201182 - 7500W WIRELESS REMOTE START GENERATOR

TROUbLESHOOTING

36

Problem

Cause

Solution

Both CO Shield

®

 LEDs not blinking 10 

times upon start up.

Starting the generator within 1 minute 
after being manually shutoff, not a CO 
shutoff event.

Wait 1 minute before trying to restart the 
generator. The LEDs should then blink ten (10) 
times.

Generator cannot supply enough power 
or overheating.

Generator is overloaded.

Review load and adjust. See “Connecting 
Electrical Loads.”

Dirty air filter.

Clean or replace air filter.

Choke lever in wrong position.

Move choke lever until it stops under “RUN” 
position or push in completely.

Engine is running but no AC output.

Poor cord connection.

Check all connections.

Circuit breaker is open.

Reset circuit breaker. Check all circuit breakers.

Faulty brush assembly.

Replace brush assembly (Service Center).

Loose wiring.

Inspect and tighten wiring connections.

GFCI tripped.

Reset GFCI receptacle breakers by first pushing 
the TEST button then the RESET button until 
green LED illuminates. Contact the help line.

Other.

Contact the help line.

Engine hunts or falters.

Engine governor defective.

Contact the help line.

Dirty fuel valve.

Clean the fuel valve.

Carburetor is dirty and running lean.

Contact the help line.

Choke lever in wrong position.

Move choke lever until it stops under “RUN” 
position or push in completely.

Repeated circuit breaker tripping.

Overload.

Review load and adjust. See “Connecting 
Electrical Loads.”

Faulty power cords or device.

Check for damaged, bare or frayed wires. Replace 
defective device.

Circuit breaker still too hot.

Let unit sit for 5 mins.