Press and hold 

STOP...

...then press and 

hold CLOSE...

...then press and hold OPEN 

until "Er" shows.

CODE SEQUENCE NUMBER

The first number shown is the most 

recent code (example: “01”). The 

display will show the sequence of 

codes that occurred starting with “01” 

and going up to code “20”. 

CODE NUMBER

The second number shown after the code 

sequence number is the code itself  

(31-99, example” “31”).

A SECOND LATER....

The operator will show the code sequence number followed by the code number:

Diagnostic Codes

TO VIEW THE CODES: 

 

 

 

 

 

 

LiftMaster.com

© 2018, LiftMaster

All Rights Reserved

01-39240-11

LiftMaster System

Installed System

Informational

External Entrapment Protection

Inherent Entrapment Protection

WIRING DIAGRAM

Model LA412UL

CODE COLOR KEY:

DIAGNOSTICS

DIAGNOSTICS

SBC

OPN

CLS
STP

COM

EYE

ONLY

EYE/

EDGE

EYE/

EDGE

COM

1

2

3

OPEN CLOSE

TO MAIN BOARD

POWER

DIAGNOSTICS

DIAGNOSTICS

SHADOW   INTERUPT      EXIT

SBC

OPN

CLS
STP

COM

EYE

ONLY

EYE/

EDGE

EYE/

EDGE

COM

1

2

3

OPEN CLOSE

TO MAIN BOARD

POWER

SHADOW   INTERUPT      EXIT

SBC

OPN

CLS
STP

COM

EYE

ONLY

EYE/

EDGE

EYE/

EDGE

COM

1

2

3

TO MAIN BOARD

POWER

SHADOW   INTERUPT      EXIT

SBC

OPN

CLS
STP

COM

EYE

ONLY

EYE/

EDGE

EYE/

EDGE

COM

1

2

3

OPEN CLOSE

TO MAIN BOARD

POWER

SBC

OPN

CLS
STP

COM

EYE

ONLY

EYE/

EDGE

EYE/

EDGE

COM

1

2

3

OPEN CLOSE

TO MAIN BOARD

POWER

DIAGNOSTICS

DIAGNOSTICS

DIAGNOSTICS

20A

DIAGNOSTICS

10W 12V

10W 12V

10W 12V

SHADOW   INTERUPT      EXIT

SBC

OPN

CLS
STP

COM

EYE

ONLY

EYE/

EDGE

EYE/

EDGE

COM

1

2

3

OPEN CLOSE

TO MAIN BOARD

POWER

43

21

Photoelectric Sensors

for close cycle

Edge Sensor

for close cycle

OR

Edge Sensor

for open cycle

Photoelectric Sensors

for open cycle

ENTRAPMENT  PROTECTION

LOCKS

ACCESSOR

POWER

ENTRAPMENT PROTECTION

CONTROLS

OR

24 Vdc

switched

OR

OR

Expansion Board

   (Optional Accessory)

Maglock

 

(Optional)

(not provided)

Solenoid Lock

 

(Optional)

(not provided)

24 Vdc

always on

Photoelectric Sensors

 

for open or close cycle

Photoelectric Sensor

 

for open or close cycle

Edge Sensor

 

for open or close 

cycle

Edge Sensor

 

for open or close 

cycle

Photoelectric Sensor

 

for open or close cycle

Control Board

COAXIAL CABLE

ANTENNA

(see below)

PLUG-IN LOOP DETECTOR

Model LOOPDETLM

(see below)

AUXILIARY RELAYS

LOOPS

Shadow Loop

Exit Loop

Interrupt Loop

Normally Open

Common

Normally Closed

Normally Open

Common

Normally Closed

SWITCH SETTINGS

1

2

3

RELAY 1

RELAY 2

OFF

Relay always off

Relay always off

OFF

OFF

OFF

OFF

ON

Energizes at open limit

Energizes at open limit

OFF

OFF

ON

Energizes when not at 

close limit

Energizes when not at 

close limit

OFF

ON

ON

Energizes when motor 

is on

Energizes when motor is

on

ON

OFF

OFF

Energizes 3 seconds

prior/during gate motion

Energizes 3 seconds prior 

and during gate motion

ON

OFF

ON

Energizes with AC or 

solar power

Energizes with battery 

power

ON

ON

OFF

Energizes when gate is 

tampered with

Energizes when gate is 

tampered with

ON

ON

ON

LEDs will blink

cycle count

Not used

RED

/

GREEN

 LIGHT FUNCTIONALITY

1

2

3

Red light

 wired to AUX RELAY 1. 

Green light

 wired to AUX RELAY 2.

AUX RELAY 1 SWITCHES

OFF

Red light OFF*

OFF

OFF

CLOSED

GATE STATE

AUX RELAY 2 SWITCHES

Green light OFF

1

2

3

ON

ON

ON

OPENING

OPEN

CLOSING

Defined Mid Stop

Undefined Mid 

Stop
Timer more than 

5 seconds
Timer less than 

5 seconds

* For red light ON when gate is closed, set switch 1 on AUX RELAY 1 to ON

Red light ON/FLASH

Red light OFF

Red light ON/FLASH

n/a

Red light ON

Red light OFF

Red light ON/FLASH

Green light OFF

Green light ON

Green light OFF

Green light OFF

n/a

Green light OFF

Green light ON

Battery

12V 7AH

Battery

12V 7AH

Solar Panels

10W minimum - 30W maximum, wired in parallel

Black

Red

ALARM

CONTROL BOARD

Blue

PRODUCT 

ID

White

White

RESET BUTTON

PRIMARY

OPERATOR

SECONDARY

OPERATOR

CONTROL BOARD

J15 Plug

 

Black

Black

Earth Ground Rod

Black

CONTROLS

LOOPS

Black

Red

Optional 33AH Battery Configuration

For 33AH battery configuration please use harness K94-37236. 

The Large Solar Control Box (XLSOLARCONTUL) can be used with 

either 7AH or 33AH batteries.

Red

Red

Red

Shadow Loop

Exit Loop

Interrupt Loop

Access

Control

Device

Control Station

Fire Department

Control Stations

Jumper

Diode

Wireless Edge Kit

Model LMWEKITU

N.C.

CODE MEANING

SOLUTION

31

Main control board has experienced an internal 

failure.

Disconnect all power, wait 15 seconds, then 

reconnect power (reboot). If issue continues, 

replace main control board.

32

Linear Drive Disengaged (Arm 1)

Disengage then re-engage arm. Check wiring and 

connections.

33

Linear Drive Disengaged (Arm 2)

35

Max-Run-Time Exceeded Error

Check for an obstruction, then reprogram the 

limits.

36

Product ID Error

Was the control board just replaced? If so, erase 

limits, enter limit setup mode and set limits. If 

not, disconnect all power, wait 15 seconds, then 

reconnect power before changing product ID 

harness.

37

Product ID Failure

Unplug product ID harness then plug back in. 

Disconnect all power, wait 15 seconds, then 

reconnect power before replacing product ID 

harness.

38

Hard Stop Limit (Arm 1)

Limit may be set too tightly against a non-

resilient hard stop (re-adjust limit). Operator may 

be at end of travel (re-adjust mounting).

39

Hard Stop Limit (Arm 2)

40

Battery overvoltage

Too much voltage on the battery. Check harness. 

Make sure there is NOT a 24V battery on a 12V 

system.

41

Battery overcurrent

Possible short of the battery charge harness. 

Check harness. Make sure you do NOT have a 

12V battery on a 24V system.

42

No battery at boot up

Check battery connections and installation. 

Replace batteries if depleted to less than 20V on 

a 24V system or less than 10V on a 12V system. 

Make sure there is NOT a single 12V battery on a 

24V system.

43

Exit Loop Error

Failure or missing loop (SHORT or OPEN - 

LiftMaster Plug-in Loop Detector only) Check 

loop wiring throughout connection. May be a 

short in the loop, or an open connection in the 

loop.

44

Shadow Loop Error 

45

Interrupt Loop Error 

46

Wireless edge battery low

Replace batteries in wireless edge.

51

Pass-point not detected (Arm 1)

Check yellow pass-point wiring. If limits are not 

accurate, reprogram.

52

Pass-point not detected (Arm 2)

53

Brownout occurred

AC/DC board supply dipped below allowable 

level. Review power supply and wiring. If 

rebooting, ensure enough time for discharge of 

power to force a fresh boot.

54

Wireless Second Operator Communication Error Check the second operator for power. If OFF, 

restore power and try to run the system. If 

powered, deactivate the wireless feature and then 

reprogram the second operator.

60

Minimum number of monitored entrapment 

protection devices not installed. 

Review monitored entrapment protection device 

connections. This swing gate operator will 

operate only after installation of a minimum of 

one external safety device in either the open or 

close direction.

61

CLOSE EYE/INTERRUPT held more than 3 

minutes

Check wired input on main control board; check 

for alignment or obstruction.

62

CLOSE EDGE held more than 3 minutes

63

OPEN EYE/EDGE held more than 3 minutes

64

CLOSE EYE/INTERRUPT held more than 3 

minutes

Check wired input on expansion board; check for 

alignment or obstruction.

65

CLOSE EYE/EDGE held more than 3 minutes

66

OPEN EYE/EDGE held more than 3 minutes

67

Wireless edge triggered more than 3 minutes

Check wired input for wiring issue or 

obstruction.

68

Wireless edge loss of monitoring

Check wireless edge inputs.

69

Wireless edge triggered

IF an obstruction occurred, no action required. If 

an obstruction did NOT occur, check inputs and 

wiring.

70

CLOSE EYE/INTERRUPT triggered, causing 

reversal, preventing close, or resetting TTC

IF an obstruction occurred, no action required. If 

an obstruction did NOT occur, check alignment, 

inputs, and wiring on main control board.

71

CLOSE EDGE triggered, causing reversal, 

preventing close, or canceling TTC

72

OPEN EYE/EDGE triggered, causing reversal or 

preventing opening

73

CLOSE EYE/INTERRUPT triggered, causing 

reversal, preventing close, or resetting TTC

IF an obstruction occurred, no action required. If 

an obstruction did NOT occur, check alignment, 

inputs, and wiring on expansion board.

74

CLOSE EYE/EDGE triggered, causing reversal 

and preventing close or canceling TTC

75

OPEN EYE/EDGE triggered, causing reversal or 

preventing opening

80

Close input (EYE/EDGE) communication fault 

from other operator

Check inputs and communication method 

between operators, either wired bus or radio. 

Ensure operator is powered. May have to erase 

the wireless communication and reprogram the 

two operators.

81

Open input (EYE/EDGE) communication fault 

from other operator

82

Close input (EYE/EDGE) communication fault 

(expansion board)

Check the connections between the main board 

and the expansion board.

83

Open input (EYE/EDGE) communication fault 

(expansion board)

84

Non-monitored device detected on the wireless 

safety system

Non-monitored contact closure devices are not 

supported. Make sure connected devices are 

monitored. Check edges for proper orientation 

and resistive end cap connection.

91

Force Reversal (Operator 1)

Check for obstruction. If no obstruction, check 

that the mechanical assembly is engaged and 

free to move. See section on Limit and Force 

Adjustment, and Obstruction Test in the manual.

92

Force Reversal (Operator 2)

93

RPM / STALL Reversal (Operator 1)

Check for obstruction. If no obstruction, check 

the operator wiring and that the mechanical 

assembly is engaged and free to move. Replace 

APE assembly.

94

RPM / STALL Reversal (Operator 2)

99

Normal Operation

No action required

To reduce the risk of INJURY or DEATH:
•   DISCONNECT power and battery BEFORE installing or servicing operator.

•  Replace ONLY with fuse of same type and rating.

•    To be compliant with UL325 and industry safety guidelines, qualified monitored 

external entrapment protection devices such as photoelectric sensors or edge 

sensors are required to be installed with this operator at each entrapment zone. 

Use ONLY LiftMaster approved entrapment protection devices (refer to the 

accessory page of manual).

•   See manual prior to servicing regarding maintenance and required safety testing.