In the refrigeration cycle, the thermostatic expansion 

valve bypass assembly check valve only allows refrigerant 

flow through the thermostatic expansion valve and into 

the evaporator coil. As the refrigerant vapor exits the coil 

at the suction line, the check valve of the drain pan loop 

check valve assembly prevents the refrigerant vapor flow 

through the drain pan loop.
Factory engineered assemblies (kits) are available for both 

shipped-loose and factory-installed at an additional cost 

to complete the reverse cycle piping and components. 

The suction line check valve assembly includes the 

suction line check valve and the piping for both the 

suction line and the connection to the drain pan loop 

inlet header. In order for the suction line check valve 

assembly to be mounted, the drain pan loop check 

valve assembly must be used. The drain pan loop check 

valve assembly includes the check valve, suction line 

tee and a bent pipe. The thermostatic expansion valve 

bypass assembly option includes the check valve, tee 

and necessary piping. In order for the thermostatic 

expansion valve bypass assembly option to be complete, 

a thermostatic expansion valve must be selected by the 

sales engineer. The thermostatic expansion valve bypass 

assembly option is dependent on the body style of the 

thermostatic expansion valves which includes the Sporlan 

SQE, SBF, EG and the Alco HFESC body styles.  The factory-

installed thermostatic expansion valve bypass assembly 

option must have the thermostatic expansion valve selection included on the order for the hot gas unit cooler.
To increase the efficiency, higher performance and greater system protection, a heat exchanger may be 

beneficial to the system. In order to use a heat exchanger, the thermostatic expansion valve bypass assembly 

option must be modified. See the piping view in Figure 2. The modification includes rerouting the pipe from the 

thermostatic expansion valve bypass check valve to the inlet connection of the liquid line to the heat exchanger. 

A pipe needs to be routed from the liquid line outlet connection of the heat exchanger to the inlet connection of 

the thermostatic expansion valve.
The electrical control option includes an adjustable defrost termination and fan delay control (DTFD) which is 

standard. For an additional cost, an optional (2) control electrical system is available with one adjustable control 

for defrost termination (DT) and one fixed control for the fan delay (FD). For both the DTFD and DT adjustable 

controls, the remote bulb position is with the bulb strapped to the piping of the thermostatic expansion valve 

bypass assembly option between the distributor sideport and the check valve. When the thermostatic expansion 

valve bypass assembly is shipped-loose, the installer will need to position the remote bulb. When the thermostatic 

expansion valve bypass assembly is factory-installed, the remote bulb should already be properly installed.

Hot Gas Reverse Cycle Kits (cont.)

Содержание Air Defrost RLC

Страница 1: ...www chandlerref com LOW PROFILE UNIT COOLER Technical Guide Models RLC Air Defrost ELC EFC Electric Defrost GLC Hot Gas Defrost CH LOPTB May 2008 Replaces CH B 15B March 2004y 2007...

Страница 2: ...ercial Refrigeration Parts Because they re a drop in replacement for existing shaded pole and PSC motors installation is quick and easy It s a high impact quick payback solution for reducing costs and...

Страница 3: ...in end compartments On 4 6 fan models drain pan has a lanyard for easy and safe access Motors Motors plug into wiring harness for easier servicing EC motors available factory installed or as a drop i...

Страница 4: ...0 10 840 6 3 900 6 627 Model RLC Air Defrost 50 Hz Model Capacity Fan Data 10 F TD 25 F SST 6 C TD 4 C SST No CFM m3 H BTUH Watts RLC040 3 800 1 112 1 670 1 117 RLC052 4 940 1 445 1 630 1 070 RLC065 6...

Страница 5: ...tor EC Motor 115 1 60 208 230 1 60 115 1 60 208 230 1 60 460 1 60 115 1 60 208 230 1 60 Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts RLC040 1 15 1 8 116 1 0 122 1 0 82...

Страница 6: ...SST 6 C TD 29 C SST No CFM m3 H BTUH Watts 6 Fins Per Inch ELC035 3 325 974 1 630 1 070 ELC040 3 800 1 113 1 630 1 070 ELC047 4 465 1 308 1 586 995 ELC065 6 175 1 809 2 1 260 2 142 ELC075 7 125 2 087...

Страница 7: ...468 2 0 236 3 600 15 7 9 0 7 8 EFC170 1 15 5 0 610 2 5 455 2 0 585 2 5 295 4 500 19 6 11 3 9 8 EFC204 1 15 6 0 732 3 0 546 2 4 702 3 0 354 5 400 23 5 13 6 11 7 EFC235 1 15 6 0 732 3 0 546 2 4 702 3 0...

Страница 8: ...35 3 325 974 1 630 1 070 GLC040 3 800 1 113 1 630 1 070 GLC047 4 465 1 308 1 586 995 GLC065 6 175 1 809 2 1 260 2 142 GLC075 7 125 2 087 2 1 170 1 989 GLC090 8 550 2 504 2 1 170 1 989 GLC120 11 400 3...

Страница 9: ...468 3 8 228 2 1 236 1 200 10 4 5 2 2 6 GLC170 1 15 9 0 580 5 0 610 5 0 410 2 5 455 2 0 585 4 7 285 2 6 295 1 500 13 0 6 5 3 3 GLC204 1 15 10 8 696 6 0 732 6 0 492 3 0 546 2 4 702 5 6 342 3 1 354 1 800...

Страница 10: ...FC Electric Defrost Model No of Fans Connections in Approx Net Wt Coil Inlet OD Suction ID External Equalizer OD Drain MPT lbs kg 6 Fins Per Inch ELC035 1 1 2 5 8 1 4 3 4 24 11 ELC040 1 1 2 5 8 1 4 3...

Страница 11: ...Inlet ODF Suction ID External Equalizer OD Drain MPT Side Port OD Hot Gas Pan Conns OD lbs kg 6 Fins Per Inch GLC035 1 5 8 5 8 1 4 3 4 3 8 5 8 26 12 GLC040 1 5 8 5 8 1 4 3 4 3 8 5 8 28 13 GLC047 1 5 8...

Страница 12: ...104 2 45 50 1 155 7 33 25 845 120 075 068 2 45 50 1 155 7 33 25 845 130 090 080 2 45 50 1 155 7 33 25 845 140 120 102 3 61 50 1 562 1 49 25 1 251 156 3 61 50 1 562 1 49 25 1 251 180 140 3 61 50 1 562...

Страница 13: ...ordered For hot gas models with the hot gas loop drain pan ONLY NOTE The drain pan check valve kit can be ordered as an independent item But the suction line check valve kit must be ordered with the...

Страница 14: ...SC body styles The factory installed thermostatic expansion valve bypass assembly option must have the thermostatic expansion valve selection included on the order for the hot gas unit cooler To incre...

Страница 15: ...es engineer In a typical 3 pipe multiple evaporator system the compressor discharge defrosts the evaporator The liquid vapor mixture of refrigerant after defrost however returns to the common suction...

Страница 16: ...0 3 24752504 600 W 208 230 1 60 4 24752505 750 W 208 230 1 60 5 24752506 900 W 208 230 1 60 6 Electrical Components Part Description No Fans 22512601 Terminal Strip 1 6 5709L Defrost Termination Fan D...

Страница 17: ...280 6 3 16 15 10 L 3 L 2 L 2 1 2 L 2 4 Fins Per Inch EFC041 1 3 16 15 2 L 1 2 L 1 3 L 1 3 L 1 4 EFC068 2 3 16 15 4 L 3 4 L 1 2 L 1 2 L 1 3 EFC080 2 3 16 15 4 L 1 L 3 4 L 3 4 L 1 2 EFC102 3 3 16 15 5 L...

Страница 18: ...18 Notes...

Страница 19: ...19 Notes...

Страница 20: ...1 FAX 770 465 5990 www chandlerref com Since product improvement is a continuing effort we reserve the right to make changes in specifications without notice For more information on Chandler refrigera...

Отзывы: