100538 - 7500W PORTABLE GENERATOR

OPERATION

17

3.  Do not over-choke. As soon as engine starts, move the 

choke to the “RUN” position over a 2-5 second duration.

!

 

CAUTION

If the ignition switch is held down in the “START” position 
longer than 5 seconds it could damage the starter.

Manual Start

1.  Push the ignition switch to the “ON” position. 

2.  Pull the starter cord slowly until resistance is felt and then 

pull rapidly.

3.  Do not over-choke. As soon as engine starts, move the 

choke to the “RUN” position over a 2-5 second duration.

"

 

NOTICE

Keep choke in “CHOKE” position for only 1 pull of the recoil 
starter. After first pull, move choke to the “RUN” position for 
up to the next 3 pulls of the recoil starter. Too much choke 
leads to spark plug fouling/engine flooding due to the lack of 
incoming air. This will cause the engine not to start.

"

 

NOTICE

For gasoline restarts with hot engine in hot ambient 
> 30°C (86°F):

 Keep the choke in 75% of the “CHOKE” 

position for only 1 pull of the recoil starter. After first pull, 
move choke to the “RUN” position for up to 3 more pulls 
of the recoil starter. Too much choke leads to spark plug 
fouling/engine flooding due to the lack of incoming air. This 
will cause the engine not to start.

"

 

NOTICE

For gas starting in cold ambient <15°C (59°F):

 the choke 

must be in 100% of the “CHOKE” position for recoil start 
procedures. Do not over-choke. As soon as engine starts, 
gradually move the choke lever to the “RUN” position over a 
2-5 second duration.

"

 

NOTICE

If the engine starts but does not run make certain that the 
generator is on a flat, level surface. The engine is equipped 
with a low oil sensor that will prevent the engine from 
running when the oil level falls below a critical threshold.

Connecting Electrical Loads

Let the engine stabilize and warm up for a few minutes after 
starting.

Plug in and turn on the desired 120 or 240 (if applicable) Volt AC 
single phase, 60 Hz electrical loads.

 

DO NOT connect 3-phase loads to the generator.

 

DO NOT connect 50 Hz loads to the generator.

 

DO NOT overload the generator.

!

 

WARNING

Connecting a generator to your electric utility company’s 
power lines or to another power source may be against 
the law. In addition this action, if done incorrectly, could 
damage your generator and appliances and could cause 
serious injury or even death to you or a utility worker who 
may be working on nearby power lines. If you plan to run a 
portable electric generator during an outage, please notify 
your electric utility company immediately and remember to 
plug your appliances directly into the generator. Do not plug 
the generator into any electric outlet in your home. Doing 
so could create a connection to the utility company power 
lines. You are responsible for ensuring that your generator’s 
electricity does not feed back into the electric utility power 
lines.

If the generator will be connected to a building electrical 
system, consult your local utility company or a qualified 
electrician. Connections must isolate generator power from 
utility power and must comply with all applicable laws and 
codes.

Do Not Overload Generator

Capacity

Follow these simple steps to calculate the running and starting 
watts necessary for your purposes: 

1.  Select the electrical devices you plan on running at the 

same time.

2.  Total the running watts of these items. This is the amount 

of power you need to keep your items running.

3.  Identify the highest starting wattage of all devices 

identified in step 1. Add this number to the number 
calculated in step 2. Starting wattage is the extra burst 
of power needed to start some electric driven equipment. 
Following the steps listed under “Power Management” will 
guarantee that only one device will be starting at a time.

Содержание 100538

Страница 1: ...g the product Failure to do so could result in serious injury This manual should remain with the product Specifications descriptions and illustrations in this manual are as accurate as known at the ti...

Страница 2: ...tor 17 GFCI 18 Stopping the Engine 18 Operation at High Altitude 18 Maintenance 19 Cleaning the Generator 19 Changing the Engine Oil 19 Cleaning and Adjusting the Spark Plug s 20 Cleaning the Air Filt...

Страница 3: ...re each use Please always exercise common sense and always err on the side of caution when operating the product to ensure no accident property damage or injury occurs We want you to continue to use a...

Страница 4: ...Keep hands and feet away from rotating parts Tie up long hair and remove jewelry Operate equipment with guards in place DO NOT wear loose fitting clothing dangling drawstrings or items that could beco...

Страница 5: ...T modify the generator in any way CAUTION Start the generator and allow the engine to stabilize before connecting electrical loads Connect electrical equipment in the off position and then turn them o...

Страница 6: ...ly fill or drain gasoline outdoors in a well ventilated area DO NOT pump gasoline directly into the generator at the gas station Use an approved container to transfer the fuel to the generator DO NOT...

Страница 7: ...practices can result in electric shock Improper connections to a building can allow current to backfeed into utility lines creating an electrocution hazard A transfer switch must be used when connect...

Страница 8: ...t oil Always check the oil level before using The machine must be resting firmly on level ground when checking Fuel Valve ON Ignition Switch ON Press the Ignition Switch to ON position Choke Move chok...

Страница 9: ...re open DANGER Using a generator indoors CAN KILL YOU IN MINUTES Generator exhaust contains carbon monoxide This is a poison you cannot see or smell 1028 L SF B Safety Icons CO Danger B UNLEADED FUEL...

Страница 10: ...engine 4 Air Filter Protects the engine by filtering dust and debris from the intake air 5 Recoil Starter Used to manually start the engine 6 Never Flat Wheels 9 5 in 24 1 cm 7 Battery Provides 12V DC...

Страница 11: ...rloads RECEPTACLES A C 4 120V AC 20A GFCI NEMA 5 20R May be used to supply electrical power for operation of 120 Volt AC 20 Amp single phase 60 Hz electrical loads B Y 120 240V AC 30A Locking NEMA L14...

Страница 12: ...arts Wheels 9 5 in 24 1 cm Never Flat Wheel A 2 Roll Pin B 2 Large R clip C 2 Engine Vibration Mounts Support Leg with Vibration Mounts D 1 Flange Bolt M8 16 E 2 Flange Lock Nut M8 F 2 Folding Handle...

Страница 13: ...is not intended for over the road use 1 Before adding fuel and oil tip the generator on it s end 2 Slide the Roll Pin B through the Wheel A from the outside 3 Slide the Roll Pin through the mount poi...

Страница 14: ...sual check should show oil about 1 2 threads from running out of the fill hole If using the dipstick to check oil level DO NOT screw in the dipstick while checking NOTICE Check oil often during the br...

Страница 15: ...ck of gasoline at the operator while filling NOTICE Our engines work well with 10 or less ethanol blend gasoline When using ethanol gasoline blends there are some issues worth noting Ethanol gasoline...

Страница 16: ...ecome hot If adequate cooling and breathing space are not supplied or if the generator is blocked or contained temperatures can become extremely heated and may lead to fire Grounding A ground terminal...

Страница 17: ...bilize and warm up for a few minutes after starting Plug in and turn on the desired 120 or 240 if applicable Volt AC single phase 60 Hz electrical loads DO NOT connect 3 phase loads to the generator D...

Страница 18: ...store the flow of electricity If the indicator light does not come back on or if the GFCI cannot be reset then it must be replaced A C B Stopping the Engine 1 Turn off and unplug all electrical loads...

Страница 19: ...ms may be performed by any non road engine repair establishment or individual The owner operator is responsible for all periodic maintenance Complete all scheduled maintenance in a timely manner Corre...

Страница 20: ...e muffler 3 Remove the spark arrestor screen 4 Carefully remove the carbon deposits from the spark arrestor screen with a wire brush Type 1 Type 2 See your model s parts list for specified type of spa...

Страница 21: ...ERY 8 HOURS OR DAILY Check oil level Clean around air intake and muffler FIRST 5 HOURS Change oil EVERY 50 HOURS OR EVERY SEASON Clean air filter Change oil if operating under heavy load or in hot env...

Страница 22: ...t to avoid spillage 3 When gasoline stops flowing from the carburetor replace and tighten the carburetor drain bolt and be sure to properly dispose of the drained gasoline according to local regulatio...

Страница 23: ...of 85 and an ethanol content of 10 or less by volume DO NOT USE E15 or E85 DO NOT OVERFILL Gasoline Capacity 5 7 gal 21 5 L Spark Plug Specifications OEM Type NHSP F6RTC Replacement Type NGK BPR6ES or...

Страница 24: ...100538 7500W PORTABLE GENERATOR SPECIFICATIONS 24 Parts Diagram...

Страница 25: ...ire 1 35 100009990 0001 Negative Wire 1 36 100021409 Battery 12V 14Ah 1 37 100021362 Fixing Bolt Battery 2 Part Number Description Qty 38 100021372 0017 Pressing Plate Battery 184 mm 1 39 100011452 00...

Страница 26: ...mp 1 8 2 83 100006138 Connection Tube Assembly 1 1 84 100087746 Connection Tube 1 85 100008945 Carbon Canister 650 cc 1 86 100008675 0001 Holder Carbon Canister 1 87 100011553 0001 Flange Bolt M8 x 32...

Страница 27: ...100538 7500W PORTABLE GENERATOR SPECIFICATIONS 27 Engine Parts Diagram...

Страница 28: ...er Assembly 1 33 100005024 Air Filter Base 1 34 100004878 Air Filter Separator 1 35 100004895 Air Filter Clip 2 Part Number Description Qty 36 100004798 Gasket Air Filter Cover 173F 2 1 37 100004781 A...

Страница 29: ...1 94 100007117 Shroud 3 1 95 100009346 Ignition Module 1 96 100009362 Bolt M6 28 Ignition 2 97 100004222 Bush 8 12 6 1 98 100009405 Charge Coil 1 99 100011270 0002 Flange Bolt M6 30 2 100 100009463 P...

Страница 30: ...100538 7500W PORTABLE GENERATOR SPECIFICATIONS 30 Wiring Diagram...

Страница 31: ...Generator cannot supply enough power or overheating Generator is overloaded Review load and adjust See Connecting Electrical Loads Insufficient ventilation Check for air restriction Move to a well ven...

Страница 32: ...nt Normal maintenance is not covered by this warranty and is not required to be performed at a facility or by a person authorized by CPE Other Exclusions This warranty excludes Cosmetic defects such a...

Страница 33: ...t to you including diagnosis parts and labor MANUFACTURER S WARRANTY COVERAGE This exhaust and evaporative emission control system is warranted for two years If any exhaust and evaporative emission re...

Страница 34: ...ed for the period of time prior to the first scheduled replacement point for that part If the part fails prior to the first scheduled replacement the part shall be repaired or replaced by CPE accordin...

Страница 35: ...ve Controls Fuel Tank Fuel Cap Fuel Lines for liquid fuel and fuel vapors Fuel Line Fittings Clamps Pressure Relief Valves Control Valves Control Solenoids Electronic Controls Vacuum Control Diaphragm...