Charmeg iQ-T Скачать руководство пользователя страница 4

 

 

Mod 

Defines if thermostat will operate with On-Off control (000) or with Auto adapt PID (001). 
In On-Off mode heating commissioning output is activated when temperature drops 
below setpoint at least as minimum as dt (differential).  

In Auto Adapt PID mode thermostat activates or deactivates the heating or cooling 
system based to repeated commissioning cycles with duration equal to HCT. Auto Adapt 
PID can achieve more accurate temperature control and thus greater economy. HCT 
parameter should be adjusted prior to Auto Adapt PID mode use. 

 
 

TRI 

Temperature reading correction parameter. Temperature reading value can be altered 

+/-5°C. To utilize that function select that parameter and adjust the value so as to show 
the correct temperature.  

dT 

Differential. Applicable only in On-Off mode (Mod=000). 

SHi 

Maximum setpoint limit. 

SLo 

Minumim setpoint limit 

Pbn 

Proportional band. Applicable only in Auto Adapt PID mode (Mod=001). 

HCT 

Time indicating the heating or cooling cycle. Enter values from 10 to 15 minutes for 
systems vulnerable to frequent activations or having big thermal inertia. Use smaller 
values for others. 

STP 

Integral step. Applicable only in Auto Adapt PID mode (Mod=001). This value is 
automatically adjusted when parameter HCT is altered. It is also possible to be adjusted 
separately. The bigger the value of the STP parameter the slower the temperature 
correction performed by the thermostat. Excessively small STP values can lead to 
opposite control result or even loss of control. 

RST 

Select this parameter in order to restore all values to the factory preset setting. 

End 

Exit form installer’s menu. 

 

 
 

 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Technical Characteristics 

(subject to alteration without prior notice) 
 

Physical dimensions 

100 x 115 x 30mm approximately

 

Power supply 

~230VAC/50Hz ±10% 

Relay contact rating 

5A/250VAC @resistive load 
(3A@inductive load) 

Adjust range

 

5 °C to +90 °C 

Differential

 

-3°C Adjustable 

Accuracy

 

+/-0.5°C 

Operation temperature

 

-10 °C to +50 °C 

Store temperature 

-20 °C to +70 °C 

 
 

Customer Care

 

Charmeg 

www.charmeg.gr 
9 Ag. Nektariou & Simachon str. Nikea- Athens- Greece 
 

Τηλ:  

+30 210 5693111

 

Φαξ: 

+30 210 5693093 

e-mail:

 [email protected] 

Skype:

 Charmeg Live Assistance Europe 

Made in Greece

 

 

Environmental Protection

 

 

This product has been manufactured from materials which can be recycled and 
reused according to the European Directive 2002/96/EC.  
Please be informed regarding the local collection system for electrical and 
electronic equipment and do not dispose the old products with your normal 

household waste. 
The correct disposal of the products will help to prevent the negative consequences of the 
environment and human health.  
 

Doc: iQT_Users_Manual_gr_en_2.docx                                                           7-Feb-16 

Figure 4- On-Off control mode (example for heating) 

Figure 5- Auto Adapt PID mode (example for heating)

 

Figure 3- Cooling mode 

Содержание iQ-T

Страница 1: ... παρατεταμένα το πλήκτρο 1 και ενώ ο θερμοστάτης βρίσκεται στην κατάσταση On εμφανίζεται ο χρόνος της αυτόματης απενεργοποίησης σε προκαθορισμένα διαστήματα 30min 1h 2h 6h Όταν εμφανιστεί ο χρόνος της επιλογής σας αφήστε το πλήκτρο 1 και ο θερμοστάτης θα αρχίσει την αντίστροφη μέτρηση στο τέλος της οποίας θα μεταβεί αυτόματα στην κατάσταση Off Κατά την αντίστροφη μέτρηση ο ενδείκτης 5 αναβοσβήνει ...

Страница 2: ...όλοιπα STP Βήμα ολοκλήρωσης Έχει εφαρμογή μόνο εφόσον ο θερμοστάτης λειτουργεί με τον τρόπο Auto Adapt PID Mod 001 Η παράμετρος ρυθμίζεται αυτόματα όταν τροποποιήσετε την παράμετρο HCT Είναι δυνατό όμως να τροποποιηθεί και μόνη της Όσο μεγαλύτερη είναι η παράμετρος αυτή τόσο πιο αργή είναι η διόρθωση που κάνει ο θερμοστάτης για να επιτύχει την επιθυμητή θερμοκρασία χώρου Υπερβολικά μικρή τιμή της ...

Страница 3: ...erformed In Off state no temperature control is performed From time to time a ZZZ message is passing through the display indicating the sleeping state of the device When 1 button is contiguously pressed in On state the delayed shut off time is shown in predefined time steps 30min 1h 2h 6h Once the time of your choice is shown release button 1 Then thermostat will initiate the countdown until shut ...

Страница 4: ...arately The bigger the value of the STP parameter the slower the temperature correction performed by the thermostat Excessively small STP values can lead to opposite control result or even loss of control RST Select this parameter in order to restore all values to the factory preset setting End Exit form installer s menu Technical Characteristics subject to alteration without prior notice Physical...

Отзывы: