W I R I N G  

WIRING INSTRUCTIONS

Verify wiring configuration with that recommended by door
manufacturer for use of this product with specific door and
accessories being utilized. The use of 18 AWG wire is
recommended.

1. Close fire door prior to ANY wiring.

2. Turn off power supply sources for the release device as well as

the door operator, before beginning.

3. Verify voltage rating of release device to power source being

utilized. Voltage is indicated on the side of the unit. Verify that
power is disconnected before proceeding.

4. When powering the device from 120Vac line voltage, locate the

3-position terminal block mounted within the device enclosure.
Connect 120Vac (single phase) power source inputs to
terminals L1 (line) and L2 (neutral) of the terminal block
(Figure 1). The third position is used for earth ground.

5. When powering the device from 24Vac or 24Vdc power,

connect to terminal board positions 1 and 2 (Figure 2).
Observe proper polarity.

6. Do not connect line power or battery until all field wiring is

complete per the following pages. The battery provides backup
power in the event of a loss of line voltage and prevents the
release of the fusible link assembly and the resulting door
closure. A pulsing sounder occurs when the battery is
disconnected or when replacement is required. The battery also
provides power to the various ancillary devices (i.e., smoke
detectors, horn/strobes, etc.).

To reduce the risk of SEVERE INJURY or DEATH:
• ALL electrical connections MUST be made by a qualified

individual.

• Disconnect power at the fuse box BEFORE proceeding. Release

device MUST be properly grounded and connected in
accordance with local electrical codes.

• Installation of ALL wiring and connections, including Class 1

and Class 2 circuits, shall be performed in accordance with,
but not limited to, the latest NFPA, UL and N.E.C. standards
and codes. In addition, ALL installations subject to Canadian
standards shall be performed in accordance with the Canadian
Electrical Code, Part I, with respect to wiring material type,
wiring gauge related to power capacity requirements and
circuit length and wiring methods. 

• ALL power wiring should be on a dedicated circuit and well

protected. The location of the power disconnect should be
visible and clearly labeled.

• ALL power and control wiring MUST be run in separate

conduit.

• 120Vac should ONLY be attached to the 3-position terminal

block mounted within the enclosure.

• DO NOT disconnect battery or remove battery fuse while unit

is under power, the door will drop.

ATTENTION

AVERTISSEMENT

AVERTISSEMENT

AVERTISSEMENT

WARNING

CAUTION

WARNING

WARNING

WARNING

PRECAUCIÓN

ADVERTENCIA

ADVERTENCIA

ADVERTENCIA

FIGURE 2

To prevent DAMAGE to the circuit board, ALL connections from
terminals 3 through 16 MUST be dry contact type.

ATTENTION

AVERTISSEMENT

AVERTISSEMENT

AVERTISSEMENT

WARNING

CAUTION

CAUTION

WARNING

WARNING

PRECAUCIÓN

ADVERTENCIA

ADVERTENCIA

ADVERTENCIA

FIGURE 1

Power Strip

Ground

L2

Option DIP
Switch

L1

Mechanical Reset
Plunger

24Vac or 24Vdc

Содержание LiftMaster LM21XPBB

Страница 1: ...L L M M 2 2 1 1 X X P P B B B B L L M M 2 2 1 1 X X P P B B B B V V B B E EX XT TE EN ND DE ED D P PE ER RF FO OR RM MA AN NC CE E R RE EL LE EA AS SE E D DE EV VI IC CE E APPROVED The Chamberlain Gro...

Страница 2: ...you must read and fully understand this manual and follow all safety instructions DO NOT attempt repair or service of your release device unless you are an Authorized Service Technician GENERAL DESCR...

Страница 3: ...that the wall or mounting surface provide adequate support for the release device Refer to the door manufacturer s recommendations for use of this product with specific door being utilized Use only ha...

Страница 4: ...tion of pull must be perpendicular to the side of the release device enclosure Install an eyebolt a minimum distance of 12 from the release device to adequately redirect sash chain pull 4 Install end...

Страница 5: ...ncillary devices i e smoke detectors horn strobes etc To reduce the risk of SEVERE INJURY or DEATH ALL electrical connections MUST be made by a qualified individual Disconnect power at the fuse box BE...

Страница 6: ...3 2 1 Voice Board Wiring Annunciator Wiring with Sleeve Low Voltage Wiring High Voltage Wiring Ground L2 L1 Power Strip Mechanical Reset Plunger Refer to wiring section for proper application of thes...

Страница 7: ...consist of 22 18 AWG wiring Use only 250Vac 3 Amp 3 AG Slo Blo fuses 1 Supervised power limited circuit 20 Ohm maximum line impedance 2 Unsupervised power limited circuit 20 Ohm maximum line impedance...

Страница 8: ...Wire Class B Style A Initiating Devices Connect wiring from N O initiating device loop to positions 3 and 4 Place the supervisory resistor LMEOLRES 10 contained within the accessory pack Figure 3 Obs...

Страница 9: ...is in the closed position and so that it will toggle states from its N O condition switch closed when door is closed to a closed condition indicating that the door edge has made contact with desired d...

Страница 10: ...lection of either message In the ON position Message 1 is activated in the OFF position Message 2 is activated Figure 12 The voice board can drive up to two 70 7V speakers Model LM8SP or speaker input...

Страница 11: ...ructions Raise door and then reset the release device by pushing downward on the mechanical reset button at the top of the device Fully insert the end link through the side opening on the device and r...

Страница 12: ...orrect If not the release device will not release the fusible link assembly in a fire condition Conversely the release device will always release the fusible link assembly when powered or reset CIRCUI...

Страница 13: ...ATH Stand clear of path of door Disconnect ALL electrical and battery power BEFORE performing maintenance ATTENTION AVERTISSEMENT AVERTISSEMENT AVERTISSEMENT WARNING CAUTION WARNING WARNING WARNING PR...

Страница 14: ...ector 24Vdc Ion 9 LM1412 Smoke Detector 12Vdc Ion 10 LMTH135 Heat Detector 135 Degree Fixed Temperature 11 LMTH194 Heat Detector 194 Degree Fixed Temperature ITEM PART DESCRIPTION 12 LMEH1224ADA Horn...

Страница 15: ...24MC LMHS2475ADA 24Vdc Horn Strobe P1224MC P2R LMEH1224ADA 24Vdc Horn H12 24 LM8SP Speaker SP201R MODEL NO DESCRIPTION LMEOLRES10 10 kOhm End of Line Resistor LMEOLRES 10 LMEOLR1224 End of Line Relay...

Страница 16: ...01 32051D 2008 The Chamberlain Group Inc 2 11 08 All Rights Reserved...

Отзывы: