SET STRIKE-OUT ALARM
The strike-out alarm will engage after 10 failed card/PIN attempts in a ten minute
period. Factory default is OFF. The strike-out alarm can be set to deny access for 10
minutes or it can be set to operate the alarm for 10 minutes.
NOTE:
Enter Master
Code or Valid Card to silence all alarm outputs.
Programming Step
Keystroke Combination
1. Enter Program Mode
✱
(Master Code) #
2. Strike-Out Alarm OFF
OR
2. Strike-Out ON
OR
2. Strike-Out Alarm ON
7 0 #
(Factory default)
7 1 #
Access will be denied for 10 minutes
7 2 #
3. Exit Program Mode
✱
Programming Step
Keystroke Combination
1. Enter Program Mode
✱
(Master Code) #
2. DOTL /Door Forced Alarm OFF
OR
2. DOTL /Door Forced Alarm ON
6 0 #
6 1 #
(DOTL:
Alarm sounds for 1 minute. Door
Forced: Alarm sounds for 1-3 minutes and
enables alarm output.)
2. Door Forced Output Timing
9 (1-3) #
3. Exit Program Mode
✱
SET DOOR OPEN TOO LONG (DOTL) OR FORCED ALARM
This setting enables both DOTL and Door Forced Alarms and requires an external
sensor input. The Door Forced alarm output timing can be set from 1-3 minutes
(default is 1 minute). The Door Open Too Long (DOTL) timing is fixed to 1 minute
and only sounds the built in buzzer. Factory default is OFF.