENTS This Chiller is intended to be installed underneath a conventional kitchen sink in a cabinet not less than 36 914mm wide inside dimension Chille...

Страница 3: ...l use 30 insulated OD faucet connection poly tube is included This insulated tube not only helps to keep the water colder but also prevents condensation from forming on the tube and running down onto...

Страница 4: ...ke sure to start with a clean tube without any foreign material free of score marks and scratches Use a utility knife with a fresh blade or Tube Cutter Do NOT use a hacksaw Step 2 Inserting the Tube W...

Страница 5: ...ng 8 PRIMARYCOMPONENTSDIAGRAM 9 ADJUSTINGTHERMOSTAT The thermostat is factory preset and requires no adjustment other than for abnormal requirements If needed the water temperature can be adjusted by...

Страница 6: ...Power 110 Volts 60Hz 3 Prong Grounded Cord Attached 1 8A 140W Motor Compressor Thermally Protected Certifications Conforms to UL Standard 399 Certified to CSA Standard C22 2 s 60335 2 24 60335 1 Refri...

Страница 7: ...the thermostat as necessary The ambient temperature is high It is normal for the Chiller to run continuously at high ambient temperatures C Water is not cold but the Chiller compressor runs continuous...

Страница 8: ...erial number Please retain your receipt or invoice as proof of purchase date and location This warranty applies only in the country in which the unit was originally sold This Limited Warranty does not...

Отзывы: