CHIEF CMS491CP2 Скачать руководство пользователя страница 7

Installation Instructions

CMS491P2 / CMS492P2 / CMS491CP2 / CMS492CP2

7

4.

Wire the EGX-SF2 outlet box as required making sure the
wiring passes through the outlet hole in the housing. Refer to
Table 1 and Table 2 for input and output specifications. (See
Figure 2)

Table 1: Input Specifications

Table 2: Output Specifications

CAUTION:

Isolated ground-mounting means NOT

grounded. Grounding wire connection required.

IMPORTANT ! :

If a separate isolated green/yellow

ground wire is installed in the building wiring, attach it
separately to the green/yellow isolated ground wire on
box. If there is no separate green/yellow isolated ground
wire, connect green ground wire to both green/yellow
isolated ground wire and green box ground wire on box.

NOTE:

The grounding conductors serving this outlet are to be
connected to earth ground at the service equipment or
other acceptable building earth ground such as the
building frame in the case of a high-rise steel-frame
structure. Connections should be made with minimum
AWG 14 copper wire intended for use on a 15 Amp
circuit. The conductors used to connect the outlet to the
line and to ground shall not be any longer than
necessary and shall avoid unnecessary bends.

NOTE:

An insulated grounding conductor that is identical in

size and insulation material and thickness to the
grounded and ungrounded circuit supply conductors,
except that it is green with or without one or more
yellow stripes, is to be installed as part of the circuit that
supplies the outlet. Refer to Table 250-122 of the
National Electrical Code regarding the appropriate size
of the grounding conductor.

NOTE:

Pressure terminal or pressure splicing connectors and
soldering lugs used in the installation of the outlet shall
be identified as being suitable for the material of the
conductors. Conductors of dissimilar metals shall not
be intermixed in a terminal or splicing connector where
physical contact occurs between dissimilar conductors
unless the device is identified for the purpose and
conditions of use.

Figure 2

Input

Input voltage, frequency

125 V AC, 60 Hz

Input connection type

4x14 AWG stranded, UL Style
1015, CSA TEW

Input Wire colors

Black - Line

White - Neutral

Green - Box Ground

Green/Yellow - Isolated Ground

Input wire length (ft.)

1 (with a 3/4” stripped end)

Output

Output

15 A, 1875 W

Power consumption

<0.5 watt

Fuses

Thermal current interrupting circuits
are in MOVs

Quantity/Type

Duplex NEMA 5-15R Isolated Ground
Receptacle

Color/Markings

Grey with protection symbol (Orange
triangle)

box ground wire

isolated ground wire

4

(back view)

(CMS491CP2 shown as example)

housing

(3 wires - black, white, yellow/green)

(green)

WHITE

(neutral)

GREEN

(box ground)

BLACK

(line)

GREEN/YELLOW

(isolated ground)

Содержание CMS491CP2

Страница 1: ...491P2 CMS491CP2 CMS492P2 CMS492CP2 Powered Ceiling Storage Boxes Spanish Product Description German Product Description Portuguese Product Description Italian Product Description Dutch Product Description French Product Description CMS491P2 CMS492P2 CMS491CP2 CMS492CP2 ...

Страница 2: ... WARRANTY It is the installer s responsibility to make sure all components are properly assembled and installed using the instructions provided READ ALL INSTRUCTIONS BEFORE USING THIS PRODUCT DANGER TO REDUCE THE RISK OF ELECTRIC SHOCK 1 Always turn off power at source before installing the outlet WARNING TO REDUCE THE RISK OF BURNS FIRE ELECTRIC SHOCK OR INJURY TO PERSONS Always turn off power at...

Страница 3: ...Installation Instructions CMS491P2 CMS492P2 CMS491CP2 CMS492CP2 3 DIMENSIONS CMS491P2 DIMENSIONS INCHES MILLIMETERS CMS491CP2 ...

Страница 4: ...CMS491P2 CMS492P2 CMS491CP2 CMS492CP2 Installation Instructions 4 DIMENSIONS continued DIMENSIONS INCHES MILLIMETERS CMS492P2 CMS492CP2 ...

Страница 5: ...esapertar fixador Allentare il fissaggio Bevestiging losdraaien Desserrez les fixations Phillips Screwdriver Destornillador Phillips Kreuzschlitzschraubendreher Chave de fendas Phillips Cacciavite a stella Kruiskopschroevendraaier Tournevis à pointe cruciforme Adjust Ajustar Einstellen Ajustar Regolare Afstellen Ajuster A 1 EGX SF2 Power Conditioner Outlet B 1 Outlet cover Grounding screw installe...

Страница 6: ...r structure directly at an equipment grounding conductor terminal of the applicable derived system or service Where installed in accordance with the provisions of this section this equipment grounding conductor shall also be permitted to pass through boxes wire ways or other enclosures without being connected to such enclosures Informational Note Use of an isolated equipment grounding conductor do...

Страница 7: ...entical in size and insulation material and thickness to the grounded and ungrounded circuit supply conductors except that it is green with or without one or more yellow stripes is to be installed as part of the circuit that supplies the outlet Refer to Table 250 122 of the National Electrical Code regarding the appropriate size of the grounding conductor NOTE Pressure terminal or pressure splicin...

Страница 8: ...ee Figure 3 OR See Figure 4 8 Tighten two Phillips screws to secure outlet box to EGX SF2 housing See Figure 3 OR See Figure 4 Figure 3 Figure 4 9 Make sure grounding screw is properly installed See Figure 5 WARNING ELECTRICAL SHOCK HAZARD Turn off power to device before performing service or connecting to outlet Figure 5 10 Remove 6 32 x 1 2 Phillips flat head screw and lock washer from front of ...

Страница 9: ...from front of box See Figure 5 or See Figure 7 NOTE Make sure LED light on outlet box lines up with hole location on faceplate B See Figure 7 Figure 7 Outlet Box Use NOTE The PROTECTED light indicates that the surge protection circuitry is active and operational Figure 8 11 CMS491CP2 shown as example B housing box not shown for clarity lock washer LED light PROTECTED indicator light ...

Страница 10: ...CMS491P2 CMS492P2 CMS491CP2 CMS492CP2 Installation Instructions 10 ...

Страница 11: ...Installation Instructions CMS491P2 CMS492P2 CMS491CP2 CMS492CP2 11 ...

Страница 12: ...4 6918 952 894 6918 Europe A Franklinstraat 14 6003 DK Weert Netherlands P 31 0 495 580 852 F 31 0 495 580 845 Asia Pacific A Office No 918 on 9 F Shatin Galleria 18 24 Shan Mei Street Fotan Shatin Hong Kong P 852 2145 4099 F 852 2145 4477 Chief a products division of Milestone AV Technologies 8800 002794 Rev00 2016 Milestone AV Technologies www chiefmfg com 03 16 ...

Отзывы: