![Charnwood Island 1 Скачать руководство пользователя страница 10](http://html1.mh-extra.com/html/charnwood/island-1/island-1_operating-and-installation-instructions-manual_2591976010.webp)
HEARTH AND FIRE SURROUND
The stove arrives bolted and shrink-wrapped to its pallet which is
intended to be cut up and used for kindling fuel.
The stove must stand on a fireproof hearth and combustible
materials must not be used in the construction of the fireplace unless
adequately fireproofed in accordance with local building regulations.
The hearth must be at least 12mm (0.5inches) thick. The positioning
of the stove and the size of the hearth are governed by building
regulations for Class 1 appliances. These building regulations state
that the hearth must extend in front of the stove by at least 300mm
(12 inches) and to the sides of the stove by at least 150mm (6
inches). If in doubt as to the positioning of the stove expert advice
should be sought either from the supplier or the local building
inspector.
The fireplace must allow good circulation of air around the appliance
to ensure that maximum heat is transferred to the room and also to
prevent the fireplace from overheating. A gap of 150mm (6 inches)
each side and 300mm (12 inches) above the appliance should give
sufficient air circulation. If a wooden mantelpiece or beam is used in
the fireplace it should be a minimum of 460mm (18 inches), and
preferably 600mm (24 inches) from the appliance. In some situations
it may be necessary to shield the beam or mantelpiece to protect it.
In order for the fire to operate correctly there must be an air gap
behind the appliance of at least 40mm, but be aware that this
distance will need to be greater in some cases to meet Building
Regulation requirements.
CONNECTIONS TO FLUES
There are several ways of connecting the stove to the flue. These are
illustrated in figures 4 to 7.
If a top flue connection (as shown in Fig. 6) or the vertical rear flue
connector (shown in Fig. 7) are used, then the chimney may be swept
through the appliance.
Horizontal lengths of flue must be kept to a minimum and should not
be more than the flue diameter. The sealing face of the flue collar
should be coated with fire cement before fixing to the body of the
stove using the two screws provided. The blanking plate must be
removed, sealed with fire cement and refitted, care being taken to
ensure that the fold on the clamping plate is in line with the lugs on
the firebox as shown on the label on the clamping plate. Ensure that
the clamping plate does not prevent the throat plate from seating
correctly. All flue connections must be well sealed.
Register Plate
With Soot Door
Alternative
Soot Door Positions
Fig. 6. Horizontal Register Plate With Top Flue Connection
Register Plate
With Soot Door
Alternative
Soot Door Positions
Fig. 5. Horizontal Register Plate With Rear Flue Connection
Register Plate
Soot Door
In Side or Rear
Of Chimney
Fig. 4. Vertical Register Plate With Bricked Up Fireplace
INSTALLATION INSTRUCTIONS
®
charnwood
10
I
I S L A N D
III
II
Содержание Island 1
Страница 1: ...Operating Installation Instructions charnwood I I S L A N D III II ...
Страница 2: ......
Страница 19: ......