20
2. USE
Current clamps and AmpFLEX
TM
flexible current sensors are used to measure the
current circulating in a cable without having to open the circuit. They are also used
to insulate the user from dangerous voltages in the circuit.
The choice of accessory to be used depends on the current value that is to be
measured and the diameter of the cables.
MN93
MN93A
5 A
MN93A
100 A
Measurement range *
0,05 ‑ 240 A
0,005 ‑ 6 A
0,1 ‑ 120 A
Clamping diameter
20 mm
20 mm
20 mm
C193
PAC93
Measurement range *
1 ‑ 1200 A
1 ‑ 1200 A
Clamping diameter
52 mm
39 mm
Amp
FLEX
TM
A193
450 mm
Amp
FLEX
TM
A193
800 mm
Measurement range *
10 ‑ 6500 A
10 ‑ 6500 A
Clamping diameter
120 mm
235 mm
* : The measurement ranges are those of the sensors. In some cases, they may differ
from the ranges that can be measured by the analyser with which they are associated.
For three‑phase measurements, start by marking the accessories using the col‑
oured rings supplied with the device: a different colour for each current terminal.
Connect the accessories to the current terminals of the device.
For the PAC93:
Set the switch to “1 mV/A”; the “ON” indicator lights.
Once the PAC93 is connected to the device, adjust the zero by turning the po‑
tentiometer with no conductor in the jaws of the clamp.
93
For the clamps:
Press the trigger on the clamp to open the jaws.
Then clamp the cable that is to be measured. Where possible, the cable should
be centred in the jaws of the clamp.
Release the trigger.
Содержание AmpFLEX A193
Страница 19: ...19 1 4 AMPFLEXTM A193 Flexible sensor Sensor opening device Specific 4 point plug Shielded cord...
Страница 62: ...62...
Страница 63: ...63...