5. SET-UP

Used to display all parameters of the device:

 

„

the software version (internal to the device),

 

„

the hardware version (of the internal boards and components of the device),

 

„

the date format,

 

„

the time format,

 

„

activation of the audible signal,

 

„

the serial number,

To set the date and time and choose the format.

To activate or deactivate the audible signal.

SET UP

OFF

../..

 

„

the duration of lighting of the backlighting,

 

„

the duration of operation of the device before automatic switching off,

 

„

the language.

next page

Set the switch to SET-UP.

This key is used to exit from the current screen without saving.

To set the contact voltage to 25 V, 50 V (default), or 65 V.

 

„

50 V is the standard voltage (default).

 

„

25 V should be used for measurements in a damp environment.

 

„

65 V is the default voltage in some countries (Austria, for example).

Use the directional keypad to select an icon, select a field, and modify it.

OK

SET-UP

Содержание C.A 6113

Страница 1: ...C A6113 INSTALLATION TESTER E N G L I S H User s manual...

Страница 2: ...re than 600V with respect to earth in measurement category III or 300V with respect to earth in measurement category IV under shelter The protection provided by the device may be compro mised if it is...

Страница 3: ...on of phase rotation 48 3 13 Compensation for the resistance of the measurement leads 50 3 14 Adjustment of the alarm threshold 52 4 ERROR INDICATION 53 4 1 No connection 54 4 2 Out of measurement ran...

Страница 4: ...f sale 4 One measuring cable 3 safety leads 5 Three probe tips red blue and green 6 Three alligator clips red blue and green 7 Two elbowed straight safety leads red and black 8 One hand strap 9 One 4...

Страница 5: ...f the device lights Battery loading Loading completed The indicator goes off 1 2 CHARGING THE BATTERY Before the first use start by fully charging the battery The charging must be done between 10 and...

Страница 6: ...DISPLAY To adjust the contrast and the brightness of the display press the key and one of the arrow keys simultaneously Display contrast sustained press or Display brightness sustained press or 1 5 US...

Страница 7: ...n which you want the device to display messages Set the switch to SET UP OK Use the directional keypad to select the languages icon OK Press the OK key to validate your choice Select your language fro...

Страница 8: ...s and one validation key Backlight lighting and adjust ment key contrast and bright ness Help key Battery charging connector Four function keys TEST button to start the measurements Connection termina...

Страница 9: ...probe and an optional current clamp line impedance Zi test of residual current devices in ramp mode test of residual current devices in pulse mode current with an optional current clamp detection of...

Страница 10: ...op strip 7 Position of the phase on the socket outlet 2 Date and time 8 Display of measurement results 3 Alarm threshold 9 Bottom strip 4 Frequency measured 10 Name of function 5 Condition of the batt...

Страница 11: ...defective installations tested etc Help associated with the error messages Messages containing the icon invite you to look up the help for ways to eliminate the error found 3 1 3 REFERENCE POTENTIAL...

Страница 12: ...s are interchanged The L symbol is displayed as soon as the voltage is high enough UL programmable in SET UP The terminal identified as L is the one that has the highest voltage with respect to PE 3 2...

Страница 13: ...For measurements at low current 12 mA or kW the polarity is positive only 3 3 2 MAKING A MEASUREMENT To comply with standard IEC 61557 the measurements must be made at 200 mA The reversal of the curre...

Страница 14: ...re the measurement is below the alarm threshold 3 3 4 READING OF THE RESULT In the case of a 200 mA current To activate the alarm Measurement at positive polarity only Measurement at negative polarity...

Страница 15: ...hreshold The polarity of the current is positive Compensation for the resistance of the measurement leads is activated Pulse mode To see the next display page U 0 0 V 1 2 00 Hz CONTINUITY 02 10 2014 1...

Страница 16: ...the TEST button In this case the continuity measurement is not enabled Eliminate the cause of the interference voltage and start the measure ment over Another possible error is measurement of an over...

Страница 17: ...ecessary to look at the display unit to check this point SET UP OFF R Set the switch to MW Use the leads to connect the device to be tested between the COM and MW terminals of the device The object to...

Страница 18: ...leads or starting another measurement wait a few seconds for the device tested to be discharged when the symbol disappears from the display unit 3 4 4 READING OF THE RESULT Duration of the measuremen...

Страница 19: ...with connections or any other information use the help function 3 4 5 ERROR INDICATION The commonest error in the case of an insulation measurement is the presence of a voltage on the terminals If it...

Страница 20: ...se with the E and H terminals 3 5 2 MAKING A MEASUREMENT There are several measurement methods We recommend the 62 method SET UP OFF Connect the cables to the H and S terminals Power down the installa...

Страница 21: ...ent stops automatically This symbol invites you to wait while the measurement is in progress TEST Value of the alarm threshold Compensation for the resistance of the measurement leads is activated If...

Страница 22: ...rement move the S rod towards the H rod by 10 of d and make another measurement Then move the S rod again by 10 of d but towards the earth electrode The 3 measurement results must be the same to withi...

Страница 23: ...he device detects a rod resistance greater than 15 kW a voltage greater than 25 V on H or on S when the TEST button is pressed In these two cases the earth measurement is not enabled Move the rods and...

Страница 24: ...residual current devices of which the nominal current is greater than or equal to 30 mA This second measurement is used to determine ZPE The device then calculates loop resistance ZS ZL PE ZL ZPE and...

Страница 25: ...e smoothing of the signal Z R Ik To activate the alarm on ZLPE in TRIP mode or on RLPE in non tripping mode 010 00 A k A To set the alarm threshold see 3 14 As default the threshold is set to 10 kA Fo...

Страница 26: ...lculation of Ik Compensation for the resistance of the measurement leads is activated In the case of a measurement with tripping TRIP and without smoothing Value of the short circuit current Value of...

Страница 27: ...ion of the phase L and of the neutral N with respect to the protective conductor PE and displays it If necessary it then automatically switches the L and N terminals so that the line impedance measure...

Страница 28: ...alarm threshold see 3 14 As default the threshold is set to 50 W 3 7 3 CONFIGURING THE MEASUREMENT Before starting the measurement you can configure it by modifying the parameters displayed Z R Ik 010...

Страница 29: ...mpedance Value of the resistance Value of the inductance Case where the measurement is below the alarm threshold Value of the reference voltage for the calculation of Ik Programmed maximum contact vol...

Страница 30: ...cretion It then measures the potential between the PE conductor and the auxiliary rod and from it deduces RA UPI PE I I being the current chosen by the user For greater accuracy it is possible to make...

Страница 31: ...istance of the measurement leads for measurements of low values see 3 13 The device proposes choosing the voltage for the Ik calculation from among the following values ULN the measured voltage value...

Страница 32: ...rode fault voltage in the event of a short circuit Case where the measurement is above the alarm threshold Use the key to see the rest of the display of the measurement Value of the reference voltage...

Страница 33: ...se of a measurement with a low current and smoothing the first display screen is the following To see the next display page 02 19 2014 10 47 50 0 50 1 Hz R A 2 5 1 0 12 mA 6 EARTH 1P Ra Value of the a...

Страница 34: ...nts The 3 measurement results must be the same to within a few percent In this case the measurement is valid If this is not the case this means that the rod is in the zone of influence of the earth el...

Страница 35: ...t a distance of more than 25 metres from the earth electrode and connect it to the RA SEL terminal of the device The symbol is then dis played Connect the clamp to the device the symbol is displayed T...

Страница 36: ...170 ULN 270 V ULN 220 V or 230 V if 90 ULN 150 V ULN 110 V or 127 V if 300 ULN 500 V ULN 380 V or 400 V To deactivate the alarm To activate the alarm on RASEL To set the alarm threshold see 3 14 As d...

Страница 37: ...urement on live circuit are A connection error An earth rod resistance that is too high 15 kW reduce it by packing the earth around the rod and moistening it A voltage on the protective conductor that...

Страница 38: ...surements on live circuits The device then measures RA and calculates UF RA x IDN or UF RA x 2 IDN or UF ZS x 5 IDN depending on the type of test requested Once this first part of the measurement has...

Страница 39: ...ult voltage plant the auxiliary rod at a distance of more than 25 metres from the earth electrode and connect it to the RA SEL terminal of the device The symbol is then displayed Rb RN RL L N 30 mA 30...

Страница 40: ...to UL This function makes it possible to locate on the distribution panel using the audible signal the RCD protecting a remote current socket outlet typical case of a panel at a distance from the soc...

Страница 41: ...8 S T D U F 1 0 7 3 V I a 2 2 3 m A T a 1 3 8 m s Tripping current Tripping time Type of signal Type of RCD Programmed maximum contact voltage The measurement results are correct The key is used to se...

Страница 42: ...e detects the positions of the phase L and of neutral N with respect to the protective conductor PE and displays them If necessary it then automatically switches the L and N terminals so that the test...

Страница 43: ...2 IDN as default Choice of pulse current IDN x 1 IDN x 2 IDN x 5 0 5 IDN 1s or 0 5 IDN 2s The 2 values at 0 5 IDN are used to perform a non tripping test Choice of the form of the test signal signal...

Страница 44: ...the measurement is in progress RCD Ta TRIP 02 25 2014 10 47 30 mA 8 U F 1 1 4 6 V T a 1 7 1 6 m s 200 ms 50 1 Hz x2 3 10 7 READING OF THE RESULT In the case of a test in pulse mode with tripping Trip...

Страница 45: ...are probably too high First disconnect all loads from the network on which you are performing the test Then perform a second test with the current reduced in UF check as far as possible If the problem...

Страница 46: ...of the four points of connection of the clamp serve to identify the type of clamp x 1 000 or x 10 000 and the other two to measure the current Knowing the ratio of the clamp the device displays a dire...

Страница 47: ...uctor through the clamp several times to increase the measured current For help with connections or any other information use the help function The frequency is too unstable for the measurement In thi...

Страница 48: ...nect the measuring cable terminated by 3 leads to the device and to each of the phases the red to L1 the blue to L2 and the green to L3 L3 PE N L1 L2 There are no parameters to program before starting...

Страница 49: ...the case of a test of direction of phase rotation are One of the three voltages is outside the measurement range connection error The frequency is outside the measurement range For help with connecti...

Страница 50: ...zero indicates that no compensation has been determined The R 0 symbol present on the bottom strip of the display unit reminds you that the resistance of the leads is compensated 3 13 1 IN CONTINUITY...

Страница 51: ...lay unit and the icon is crossed out 3 13 5 ERROR If the resistance of the measurement leads is too high 2 5 W per lead compensation is impossible Check the connections and any junctions and leads tha...

Страница 52: ...ss the key to activate it 3 14 ADJUSTMENT OF THE ALARM THRESHOLD The device makes an audible signal and the indicator flashes in continuity resistance and insulation measurement if the measurement is...

Страница 53: ...in clear language on screen Example of error screen OK Press the OK key to erase the message Or press the help key for help in solving your problem The following screen is then displayed OK Press the...

Страница 54: ...symbol and a corresponding error message 4 5 DEVICE TOO HOT The internal temperature of the device is too high Wait for the device to cool off before making another measurement This case concerns ess...

Страница 55: ...nal protection devices are intact the display should indicate Set the switch to ZS RA SEL 50 0 50 1 Hz L PE 0 0 V L N V N PE V 6 LOOP ZS 03 07 2014 10 47 6 mA 50 0 50 1 Hz L PE V L N V N PE 0 0 V 6 LO...

Страница 56: ...nal SET UP OFF the duration of lighting of the backlighting the duration of operation of the device before automatic switching off the language next page Set the switch to SET UP This key is used to e...

Страница 57: ...rm activated Alarm threshold 2 Insulation measurement Test voltage 500 V Alarm activated Alarm threshold 500 k 3P earth resistance measurement Simple measurement no measurement of the rods Compensatio...

Страница 58: ...58 To choose the language Direction of phase rotation No configuration...

Страница 59: ...ts must be made using the battery 6 2 ELECTRICAL CHARACTERISTICS 6 2 1 VOLTAGE MEASUREMENTS Particular reference conditions Peak factor 1 414 in AC sinusoidal signal AC component 0 1 in DC measurement...

Страница 60: ...reference conditions Resistance of the leads zero or compensated Inductance of the leads zero External voltage on the terminals zero Inductance in series with the resistance zero Compensation of the...

Страница 61: ...ainty on the measurement of the test voltage 2 5 3 ct Measurement range at 50 V 0 01 7 99 M 8 00 39 99 M 40 0 399 9 M 400 1999 M Measurement range at 100 V 0 01 3 99 M 4 00 39 99 M Measurement range a...

Страница 62: ...0 399 9 400 3999 0 20 15 00 k 1 Resolution 0 01 0 1 1 10 Intrinsic uncertainty 2 5 ct 2 2 ct 10 2 ct Operating uncertainty 9 20 ct 9 5 ct Typical peak to peak measure ment current 2 4 3 mA 4 2 mA 3 5...

Страница 63: ...t 5 2 ct Intrinsic uncertainty on the inductive part 10 3 ct 10 3 ct 5 2 ct 5 2 ct Operating uncertainty on the impedance measurement 20 3 ct 12 3 ct 12 2 ct 5 2 ct 4 There is no measurement of the in...

Страница 64: ...oltage potential of the protective conductor with respect to the local earth 5 V Resistance of the voltage measurement probe 15 kW Potential of the voltage probe with respect to the PE UL Residual lea...

Страница 65: ...of the installation on the measured impedance value and on the activa tion of the smoothing filter SMOOTH If smoothing is activated SMOOTH mode the instability of the intrinsic uncertainty is then hal...

Страница 66: ...rent IDN The voltages indicated correspond to the minimum necessary mains voltage Wave for UF I 10 mA 30 mA 100 mA 300 mA 500 mA 650 mA 1000 mA Variable or 25V IDN Ramp or pulse 99 V 133 V IDN 1000 mA...

Страница 67: ...2 4 mA As default this current is 0 4 IDN Characteristics in ramp mode Range IDN 10 mA 30 mA 100 mA 300 mA 500 mA 650 mA 1000 mA Variable 6 to 999 mA Nature of the test Determination of UF Tripping te...

Страница 68: ...surement on a live circuit in non tripping mode UF is calculated as follows UF RA x ID Where ID is itself defined as follows ID IDN x K x Q With K multiplier from among the following seven possible va...

Страница 69: ...inals the device synchronizes to the frequency of this voltage allowing current measurements from 0 5 mA Characteristics with the C177A clamp Transformation ratio 10 000 1 Measurement range 0 020 3 99...

Страница 70: ...easurement Typical Maximum Temperature 10 55 C 1 10 C 1 ct 2 10 C 2 ct Relative humidity 10 85 RH at 45 C 2 3 2 ct Supply voltage 8 4 10 V 0 25 or 2 ct 2 2 ct 50 60Hz AC voltage superposed on the test...

Страница 71: ...15 8 45 Hz 45 450 Hz 1 0 5 1 1 ct 1 5 1 ct 50 60Hz series mode rejection in AC 0 500 Vac 50 dB 40 dB 6 3 6 EARTH MEASUREMENT ON LIVE CIRCUIT LOOP AND SELECTIVE EARTH Quantities of influence Limits of...

Страница 72: ...8 with E6 influence of the phase angle from 0 to 18 E7 influence of the network frequency from 99 to 101 of the nominal frequency E8 influence of the network voltage from 85 to 110 of the nominal volt...

Страница 73: ...tially discharged even if it had been fully recharged just before going into storage In this case before using it again you should fully recharge the battery at least 7 hours The longer your battery i...

Страница 74: ...follows Remove the battery compartment cover voir 8 2 Disconnect the battery connector Wait approximately 10 seconds Reconnect the battery connector to the device Put the battery compartment cover bac...

Страница 75: ...d characteristics measurement category III 600V with respect to earth or 300V in CAT IV under shelter 550V in dif ferential between the terminals and 300V CAT II on the charger input The device is in...

Страница 76: ...terminal W to terminal COM R resistance measured with a negative current flowing from terminal W to terminal COM R resistance measured alternately with a positive current then a negative current RD re...

Страница 77: ...N terminals UL PE voltage measured between the L and PE terminals UN nominal test voltage in insulation measurement generated between the MW and COM terminals UN PE voltage measured between the N and...

Страница 78: ...her than the one specified may result in damage to equipment or bodily injury by explosion or fire To keep the device safe replace the battery only with the original model Do not use a battery with a...

Страница 79: ...EL SET UP OFF Press the 3 keys indicated below simultaneously SET UP OFF OK 6 Place the battery in its compartment and arrange the wires to that they do not protrude 7 Put the battery compartment cove...

Страница 80: ...he following cases Inappropriate use of the equipment or use with incompatible equipment Modifications made to the equipment without the explicit permission of the manufacturer s technical staff Work...

Страница 81: ...3P earth kit 50 m P01102021 3P earth kit 100 m P01102022 1P earth kit 30 m black P01102018 C177 clamp 20 A P01120335 C177A clamp 200 A P01120336 MN77 clamp 20 A P01120460 Continuity pole P01102084A 10...

Страница 82: ...hai Pujiang Enerdis Instruments Co Ltd 3 Floor Building 1 N 381 Xiang De Road Hongkou District 200081 SHANGHAI Tel 86 21 65 21 51 96 Fax 86 21 65 21 61 07 ITALIA Amra SpA Via Sant Ambrogio 23 25 20846...

Отзывы: