© 2000 Chemetron Fire Systems. All rights reserved (1/2000). Chemetron Fire Systems and Cardox are registered trademarks.
FM-200 is a registered trademark of Great Lakes Chemical Corporation.
FM-200
Gamma Series Systems
®
Stock
Number
Description
10260260
3/16 in. (5 mm) Connector 16 in. (40.6 cm) long
10260267
3/16 in. (5 mm) Connector 20 in. (50.8 cm) long
10260303
3/16 in. (5 mm) Connector 28 in. (71.1 cm) long
Pressure Gauge
Stock
Number
Description
20240041
Pressure Gauge Assembly
20610262
Pressure Gauge Assembly w/supervisory
pressure switch
Bleeder Valve - S/N 10610731
Pressure Gauge Assembly
A bleeder valve is used in the
In systems requiring more than one cylinder, a pressure
pilot line to prevent accumula-
gauge assembly is required for each cylinder other than
tion of pressure due to acciden-
the pilot cylinder as a means of visual surveillance of the
tal leakage through a solenoid
pressure condition within the cylinder.
pilot valve assembly, which, if
unvented, could cause a false
discharge of the system.
Discharge Connection Fittings - S/N 20710212
A 2 in. (50 mm) grooved elbow, nipple, and companion
coupling and gasket are used to
extend the discharge outlet
fitting of the cylinder valve to
the piping system. These fit-
tings ease assembly and
accommodate some mi-
nor differences in align-
ment.
Flexible Connector
Lengths of 3/16 in. (5 mm) flexible connectors are used to
interconnect the cylinder valve devices. These hoses have
a stainless steel wire braid cover and a Teflon liner, and are
fitted at each end with a 1/4 in. swivel flare nut.
OPTIONAL EQUIPMENT
Pressure Switch
A pressure switch is used in the system to implement the
shut down of power and various items of equipment, such
as fans; and for annunciation and alarm purposes.