Installation Instructions
PAC521N
5
INSTALLATION
The PAC521N is intended for use both in installations where an
existing finished drywall wall is present, and where the wall
surface has not been finished and the structural studs are
exposed. The wall must be finished around the opening of the
box after the box has been installed.
A 15 Amp duplex outlet may be installed into the PAC521N, and
the PAC521N must then be connected to a 15 Amp branch
circuit.
WARNING:
IMPROPER INSTALLATION CAN RESULT
DEATH OR SERIOUS PERSONAL INJURY! This accessory
should be installed by qualified personnel.
PAC521N Site Preparation
1.
Identify a suitable wall location for the accessory.
WARNING:
ELECTRICAL SHOCK HAZARD! CUTTING
OR DRILLING INTO ELECTRICAL WIRES OR CABLES
CAN CAUSE DEATH OR SERIOUS PERSONAL INJURY!
ALWAYS make certain area behind mounting surfaces is free
of electrical wires and cables before cutting, drilling, or
installing fasteners.
WARNING:
EXPLOSION AND FIRE HAZARD! CUTTING
OR DRILLING INTO GAS PLUMBING CAN CAUSE DEATH
OR SERIOUS PERSONAL INJURY! ALWAYS make certain
area behind mounting surfaces is free of gas, water, waste, or
any other plumbing before cutting, drilling, or installing
fasteners.
2.
Using a stud sensor, locate and mark studs.
NOTE:
Housing is designed to fit between two adjacent wall
studs, or in a drywall surface.
3.
If installing the PAC521N to wall studs, center and level
housing between marked studs.
4.
Using housing as a template, draw pencil line completely
around housing.
5.
Measure the marked area and compare to the dimensions
in Figure 1.
•
If measurements match continue to Step 6.
•
If measurements do NOT match, adjust markings to
match dimensions. (See Figure 1)
6.
Cut drywall on
outside
edge of line and remove.
Figure 1
Installation Into Drywall
1.
Insert PAC521N into drywall opening. (See Figure 2)
Figure 2
2.
Tighten screws on the four drywall clamps so that they are
locked in place in the drywall, and not laying flat against the
PAC521N. (See Figure 2)
PAC-521
11 ½”
(292mm)
8”
(203mm)
CUTOUT AREA
(CONFIGURATION A)
11 ½”
(292mm)
8”
(203mm)
CUTOUT AREA
(CONFIGURATION B)
1
2
1
Drywall clamp
x 4