Make a loop measurement without tripping. For this, refer to the operating instructions of the
multifunction tester.
The loop impedance must be less than 100Ω (per the NFC 15100 or IEC 60364 standard).
2.2.2. CHECK OF THE EARTH
This measurement serves to check the connection of the charging terminal to earth.
Set the charging switch (PP) to
N.C.
and the mode switch (CP) to
A
.
Connect the installation tester to the CA 6651.
Via the Schuko
®
type connector (2P+E), for single-phase (L1, N, and PE terminals)
SET UP
OFF
OK
/
N.C.
A
Red wire to the phase (L1, L2
or L3).
Blue wire to N.
Green wire to PE.
Do not use the Schuko
®
type connector for anything other than the test. Do not connect an
electrical load to it.
Or via the L1, L2, L3, and N or PE terminals, for three-phase or if the installation tester does not
have a cord with a mains plug.
SET UP
OFF
OK
/
N.C.
A