background image

Air Conditioning Centre / Martin Industries Ltd 

© 

2004 - 2009

 6 

 

Model KFR-32GW/X1c rev. 409

 

 
 

 

3b 

Installation of the Indoor Unit 

 

PLEASE NOTE: when removing the 

first

 copper   

end plug pipe (either one, as it does not matter 
which is removed first) from the back of the   
indoor unit (these are the short pieces of pipe   
with crimped and soldered ends, or end caps) 
you should hear a rush of air escaping at high   
pressure, this is completely normal, the units are 
pressurised at the factory to ensure it is leak free 
when you receive it. If you do not hear any air   
escape as the first of these pipes are undone,   
please contact us BEFORE FITTING as your unit   

may

 be faulty.   

 

Installation Procedure 
 

z

 

First check the wall and make sure that it is firm and secure. Use four suitable screws with 
suitable wall plugs to fasten the installation bracket onto the wall. Keep it level and completely flat 
to the wall otherwise it might cause water droplets to form on the plate when the air-conditioner is 
running in cooling mode. Make sure the top is well fixed at the highest points, or the bracket may 
flex. 

z

 

Decide where you are going to position your pipe-work for exiting through the wall.   

z

 

See ‘selection of the installation position’ in section 1 above for notes on different ways to position 
the copper pipes. 

z

 

The water drain pipe attached to the back of the indoor unit may be positioned at either end of the 
drip tray. There is a rubber ‘bung’ at the opposite end. Simply remove the ‘bung’ and swap it with 
the water drain pipe. Make sure that both a re-fitted securely so the do not leak any water. Use 
some PTFE plumbers tape if required to form a tight seal. 

z

 

Drill a 65mm diameter hole where you are going to exit your pipe-work through the wall of the 
building. 

Alternatively

 (if you have visible bricks on your building) remove a quarter of a brick by 

‘chain’ drilling a series of small holes joined together vertically down through a brick, then drill the 
same round the end of the mortar and knock through the quarter piece of brick. The hole should 
slant downward slightly so that your water drain pipe will have a sufficient ‘run-off’ to use gravity to 
drain the condensate water from the indoor unit to the outside of the building. (The indoor unit can 
produce over 2 litres per hour in the summer). There is a 2 metre ribbed extension pipe which 
may be used if necessary to extend the condensate drain pipe, please use a good tape to join the 
2 pipes. The extension fits on one way round only. 

z

 

Once you have decided where you will be placing your copper pipes, water drain pipe and 
electrical wires, and drilled the suitable holes for each (or combined all together into 1 hole), you 
are ready to mount the indoor unit. Depending on your pipe directions you may need to attach 
your copper pipes to the pipes on the back of the indoor unit first (refer to the section on attaching 
pipes if necessary). 

z

 

‘Hang’ the indoor unit on the 2 ‘lugs’ at the top of the mounting bracket and make sure the unit is in 
the middle of the bracket. Push the lower part of the casing against the mounting bracket until the 
2 bottom ‘latches’ on the mounting plate click into place 
on the rear of the plastic casing.   

 

3c 

Checking the water discharge   

Only attempt this procedure if you are confident you   
will be able to remove/replace the front plastic casing without 
damaging the clips at the top of the unit. If you have fitted the 
water drain pipe correctly, slightly downwards then it will 
most likely be OK anyway! 
 
 
 
 
 
 
 
 
 
 
 

 

Содержание KFR-32GW/X1c

Страница 1: ......

Страница 2: ...esponsibility of the purchaser installer The supplier manufacturer accept no responsibility for sub standard or incorrect installations Guide to the customer z The customer should make provision for a suitable power supply source the voltage should be in the range of 90 110 of the rated voltage of the system z The power supply circuit should have MCB leakage protection The power supply capacity sh...

Страница 3: ...flex Remote control with batteries Plastic tube for hole in wall Plastic round trim for hole in wall Putty to seal hole in wall Tape to wrap pipes after installation Water drain extension pipe translucent ribbed pipe Right angled black plastic hose connector for fitting to base of outdoor unit to pipe away any drips if fitting above a pathway attach standard garden hosepipe to the required length ...

Страница 4: ...ect the most suitable installation position 2 How to bend the 2 copper pipes correctly by hand 3 Installing the air conditioner 4 Connecting correctly bending the pipes 5 Expelling the air in the pipes and the indoor unit 6 Electrical Connection 7 Testing 8 Service Maintenance 9 Error Codes 10 Circuit Diagrams ...

Страница 5: ... you are not compressing them or kinking them during this pipe alignment process Once finished the foam insulation should be put back and re taped in place with a good quality waterproof tape Outdoor Unit z The outdoor unit can be positioned higher or lower than the indoor unit z The unit is designed to be weather proof however ideally the unit should be sited in the shade to avoid the heat of the...

Страница 6: ...tiny impression with your thumbs and pull down slightly with your fingertips Continue in this way making perhaps 30 or so tiny indents until you have a perfect curve Observe the pipe and check it is not depressed more than 1mm in any place Then slide back the foam insulation until it meets then tape the joint with some good waterproof tape Make all required curves in the same way 3a Installation o...

Страница 7: ...eal z Drill a 65mm diameter hole where you are going to exit your pipe work through the wall of the building Alternatively if you have visible bricks on your building remove a quarter of a brick by chain drilling a series of small holes joined together vertically down through a brick then drill the same round the end of the mortar and knock through the quarter piece of brick The hole should slant ...

Страница 8: ...he pipe over the brass cone and fasten the connection nut carefully at first by hand until tight and then with 2 spanners that fit correctly until it is tightly fastened The pipes must be tight to avoid refrigerant leaks but be careful not to damage the fittings DO NOT OVERTIGHTEN a single full pull on the spanners to the extent of your arms should be sufficient The fastening direction is shown in...

Страница 9: ...t gas may be COLD in winter not normally in summer You may possibly notice a slight oily residue on the tip of the screwdriver this is normal BUT do not worry and do not release for longer than 5 seconds even if no oil is present oil is not always seen as it may have been very settled in your system so none may be released from the valve f VERY IMPORTANT Finally open the stop and T branch TOP and ...

Страница 10: ...4 generally means a lack of refrigerant or too low pressure E5 can mean too high pressure caused by a kinked pipe or defective valve Switch off if any error codes occur and contact us immediately otherwise further damage may occur dF is not an error code it means your system is simply defrosting itself and will resume to normal operation in a few minutes time This is a standard feature and should ...

Страница 11: ...Air Conditioning Centre Martin Industries Ltd 2004 2009 10 Model KFR 32GW X1c rev 409 10 Circuit Diagrams Indoor Unit Circuit Diagram Outdoor Unit Circuit Diagram ...

Страница 12: ......

Отзывы: