19
+
–
+
–
PUSH
BUTTON
DOOR SENSOR
(SUPERVISED)
DOOR STRIKE
MAGLOCK
DOOR SENSOR
(NON-SUPERVISED)
OR
EOL (End of Line) Resistor
(1k ohm)
PROXIMITY
SENSOR
For DC Power:
Install a 1N4005
diode or equivalent
Use 18-22 AWG
Power for Maglock
(Not Provided)
DO NOT
use the power
supply for the controller
Use 18-22 AWG
For DC Power:
Install a 1N4005
diode or equivalent
Power for Door Strike
(Not Provided)
REQUEST TO EXIT
GROUND
SUPERVISED
NORMALLY OPEN
COMMON
NORMALLY CLOSED
NORMALLY OPEN
COMMON
NORMALLY OPEN
COMMON
NORMALLY CLOSED
COMMON
OR
OR
REQUEST TO EXIT
SUPERVISED (DOOR STATUS)
*PRIMARY RELAY
ALARM BYPASS
NORMALLY OPEN
COMMON
AUXILIARY RELAY
OR
NOTE:
The length of the unshielded
wires should be kept to a minimum to
avoid electrical noise.
RED LED - brown
GREEN LED - orange
DATA 1 - white
DATA 0 - green
GROUND - black
12Vdc - red
READER
OR
KEYPAD
WIEGAND
LIGHT
LOAD
LINE
NEUTRAL
Isolation
Relay
Low
Voltage
Power
Supply
NOTE:
For KPR2000
keypad, wire the pink and
black (ground) wires together.
For AC Power:
Install a Siemens S10K30MOV
(Metal Oxide Varistor) (provided)
or equivalent
For AC Power:
Install a Siemens
S10K30MOV
(Metal Oxide Varistor)
(provided) or equivalent
DOOR 1 or 2
* NOTE:
MAGLOCK, door strike
and ALARM BYPASS not
evaluated by UL.
NOTE:
DO NOT
run high voltage
power within
the CAPXM
enclosure.
Door Access
Disconnect power BEFORE making electrical connections.
Below is an example of a wiring setup for door access. Door access can be
wired to Door 1 or 2 on the Door Board.
PRE-INSTALL
NETWORK
INSTALL
ACCESS CONTROL
INTRODUCTION
INTRODUCTION
PRE-INSTALL
NETWORK
INSTALL
ACCESS CONTROL
INTRODUCTION
PRE-INSTALL
NETWORK
INSTALL
ACCESS CONTROL
INTRODUCTION
PRE-INSTALL
NETWORK
INSTALL
ACCESS CONTROL
INTRODUCTION
PRE-INSTALL
NETWORK
INSTALL
ACCESS CONTROL