background image

— 5 —

Interpretation of ARVI readings on Overhead

Reading

Appropriate line-to-line voltage class

No Indication

Voltage below line-to-line voltage class

Circuit Condition

Energized

De-Energized

Probably de-energized and read-
ing is due to static; however, do not
assume that circuit is de-energized.
Instead, check and confirm circuit
condition by another method.

All interpretations should take into account the circuit configuration, length, proximity
to other lines; and should be consistent with previous experience on same circuit with this
instrument.  If ever in doubt about interpreting ARVI reading under any circumstance,
always assume circuit is energized and take appropriate safety precautions.

Do not allow universal fitting to touch any part of URD cabinet, to become grounded
in any other way, or to contact another phase as this will cause erroneous voltage
indication and could cause severe personal injury or damage to equipment.

Operation — Underground (URD)  C403-3374 ONLY

Always use appropriate length stick even if wearing rubber gloves.

Contact with universal ferrule or other part even with rubber gloves will cause
erroneous voltage indication.

Always use with a universal pole of proper length to maintain its calibration.

When using the ARVI on underground systems, the same basic rules and
procedures apply as with overhead; for example, maintaining proper working
clearances to all parts of the tool, keeping tool clean and dry. However, the
following are two additional instructions when using the tool on underground
equipment. The readings taken in URD cabinets will typically be higher than on
an overhead line.

Do not use any probes on the ARVI when testing live-front URD equipment.

Failure to follow this warning could result in personal injury or damage to equipment.

Turn unit on by pushing and releasing the power switch.
3.  Make contact with the line to be measured with the shepherd hook per the

following instructions:

a.  Keep ARVI perpendicular to the phase conductor.
b.  Keep ARVI away from poles or structures a distance at least twice the

circuit’s phase spacing, i.e. test out on span rather than near structure,
jumpers, risers, cutouts, insulators, ground wires and any system com-
ponents other than the conductor being tested.

c.  Test three or four locations to check consistency. Where little or no

consistency is apparent, consider the highest reading as correct.

4.  If the ARVI is left on the conductor for approximately 15 seconds, it will go into

the Auto-Hold mode and hold the voltage indication until reset (see Auto-Hold
section of these instructions).

!

CAUTION

!

WARNING

!

WARNING

Содержание C403-3374

Страница 1: ...to installation operation or maintenance Should additional information and details be desiredorifsituationsarisewhicharenotcoveredadequatelyfortheuser spurpose the specifics should be referred to Hubbell Power Systems Chance Before operating a CHANCE Auto Ranging Voltage Indicator thoroughly read understand and follow these instructions Keep these instructions in the device case for future referen...

Страница 2: ...ible open gaps dispatcher hold orders and apparatus tag outs have rendered the circuit de energized Operation General To turn the unit on press and release the Power push button Upon power up each LED will illuminate individually from the lowest voltage to the highest followed by the audible alarm These tests verify the function of the LED s alarm batteries and internal circuitry Full unit functio...

Страница 3: ... from all system components other than the specific conductor being tested Auto Hold The ARVI has a hold feature built into the circuitry which automatically holds a reading when the unit is left on an energized conductor or senses constant voltage for a period of approximately 15 seconds In the hold mode the LED representing the voltage range being indicated will become solid The audible beeping ...

Страница 4: ...her part even with rubber gloves will cause erroneous voltage indication Always use with a universal pole to maintain its calibration Test phase Electromagnetic action of current Both can induce a high static condition on the de energized circuit Activity shown between only two conductors for clarity here Similar effects exist between all conduc tor pairs ARVI indicates the combined field intensit...

Страница 5: ...per length to maintain its calibration When using the ARVI on underground systems the same basic rules and procedures apply as with overhead for example maintaining proper working clearances to all parts of the tool keeping tool clean and dry However the following are two additional instructions when using the tool on underground equipment The readings taken in URD cabinets will typically be highe...

Страница 6: ...ull elbow with elbow pullertool thenorientelbowsoitisaccessiblewithARVI Operator 2 install elbow adapter on ARVI then insert elbow adapter into elbow to check elbow cable for voltage 1 Due to the close proximity of energized parts and grounded surfaces probes must not be used when using the ARVI on live front URD equipment because probes could either bridge from phase to phase or phase to ground o...

Страница 7: ...k of the panel noting proper polarity CAUTION Ensure that the wires connected to the orange connector in the panel assembly remains connected and arenotdamagedandthebatterystrapissecure Afterthepanelandscrews are replaced in the housing test the function of the unit on a known energized voltage source or with the Voltage Indicator Tester After replacing batteries ensure that the wires connected to...

Страница 8: ...le Bag for two 8 universal poles Auto Ranging Voltage Indicator 600V 69kv C403 3409 T403 0857 T403 0856 Repair If repair calibration or parts are required please contact M W Bevins Co 9903 E 54th St Tulsa OK 74146 918 627 1273 918 627 1294 FAX www mwbevinsco com Specifications Operating temp 20 to 80 C Unit power Four 4 AAA batteries C403 3409 Voltage Indicator Tester Care The ARVI is an electroni...

Отзывы: