I-PR3C-03.doc
Issue 03
17/01/2022
6
IOM
–
PROTECTA LED Ex ec
5
Check any external and internal earths.
6
Check all terminations are firmly screwed down, tighten if necessary.
7
Check clips visually for any damage and replace, if necessary.
8
If it has been suspected that the Luminaire has suffered mechanical damage, a stringent workshop check
on all components should be made. All components can be removed from the Luminaire for inspection.
4.0
Electrical Fault Finding and Replacement
The supply must be isolated before opening the Luminaire.
Any live fault finding must be done by a competent electrician and, if carried out with Luminaire in place, under a
permit to work.
The control gear can be tested for continuity of connections with a low voltage tester.
If LED’s go out repeatedly, and replacement components do not work or expected life is reduced, the control
gear should be returned for replacement / testing.
On re-assembly all faulty / damaged wiring should be replaced, and connections checked.
5.0
Disposal of Material
The unit is made from combustible materials. The control gear contains plastic parts and polyester resin. All
electrical components and the body parts may give off noxious fumes if incinerated. Take care to render these
fumes harmless or avoid inhalation. Any local regulations concerning disposal must be complied with. Any
disposal must satisfy the requirements of the WEEE directive [2012/19/EU
and Regulations 2012
] and therefore
must not be treated as commercial waste. The unit is mainly made from incombustible materials.
5.1
LED’s
LED’s in modest quantities are not "special waste". They should be broken up in a container to avoid injury.
Avoid inhaling dust.
Table A
Series Standard circuit
Inotec modules
Refer to
Section:
1.0
Product code
Body
Type
Nominal
Voltage
Ambient
Temperature
T
Rating
Max Surface
Temperature
(Dust)
PR3C/02L/LE/JSVS
2ft Twin
230Vac
176-264Vdc
-15°C < Ta < +50°C
T4
75°C
PR3C/04L/LE/JSVS
2Ft Twin
230Vac
176-264Vdc
-15°C < Ta < +50°C
T4
75°C
PR3C/07L/LE/JSVS
4Ft Twin
230Vac
176-264Vdc
-15°C < Ta < +50°C
T4
75°C
PR3C/02L/LE/JSVT
2ft Twin
230Vac
176-264Vdc
-15°C < Ta < +50°C
T4
75°C
PR3C/04L/LE/JSVT
2Ft Twin
230Vac
176-264Vdc
-15°C < Ta < +50°C
T4
75°C
PR3C/07L/LE/JSVT
4Ft Twin
230Vac
176-264Vdc
-15°C < Ta < +50°C
T4
75°C
To comply with the Waste Electrical and Electronic Equipment directive 2012/19/EU and
Regulations 2012 the apparatus cannot be classified as commercial waste and as such
must be disposed of or recycled in such a manner as to reduce the environmental impact.