background image

100554 - 3500W WIRELESS START GENERATOR

STORAGE

27

A trickle charger or battery maintainer should be used to charge 
the battery while the generator is in storage. Maximum charging 
rate should not exceed 1.5 amps. Follow the instructions 
included with the trickle charger or battery maintainer. 
The battery should be fully charged at least once per month.

Remote Control Battery

"

 

NOTICE

 

Always purchase the correct size and grade of battery 
most suitable for the intended use. 

 

Clean the battery contacts and also those of the device 
prior to battery installation. 

 

Remove batteries from equipment which is not to be 
used for an extended period of time. 

 

Remove batteries if consumed or if product is to be left 
unused for a long time.

Maintenance Schedule

Follow the service intervals indicated in the following 
maintenance schedule. 

Service your generator more frequently when operating in 
adverse conditions. 

Contact our Technical Support Team at 1-877-338-0999 
to locate the nearest CPE certified service dealer for your 
generator or engine maintenance needs.

EVERY 8 HOURS OR PRIOR TO EACH USE

 

#

Check oil level

 

#

Clean around air intake and muffler

FIRST 5 HOURS (BREAK IN)

 

#

Change oil

EVERY 50 HOURS OR ANNUALLY

 

#

Clean air filter

 

#

Change oil if operating under heavy load or in hot 
environments

EVERY 100 HOURS OR ANNUALLY

 

#

Change oil

 

#

Clean/adjust spark plug

 

#

Check/adjust valve clearance*

 

#

Clean spark arrestor

 

#

Clean fuel tank and filter*

EVERY 250 HOURS

 

#

Clean combustion chamber**

EVERY 3 YEARS

 

#

Replace fuel line*

* To be performed by knowledgeable, experienced owners or CPE certified 

service centers.

STORAGE

!

 

DANGER

Gasoline vapors are highly flammable and extremely 
explosive.

Fire or explosion can cause severe burns or death. Only 
fill or drain fuel outdoors in a well-ventilated area. DO NOT 
pump gasoline directly into the generator. Use an approved 
container to transfer the fuel to the generator. Never use 
a gasoline container, gasoline tank, or any other fuel item 
that is damaged or appears damaged. DO NOT overfill the 
gasoline tank. Always keep fuel away from sparks, open 
flames, pilot lights, heat and other sources of ignition. 
DO NOT light or smoke cigarettes.

Short Term Storage (up to 30 days)

Gasoline may gum up and clog the carburetor if the generator is 
not run or carburetor drained within 4 weeks.

1.  Be sure all appliances are disconnected from the generator.

2.  Start the generator as instructed in “Starting the Engine” 

section.

3.  Turn the fuel valve to the “OFF” position.

4.  Let the engine run until fuel starvation has stopped the 

engine. This usually takes a few minutes.

5.  Move the ignition switch to the “OFF” position.

Mid Term Storage (30 days – 1 year)

Gasoline in the tank has a maximum shelf life of up to 1 year 
with the addition of a properly formulated fuel stabilizer and 
stored in a cool, dry place.

1.  Be sure all appliances are disconnected from the generator.

2.  Add a properly formulated fuel stabilizer to the gasoline 

tank.

3.  Turn the fuel valve to the “ON” position.

4.  Start and run the generator for 10 minutes so the treated 

gasoline cycles through the fuel system.

Содержание 100554

Страница 1: ...ore operating the product Failure to do so could result in serious injury This manual should remain with the product Specifications descriptions and illustrations in this manual are as accurate as kno...

Страница 2: ...g the Engine 20 Battery 22 Connecting Electrical Loads 22 Do Not Overload Generator 23 Stopping the Engine 23 Operation at High Altitude 24 Maintenance 25 Cleaning the Generator 25 Changing the Engine...

Страница 3: ...ays exercise common sense and always err on the side of caution when operating the product to ensure no accident property damage or injury occurs We want you to continue to use and be satisfied with y...

Страница 4: ...ing parts can entangle hands feet hair clothing and or accessories Traumatic amputation or severe laceration can result Keep hands and feet away from rotating parts Tie up long hair and remove jewelry...

Страница 5: ...ceration Broken bones fractures bruises or sprains could result When starting engine pull the starter cord slowly until resistance is felt and then pull rapidly to avoid kickback DO NOT start or stop...

Страница 6: ...to relieve pressure in the tank Only fill or drain gasoline outdoors in a well ventilated area DO NOT pump gasoline directly into the generator at the gas station Use an approved container to transfer...

Страница 7: ...y Symbols C UNLEADED FUEL ONLY Minimum octane rating of 85 Maximum 10 ethanol GASOLINA REGULAR SOLAMENTE 85 octanos como m nimo M ximo de etanol de 10 ESSENCE SANS PLOMB SEULEMENT Indice d octane mini...

Страница 8: ...efore operation Electric Shock Failure to use in dry conditions and to observe safe practices can result in electric shock Improper connections to a building can allow current to backfeed into utility...

Страница 9: ...ng Proper interpretation of these symbols will allow you to more safely operate the product SYMBOL MEANING ON START STOP or OFF Battery ON Battery OFF Locking Receptacle RV Ready Receptacle Circuit Br...

Страница 10: ...ion 4 Press ignition switch to the ON position 5 Move choke lever to CHOKE position 6 Pull the recoil starter 7 Move the choke lever to RUN position 8 Plug in desired device Stopping the Engine 1 Turn...

Страница 11: ...gine by filtering dust and debris from the intake air 4 Recoil Starter Used to manually start the engine 5 Never Flat Wheels 8 in 20 3 cm 6 Oil Fill Cap Dipstick Used to check and fill oil level 7 Bat...

Страница 12: ...h Reset Protects the generator against electrical overloads RECEPTACLES A W 120V AC 30A Locking NEMA L5 30R May be used to supply electrical power for operation of 120 Volt AC 30 Amp single phase 60 H...

Страница 13: ...hertz Example 60 0 hertz Run Time R Run time of the generator for the current session Example 6 hours Total Run Time Total run time of the generator since first operation Example 16 hours Intelligauge...

Страница 14: ...Control Panel voltage off before the engine shutdown protects connected appliances from being damaged by non 60 Hz voltage while the generator coasts to a stop The on off voltage delay at startup and...

Страница 15: ...sembly Parts Wheels 8 in 20 3 cm Never Flat Wheel A 2 Roll Pin B 2 Large R clip C 2 Engine Vibration Mounts Support Leg with Vibration Mounts D 1 Flange Bolt M8 16 E 2 Flange Lock Nut M8 F 2 Folding H...

Страница 16: ...il or gasoline to the generator NOTICE DO NOT attempt to run generator without first removing the shipping support brackets Damage to the generator as a result of not removing the brackets will void t...

Страница 17: ...mage to the generator as a result of failing to follow these instructions will void your warranty NOTICE The generator rotor has a sealed pre lubricated ball bearing that requires no additional lubric...

Страница 18: ...n rings After the 5 hour break in period change the oil NOTICE Synthetic oil may be used after the 5 hour initial break in period Using synthetic oil does not increase the recommended oil change inter...

Страница 19: ...nd terminal connected to the frame of the generator has been provided see Controls and Features for terminal location For remote grounding connect of a length of heavy gauge 12 AWG minimum copper wire...

Страница 20: ...ng and breathing space are not supplied or if the generator is blocked or enclosed temperatures can become extremely heated and may lead to fire Surge Protection Electronic devices including computers...

Страница 21: ...tart If the engine fails to start within five seconds release the switch and wait at least ten seconds before attempting to start the engine again CAUTION If the ignition switch is held down in the ST...

Страница 22: ...t only A safety feature is provided which delays the electrical power availability during starting mode The delay lasts for approximately 15 seconds The delay is provided to prevent damage to the gene...

Страница 23: ...of power needed to start some electric driven equipment Following the steps listed under Power Management will guarantee that only one device will be starting at a time Power Management Use the follo...

Страница 24: ...nrichment of the air fuel ratio Other high altitude issues can include hard starting increased fuel consumption and spark plug fouling To alleviate high altitude issues other than the natural power lo...

Страница 25: ...tor 4 Inspect all air vents and cooling slots to ensure that they are clean and unobstructed To prevent accidental starting remove and ground the spark plug wire before performing any service Changing...

Страница 26: ...ne is equipped with a spark arrestor Adjusting the Governor WARNING Tampering with the factory set governor will void your warranty The air fuel mixture is not adjustable Tampering with the governor c...

Страница 27: ...50 HOURS Clean combustion chamber EVERY 3 YEARS Replace fuel line To be performed by knowledgeable experienced owners or CPE certified service centers STORAGE DANGER Gasoline vapors are highly flammab...

Страница 28: ...completely before continuing 2 Use the drain bolt on the carburetor to empty any excess gasoline from the gasoline tank and carburetor into an appropriate container Use a funnel and appropriate hose i...

Страница 29: ...6 7 37 8 48 9 10W 30 5W 30 Synthetic 10W 40 5W 30 NOTICE Temperature will affect engine oil and engine performance Change the type of engine oil used based on the temperature to suit the engine needs...

Страница 30: ...100554 3500W WIRELESS START GENERATOR SPECIFICATIONS 30 Parts Diagram...

Страница 31: ...hing 12 9 13 4 Part Number Description Qty 33 100032369 Vibration Mounting Fuel Tank 4 34 100010439 0001 Washer 6 5 2 25 Black 4 35 100011268 0002 Flange Bolt M6 25 Black 5 36 100009075 Rubber Damper...

Страница 32: ...Cable Clamp 1 83 1ZC7DF0N2 Engine 208 cc 1 84 100021030 Holder Air Cleaner 1 85 100000658 Clamp 2 2 86 100005148 Clamp 1 1 87 100095515 Connection Tube 1 800 mm 1 88 100095519 Connection Tube 2 245 mm...

Страница 33: ...100554 3500W WIRELESS START GENERATOR SPECIFICATIONS 33 Engine Parts Diagram...

Страница 34: ...02 Flange Bolt M5 14 6 36 100004795 Gasket Air Filter Cover 1 37 100004770 Air Filter Element 1 38 100004873 Air Filter Cover 1 Part Number Description Qty 39 100011452 0003 Lock Nut M6 Flange 2 40 10...

Страница 35: ...00004217 Bushing 8 12 8 1 93 100009400 Charge Coil 1 94 100011269 0003 Bolt M6 28 2 95 100009535 Flywheel 1 96 100007028 Cooling Fan 1 97 100007550 Pulley Starter 1 98 100011459 0003 Flange Nut M14 1...

Страница 36: ...100554 3500W WIRELESS START GENERATOR SPECIFICATIONS 36 Wiring Diagram...

Страница 37: ...sition Turn battery switch to ON position Generator shuts down during operation Out of fuel Fill fuel tank Low oil level Fill crankcase to the proper level Place generator on a flat level surface Gene...

Страница 38: ...nt Normal maintenance is not covered by this warranty and is not required to be performed at a facility or by a person authorized by CPE Other Exclusions This warranty excludes Cosmetic defects such a...

Страница 39: ...t to you including diagnosis parts and labor MANUFACTURER S WARRANTY COVERAGE This exhaust and evaporative emission control system is warranted for two years If any exhaust and evaporative emission re...

Страница 40: ...ed for the period of time prior to the first scheduled replacement point for that part If the part fails prior to the first scheduled replacement the part shall be repaired or replaced by CPE accordin...

Страница 41: ...ve Controls Fuel Tank Fuel Cap Fuel Lines for liquid fuel and fuel vapors Fuel Line Fittings Clamps Pressure Relief Valves Control Valves Control Solenoids Electronic Controls Vacuum Control Diaphragm...

Отзывы: