LT-WIC101010
Page 16 of 16
3
rd
Printing
Alarm Block 2:
Alarm 66
Block
Block#-Pair#
Pin #
BBU Wire Color
(per local market)
Normal
Contact
State
(NC or NO)
AT&T Alarm
Label/Verbiage
Comments or
Factory/OEM Alarm
B
B
U
1
7
-20
2-1
1
WHITE/BLUE
NC
RBS DC CR
DC PLANT PCR
2
BLUE/WHITE
2-2
3
WHITE/ORANGE
NC
RBS DC MJ
DC PLANT PMJ
4
ORANGE/WHITE
2-3
5
WHITE/GREEN
NC
RBS DC HIGH VOLT
DC PLANT HV1
6
GREEN/WHITE
2-4
7
WHITE/BROWN
NC
RBS DC LOW VOLT
DC PLANT LV1
8
BROWN/WHITE
B
B
U
2
1
-24
2-5
9
WHITE/SLATE
NC
RBS FUSE FAIL
DC PLANT FA
10
SLATE/WHITE
2-6
11
RED/BLUE
NC
RBS DC RECT MJ
DC PLANT RFA
12
BLUE/RED
2-7
13
RED/ORANGE
NC
RBS DC RECT CR
DC PLANT RFA(MULT)
14
ORANGE/RED
2-8
15
RED/GREEN
NC
RBS BATT TEMP HIGH
DC PLANT HITEMP1
16
GREEN/RED
B
B
U
2
5
-28
2-9
17
RED/BROWN
(SPARE)
18
BROWN/RED
2-10
19
RED/SLATE
(SPARE)
20
SLATE/RED
2-11
21
BLACK/BLUE
(SPARE)
22
BLUE/BLACK
2-12
23
BLACK/ORANGE
NO
RBS GENERATOR
RUNNING
Gen run
24
ORANGE/BLACK
B
B
U
2
9
-32
2-13
25
BLACK/GREEN
NO
RBS GENERATOR
FUEL LOW
Gen low fuel
26
GREEN/BLACK
2-14
27
BLACK/BROWN
NO
RBS GENERATOR
SHUT DOWN
Gen shutdown
28
BROWN/BLACK
2-15
29
BLACK/SLATE
NO
RBS GENERATOR MJ
Gen major
30
SLATE/BLACK
2-16
31
YELLOW/BLUE
NO
RBS GENERATOR
FUEL LEAK
Fuel basin rupture
32
BLUE/YELLOW
2-17
33
WHITE/BLUE
NC
RBS DC CR
DC PLANT PCR
34
BLUE/WHITE
2-18
35
WHITE/ORANGE
NC
RBS DC MJ
DC PLANT PMJ
36
ORANGE/WHITE
2-19
37
38
2-20
39
40
2-21
41
42
2-22
43
44
2-23
45
46
2-24
47
48
2-25
49
50
Gray highlighted cells: fixed gen sites only