1.0 Introduction – Protecta LED GRP
This installation leaflet covers the range of Protecta GRP luminaire models with the Ex q control gear. These luminaires are
mainly used in harsh environments and are constructed using a corrosion resistant glass reinforced polyester body and
polycarbonate diffuser. The integrated unit consists of a battery pack and a mains supplied driver to supply the LED strips
and charge the battery pack in normal situations and power the LED strips from the battery pack in an emergency situation.
The driver monitors the emergency functions and displays the emergency unit status by means of a green LED. Refer to the
current catalogue for information on product references. The luminaires are available in 02L (2ft) and 05L (4ft) sizes.
2.0 Electrical Supplies
Lamps
02L - 2 x 600mm LED Strip
05L - 2 x 1200mm LED Strip
Voltage range AC
110-130V or 220-254V
Frequency range Hz
47-63Hz
Power Watts 220-254V
34W
65W
Current Amps 220-254V
0.16A
0.30A
Power Watts 110-130V
34W
65W
Current Amps 110-130V
0.28A
0.55A
The safety limit for surface temperature (T rating) is +/-10% on the rated voltage. The maximum nominal variation from rated
voltages stated above is +/- 6%.
Batteries
6V 4Ah NiCd (02L)
6V 7Ah NiCd (05L)
Emergency Duration
90 minutes or 3 hours depending on model specified
Power Factor >0.95
Power is constant over voltage range.
Over Voltage
400V ac for 1 min
Through Wiring
The through current rating is 16A. 4mm² terminals are standard (6mm² wiring can be
used in the terminals in accordance with the luminaire certificate).
Fuse and MCB Ratings
It is recommended that for selection of MCBs users should consult the MCB
manufacturer as this unit contains electronic control gear. The electronic control gear has
nominal values of inrush current of 35A for 70µs on 230V and 70A for 70µs on 110V.
Storage
Luminaires are to be stored in cool dry conditions preventing ingress of moisture and
condensation. Storage temperature range to be -40°C to +80°C.
Battery packs in storage should be cycled charged/discharged/charged every 9
months, as per instructions below.
Always disconnect battery plug and socket for storage
.
Any specific instructions concerning emergency luminaires must be complied
with.
(Warning: Battery packs not cycled and stored for a year may not be