Chalmit Protecta III 02L Скачать руководство пользователя страница 1

 
 
 

 

 

I-PR3C-03.doc   

 

Issue 03  

17/01/2022 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

                                                IOM 

 

PROTECTA - LED Ex ec

 

 

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS 

Protecta III – Zone 2(Ex ec) LED Luminaires for use 

with Inotec Central Battery System (CBS) 

ATEX, IECEx and UKEX 

 
Important

Please read these instructions carefully before installing or maintaining this equipment.  

 

 

 

Good electrical practices should always be followed, and this data should be used  
as a guide only. 

 
 

 

 
 

MODEL SIZE 

DIMENSION ‘A’

DIMENSION ‘B’

02L 

742

400

04L 

742

400

07L 

1352

700

 

 

 

Содержание Protecta III 02L

Страница 1: ...minaires for use with Inotec Central Battery System CBS ATEX IECEx and UKEX Important Please read these instructions carefully before installing or maintaining this equipment Good electrical practices...

Страница 2: ...U by reason of the Type Examination EU Type Examination and meets the UK statutory requirements Sl 2016 No 1107 and compliance with the Essential Health and Safety Requirements M Poutney Technical Man...

Страница 3: ...tially explosive atmosphere consideration should be given to verifying that the maximum surface temperature of the luminaire is below the ignition temperature of the hybrid mixture 3 1 3 Cleaning The...

Страница 4: ...uct is certified for ATEX IECEx and UKEX and to comply with the certification for installation cable glands and sealing plugs must be ATEX IECEx or UKEX certified depending on site requirements Cable...

Страница 5: ...ring between body and tray Replace in reverse order 3 8 4 Retro Fitting Lamps to LED s Before opening the front cover ensure that the luminaire is isolated from the mains supply Access for retro fitti...

Страница 6: ...nts and the body parts may give off noxious fumes if incinerated Take care to render these fumes harmless or avoid inhalation Any local regulations concerning disposal must be complied with Any dispos...

Страница 7: ...Watts Line Current Inrush Current Duration 02L JSVS 2 x 560mm 2296 400mA 18 0 08A 31A 41 s 04L JSVS 2 x 1120mm 3526 300mA 25 0 11A 27A 41 s 07L JSVS 2 x 1120mm 6596 600mA 54 0 24A 22A 42 s 02L JSVT 2...

Страница 8: ...I PR3C 03 doc Issue 03 17 01 2022 8 IOM PROTECTA LED Ex ec...

Страница 9: ...gegeben da keine nderungen erfolgt sind die einen Einfluss auf den technischen Stand des Produkts haben Terms of the directive Standard Date Certified to Standards Date Declared to Prescription de la...

Страница 10: ...Produkts der Produkte zusammen mit dieser Erkl rung das Ger t die Ger te alle technischen und regulativen Anforderungen der oben aufgef hrten Direktiven erf llt Name and Date Mark Poutney 17 01 2022...