Do NOT turn power on until you have finished making ALL power and control wiring connections.
12
T Y P I C A L I N S T A L L A T I O N
POWER AND GROUND WIRING CONNECTIONS
NOTE:
Power and control wiring must be run in separate conduit
in accordance with local electrical codes. Must use 14 AWG or
heavier wire for power wiring. Use conduit knockouts for wiring as
indicated on the electrical box labels.
IMPORTANT NOTE:
Operator must be properly grounded. Failure
to properly ground the operator could result in electric shock and
serious injury.
To reduce the risk of SEVERE INJURY or DEATH:
• ANY maintenance to the operator or in the area near the
operator MUST NOT be performed until disconnecting the
electrical power and locking-out the power via the operator
power switch. Upon completion of maintenance the area
MUST be cleared and secured, at that time the unit may be
returned to service.
• Disconnect power at the fuse box BEFORE proceeding.
Operator MUST be properly grounded and connected in
accordance with local electrical codes. The operator should be
on a separate fused line of adequate capacity.
• ALL electrical connections MUST be made by a qualified
individual.
• DO NOT install ANY wiring or attempt to run the operator
without consulting the wiring diagram.
• Reversing devices are recommended for ALL installations.
• ALL power wiring should be on a dedicated circuit and well
protected. The location of the power disconnect should be
visible and clearly labeled.
• ALL power and control wiring MUST be run in separate
conduit.
ATTENTION
AVERTISSEMENT
AVERTISSEMENT
AVERTISSEMENT
WARNING
CAUTION
WARNING
WARNING
WARNING
PRECAUCIÓN
ADVERTENCIA
ADVERTENCIA
ADVERTENCIA
8
Remove cover
9
Run wires to electrical box according to
local electrical codes
Conduit
Power
Control
10
Attach power and ground wires to high voltage
terminal strip
Line Power 115 Vac Single Phase
Hot
Neutral
Ground
DISTANCE GAUGE
50'
14
AWG
100'
12
AWG
200'
8
AWG*
350'
6
AWG*
500'
4
AWG*
1000'
2
AWG*
POWER WIRING CHART
* Maximum wire gauge that can be connected to the
operator’s terminal is 12 AWG. When a larger wire gauge
is required, the wire must be gauged down to 12 AWG.