2nd
Activation /deactivation of the secondary key function. The symbol 2nd
is displayed
on the screen.
CONFIG/
FREQUENCY
Setting measurement parameters
before
measuring:
m
Ω
AUTO – 2 wire/4 wire measurement
MANU – 2 wire/4 wire measurement – measurement current flow
direction
3 poles
AUTO – U
OUT
MANU – U
OUT
– measuring frequency – coupling (EARTH COUPLING)
4 poles
AUTO – U
OUT
MANU – U
OUT
– measuring frequency
ρ
AUTO – measuring method - U
OUT
MANU – measuring method – U
OUT
– measuring frequency
Setting measurement parameters
during
measurement in MANUAL mode:
All functions except m
Ω
: measuring frequency
m
Ω
: measurement current flow direction
DISTANCE
Only when measuring ground resistivity (
ρ
), programming distances
A
and/or
d
,
before or after measurement.
DISPLAY
Display of the various screens and results available in roll mode.
Exit of the memory function without recording.
SMOOTH
Activation / deactivation of the smoothing of measurement display.
MEM
Memorisation of a measurement and all the information relating to an address defined
by an object number (
ObJ.
) and test number (
tESt
).
An index for the following functions is automatically associated with the test
number:
1, 2, 3, 4 for coupling measurements (EARTH COUPLING).
DISTANCE for resistivity (
ρ
)
MEM needs to be pressed twice:
1
st
press: confirmation of the memorisation address (can be changed with the
and
keys).
2
nd
press: memorisation at the chosen address
MR
Reading of the values memorised.
The address (OBJ./TEST) and, as applicable, the associated index, are selected with
the and
keys.
All the information linked to the recalled measurement can be displayed with the
DISPLAY key.
Selects the parameter to be modified (in roll mode, from left to right).
The modifiable parameter flashes.
Incrementation in roll mode of the value of the flashing parameter selected.
Decrementation in roll mode of the value of the flashing parameter selected.