background image

ventilate the room.
b) Let the fire out and safely dispose
of the fuel from the appliance.
c) Check for flue or chimney
blockage, and clean if required.
d) Do not attempt to re-light the fire
until cause of fume has been
identified, if necessary seek
professional advice.

The most common cause of fume
emission is flueway or chimney
blockage. For your own safety these
must be kept clean.

Check that :

a) The doors are tightly closed.
b) The aircontrols are set at the
minimum setting.
c) the thermostat flap is closed (at the
bottom of the left hand side of the
appliance, see Fig. 1.) and that it is not
prevented from closing completely by
a piece of ash,
d) The airwash control is closed.
e) A suitable fuel is being used.
f) Door seals and airwash slide are
intact.

Fire blazing out of control

Over-Firing

Freezing

Lack of Heat To

Radiators / Hot Water

If the fire is over-fired it will cause
premature failure of the internal fire
parts. Overfiring is occurring when
any parts of the fire begin to glow red.
To prevent over-firing ensure that:
a) the door seals are kept in good
condition, and that the doors are
sealing correctly,
b) the thermostat on the fire is
working correctly,
c) a suitable fuel is being used,
d) the fire is not fitted onto a heating
system which is too large.

Do not light the fire if there is any
possibility that any parts of the system
may be frozen.

Check that:
a) the fire is burning properly - if not
then carry out the checks under "Fire
Will Not Burn".
b) the throat plate is fitted correctly
(see Fig. 3.) and that it is not distorted.
c) the door seals are in good condition.

d) If the hot water goes cold when the
pump is turned on, or if some radiators
are hotter than others, then the system
may need balancing, the pump may be
pumping the water too quickly around
the system, or the radiators may need
bleeding. Please ask your installer to
check these points.

If the chimney is thoroughly and
regularly swept, chimney fires should
not occur. However, if a chimney fire
does occur turn the controls to the
minimum setting, and tightly close the
doors of the appliance. This should
cause the chimney fire to go out in
which case the controls should be kept
at the minimum setting until the stove
has gone out. The chimney and
flueways should then be cleaned. If
the chimney fire does not go out when
the above action is taken then the fire
brigade should be called immediately.

After a chimney fire the chimney
should be carefully examined for any
damage. Expert advice should be
sought if necessary.

Chimney Fires.

Page 4

Country 15B 09/03

Содержание Country 15B

Страница 1: ...stallation Instructions C H A R N W O O D B i s h o p s W a y N e w p o r t I s l e o f W i g h t P O 3 0 5 W S U n i t e d K i n g d o m T 4 4 0 1 9 8 3 5 3 7 7 9 9 F 4 4 0 1 9 8 3 5 3 7 7 8 8 c h a r n w o o d a j w e l l s c o u k w w w c h a r n w o o d c o m ...

Страница 2: ...At first you may find it helpful to try several fuels to find the most suitable If you are unable to obtain the fuel you want ask your supplier or an approved fuel distributor to suggest an alternative Use the door opening and ashpan tool to open and close the doors Turn the right hand door knob anti clockwise to open and clockwise to close see Fig 1 Your Charnwood stove is fitted with a multifuel...

Страница 3: ...ld be emptied regularly before it becomes too full Never allow the ash to accumulate in the ashpans so that it comes in contact with the underside of the grate as this will seriously damage the grate bars The ashpans are handled using the tool provided Care should be taken to ensure that ash is cool before emptying it into plastic liners or bins To make ash removal easier there is a special availa...

Страница 4: ... appliance flue outlet and the flue pipe connecting the stove to the chimney must be cleaned with a flue brush After clearing any soot from within the stove replace the throat plate see Fig 3 the front firebars and side fireplates Different types of sweep s brushes are available to suit different flueways For standard brick chimneys a wire centre sweep s brush fitted with a guide wheel is recommen...

Страница 5: ... suitable fuel is being used d the fire is not fitted onto a heating system which is too large Do not light the fire if there is any possibility that any parts of the system may be frozen Check that a the fire is burning properly if not then carry out the checks under Fire Will Not Burn b the throat plate is fitted correctly see Fig 3 and that it is not distorted c the door seals are in good condi...

Страница 6: ...t advice should be sought regarding the necessity of having the chimney lined If it is found necessary to line the chimney then a lining suitable for Solid Fuel must be used If there is no existing chimney then a prefabricated block chimney or a twin walled insulated stainless steel flue to BS 4543 can be used either internally or externally These chimneys must be fitted in accordance with the man...

Страница 7: ... as it will allow greater flexibility in the way that the system is operated as well as ensuring that there is sufficient heat Connect the heating system to the boiler ensuring that the primary flow pipe rises continuously from the appliance to the vent Fill the system with water and check for leaks The circulating pump may be controlled by means of time switches room thermostats or outdoor thermo...

Страница 8: ...ld on the clamping plate is in line with the lugs on the firebox as shown in Fig 12 Ensure the clamping plate does not prevent the throat plate from seating correctly All flue connections must be well sealed Various types and positions of soot doors are shown in figures 8 to 10 Before lighting the fire check the cold setting distance of the thermostat Remove the cover plate on the left hand side o...

Страница 9: ...llowing a suitable period of time for the fire cement and mortar to dry out the stove should be lit and checked to ensure that smoke and fumes are taken from the appliance up the chimney and emitted safely Also check all joints and seals The central heating pump should be COMMISSIONING adjusted to give the correct water flow against the circuit resistance and the system should be correctly balance...

Страница 10: ...Knob 10 012 FV14 1 Secondary Air Slide 45 012 FV10B 19 Thermostat Cover 11 012 FV14 2 Secondary Air Slide Guide 46 012 FV11 Serial No Label 12 012 FV14 3 Secondary Air Slide Retainer 47 012 FW34 Scraper Tool 13 012 FV14 4 Secondary Air Cover 48 010 TW33 Vert Rear Flue Connector Opt l Extra 14 004 FV15 Secondary Air Rod 49 010 BW51 Ash Carrier Optional Extra 15 002 EW15 Side Fire Plate 50 008 TH02 ...

Страница 11: ... a y N e w p o r t I s l e o f W i g h t P O 3 0 5 W S U n i t e d K i n g d o m T 4 4 0 1 9 8 3 5 3 7 7 9 9 F 4 4 0 1 9 8 3 5 3 7 7 8 8 c h a r n w o o d a j w e l l s c o u k w w w c h a r n w o o d c o m Your Local Charnwood Dealer ...

Отзывы: