Channel Safety Systems Wyvern Скачать руководство пользователя страница 2

CHANNEL SAFETY SYSTEMS 

 

 

 

 

 

        t:  0845 884 7000   |   w: www.channelsafety.co.uk

INSTRUCTION MANUAL  - Issue 1 - 02/2014 

 

 

 

 

 

 

 

            

|   2

WYVERN CONVENTIONAL EMERGENCY LUMINAIRE

MOUNTING AND WIRING

The luminaire is suitable for both Indoor and Outdoor applications - Please make reference to the diagram below for Luminaire Assembly details.

SPECIFICATION

IP Rating

IP65

Battery Voltage

2.4V 4mAh

Duration

3 hours

Battery Format

1 x 2 cells (4.4AH Nickel-Cadmium)

Lamp

8W 12" T5

Ballast Lumen Factor

0.25

Rated lumen Output

65 lumens

Rated Supply Voltage 

230V 50Hz ±10%

Supply current

70mA (max)

Charging current

0.17-0.3 A

Discharge current

1.15 A Nominal

Ambient temperature range

0°C to +30°C and up to 80% Relative Humidity

Max continuous cell temp for 4-year battery life.

55ºC

Standards

EN60598-2-22:1999, EN55015:1996, EN61547:1996

Weight 

1.3Kg

Remove diffuser retaining screws 

Remove hinged geartray-retaining screws 

 

BESA box mounting option 

Cable entry option 

Drill start wall fixing 

Cable entry option 

Connect battery to the PCB on emergency luminaries before re-fi tting gear tray.

The luminaire should be mounted using the fi xing holes provided, on a sound fl at surface. If the luminaire is to be used in a weatherproof application, Please 

ensure that all cable entry and fi xing points are suitably sealed. Route the incoming cables around the outside of the body well away from the control gear, 

and make-off  the conductors in the gear-tray mounted terminal block.