When the Alarm is in “Standby" mode (see 

item 6.1), to activate this mode press and hold the 
“Тест” (Test) button for at least 3 s.  

The fact that the Alarm is in the “Mute” mode 

is confirmed by LED indicator flashing 1 time per 
10 s.  

The  Alarm  autonomously  switches  to  a 

"Standby" mode for no more than 10 minutes. 

In  order  to  switch  the  Alarm  from  a  "Mute" 

mode to  a "Standby"  mode,  you should press the 
“Тест” (Test) button again. 

7  GROUPING OF ALARMS  

7.1 

Alarms  may  be  combined  in  a  group 

if  you  are  required  that  triggering  of  one  alarm 
caused triggering of others. 

7.2 

To  combine  Alarms  in  a  group,  they 

are  to  be  connected  with  the  two-wire  loop  as 
shown in the figure: 

 

Fig. 2 Wiring of Alarm by two-wire loop 

Вх/Вых 

I/O 

 

7.3 

In order to combine Alarms in a 

group you need to remove the flap on the Alarm 
housing:  

 

Observing the polarity, connect the two-wire 

loop 

to 

the 

connector 

of 

the 

Alarm:

 To 

check  the  operation  of  Alarm  group  cause 
triggering  of  any  one  Alarm.  In  triggered  Alarm 
an intermittent audible signal activates, as well as 
frequent  flashing  of  the  optical  indicator.  All 
other Alarms must issue only audible signals. 

8  MAINTENANCE 

8.1  At  least  once  every  6  months  purge  the 

Alarm by air during 1 minute from all directions, 
using  for  this  purpose  a  vacuum  cleaner  or  a 
compressor  with  a  pressure  of  (0.5–2)  kg/cm

2

and after that test the Alarm. 

8.2  You  should  weekly  check  the  operability 

of  the  Alarm  by  pressing  the  “Тест”  (Test) 
button. 

POWER SUPPLY BATTERY 

Only for CV212-12-01 option.

 

 

9.1  When battery low, the Alarm issues 

simultaneous short audible and light signals.  
 

To  replace  the  battery,  contact  your  service 

provider.  

9.2  After the battery replacement, the Alarm 

should be tested for compliance to the item 5.4.3. 

10 DISPOSAL 

10.1 

The  Alarm  models  CV212-12, 

CV212-12-01  pose  no  danger  to  human  life  and 
health, as well as to the environment after the end 
of life.  

10.2 

After the end of life of the battery  it 

must  be  removed  and  disposed  separately  in 
accordance with legislation in forth. 

Содержание CV212-12

Страница 1: ...С Atmospheric pressure between 84 and 107 kPa 2 SPECIFICATIONS 2 1 Main technical data Sensitivity not less than 0 05 dB m Technical availability time not more than 15 seconds Power supply voltage 3V Current consumption not more than 2 µA Sound volume level at a distance of 3 m not less than 85 dB Maximum number of Alarms in a group not more than 32 Overall dimensions diameter not more than 105 mm...

Страница 2: ... Alarm shall be carried out by power tool with an operating voltage up to 42 V and a power up to 40 W having proper insulation of live circuits from the housing of the power tool 4 3 Installation replacement and de installation of the Alarm shall be carried out observing the work at height regulation 5 PRODUCT SETUP AND INSTALLATION 5 1 The Alarm shall be installed on the monitored object in accor...

Страница 3: ...indicator is flashing once every 6 minutes 6 2 Test mode Press and hold the Тест Test button until the audible signal sounds and LED indication flashes then release the button After a short time the audible signal terminates 6 3 Fire mode After the smoke level exceeds the acceptable value the Alarm is switched to a Pre alarm mode LED indicator flashes frequently next the Alarm is switched to a Fir...

Страница 4: ...eration of Alarm group cause triggering of any one Alarm In triggered Alarm an intermittent audible signal activates as well as frequent flashing of the optical indicator All other Alarms must issue only audible signals 8 MAINTENANCE 8 1 At least once every 6 months purge the Alarm by air during 1 minute from all directions using for this purpose a vacuum cleaner or a compressor with a pressure of...

Отзывы: