background image

12

9

The boiler is suitable for sealed systems only. The

maximum cold water mains pressure for the appliance is
10 bar. All fittings and pipework connected to the
appliance should be of the same standard.  If there is a
possibility of the incoming mains pressure exceeding 10
bar, particularly at night, then a suitable pressure limiting
valve must be fitted. 

The boiler is designed to provide hot water on demand. If
there is a requirement for greater demands, for example if
the property has several bathrooms and cloakrooms, a
vented or unvented hot water storage system should be
used.

Showers

Any shower valves used with the appliance should be of a
thermostatic or pressure balanced type. Refer to the
shower manufacturer for performance guidance and
suitability.

Flushing and Water Treatment

The performance of the appliance could be impaired by
system debris or the effects of corrosion. The system must
be flushed thoroughly to remove metal filings, solder,
machining oils and other fluxes and greases before
connecting the boiler. If it is an existing system, an
appropriate flushing and descaling agent should be used.
Refer to BS 7593 (1992) for guidance. For more
information on the use of corrosion inhibitors, flushing and
descaling agents, advice can be sought from the
manufacturers of water treatment products such as:

Betz Dearborn Ltd
Foundry Lane
Widnes
Cheshire
WA8 8UD

Tel: 0151 424 5351

Fernox Manufacturing
Britannica Works
Clavering
Essex
CB11 4QZ
Tel: 01799 550811

System Controls

The boiler is electrically controlled and is suitable for most
modern electronic time and temperature controls. The
addition of such external controls can be beneficial to the
efficient operation of the system. The boiler connections
for external controls are 24V and so only controls of 24V
or that have voltage free contacts should be used.

By pass and Pump

The boiler is fitted with an automatic by pass. Although
adjustment is not necessary.

Expansion Vessel

The expansion vessel is pre-charged to 0.7 bar (10 lb/in

2

).

The vessel is suitable for systems up to 145 litres
capacity. For systems of greater capacity an additional
expansion vessel will be required. Refer to the chart below
and BS 7074 pt 1 or BS 5449.

Filling Point

Provision must be made to be able to charge the system
on commissioning and to make up any subsequent
pressure loss.
The method of connection must utilise approved
equipment and must comply with the water regulations. A
filling loop can be so installed as to be hidden beneath the
boiler.

20

40

60

80

100

120

Pf

140

160

180

200

220

240

0,7

0,8

0,9

1,0

1,1

1,2

1,3

1,4

1,5

1,6

1,7

1,8

1,9

2,0

Capacité maximale de l'installation (en litres)

80

°

C

70

°

C

60

°

C

50

°

C

40

°

C

260

Pression à froid pour le circuit chauffage (en bar)

Liters

Pressure

System capacity chart

Fig. 21

System Guidance

Содержание Britony SE 100 L.P.G.

Страница 1: ...nstallation and Operating instructions These instructions Must Be Left With The Appliance Manufactures N Model Type Gas Council N 200906812037 31 Britony SE 80 Nat 47 980 16 200906812027 31 Britony SE 80 L P G 47 980 18 200906813037 31 Britony SE 100 Nat 47 980 17 200906813027 31 Britony SE 100 L P G 47 980 19 GB IE ...

Страница 2: ...hone the national warranty helpline 0870 600 9888 Advice on installation or servicing can also be obtained by contacting the Technical Department on Tel 0870 600 9888 Fax 01494 459775 GUARANTEE The manufacturer s guarantee is for 12 months from the date of purchase The guarantee is invalidated if the appliance is not installed in accordance with the recommendations made herein or in a manner not a...

Страница 3: ... FOR SETTING THE BUILT IN CLOCK 14 General layout 14 To set the time 14 To set the On and Off times 14 To select function mode 14 INCORRECT FUNCTION 15 NOTES 15 The BRITONY COMBI SE is a fully automatic wall mounted low water content combination boiler It is a room sealed fan assisted balanced flued appliance providing central heating and mains pressure domestic hot water on demand It has electron...

Страница 4: ... heating control thermistor 17 Three way valve 18 Secondary heat exchanger 19 Two position Selector switch OFF O ON I 20 Domestic hot water temperature adjustment 21 Heating flow temperature adjustment 22 Heating temperature indicator 23 Green indicator Power ON 24 Orange indicator Burner ON 25 Red indicator Lock out flame failure 26 Reset button 27 Pressure gauge 28 DHW mode indicator 29 Heating ...

Страница 5: ...100 PROPANE L P G G31 Gas rate Maximum in kg h 2 00 2 42 Maximum in ft3 h 37 44 8 Inlet pressure Nominal in mbar 37 37 Nominal in in wg 14 8 14 8 Burner pressure Nominal in mbar 35 30 4 Nominal in in wg 14 12 2 BUTANE L P G G30 Gas rate Maximum in kg h 2 04 2 45 Maximum in Lbs h 4 50 5 40 Inlet pressure Nominal in mbar 28 28 Nominal in in wg 11 2 11 2 Burner pressure Nominal in mbar 26 7 24 Nomina...

Страница 6: ...100 Type C 12 206 143 Ø 125 Ø 80 120 Ø 80 Type C 32 xx Type C 32 xy 250 Ø 80 250 Type C 32 xy C52 The boiler is suitable for the flue types type C 12 type C 32 xx C32 xy or C 52 Outer case dimensions Width 440 minimum space required 450 Height 850 Depth 380 All dimensions in mm Safety valve center line Minimum clearances Both sides 5 mm Above casing 170 mm Below casing 200 mm Front for servicing 5...

Страница 7: ...t the central heating for the duration of hot water delivery I reset 19 23 25 22 26 24 5 Fig 6 a b c d e Fig 7 Central Heating Mode To be able to supply heating the main switch 19 Fig 6 must be in I position This will be confirmed by the green indicator light 23 Fig 6 Turn the selector switch 21 clock wise to establish the green heating indicator 29 Fig 6 When there is a demand for heating either ...

Страница 8: ...Quinnel Wireworks Old Kent Road London SE15 1NL Tel 0171 639 1357 Ventilation The room in which the boiler is installed does not require specific ventilation If it is installed in a cupboard or compartment permanent ventilation is not required for cooling purposes Gas Supply The gas installation and soundness testing must be in accordance with the requirements of BS 6891 The boiler requires a 22 m...

Страница 9: ... should be carefully checked for leaks as frequent refilling could cause premature system corrosion or unnecessary scaling of the heat exchanger Fitting the Horizontal Flue The instructions for the vertical and biflux twin pipe flue options are included with the relevant adapter kits The standard flue supplied with the appliance is suitable for lengths from 300 mm minimum to 790 mm maximum This me...

Страница 10: ...16 P3 potentiometer TAC Temporisation Anti Cycle may now be adjusted between 30 seconds and 3 minutes see detail factory set at 3 minutes JP3 the spade connector fig 14 allows the gas rate to be reduced to 1 3 performance by positionning spade across pins as shown fig 14 Full performance across pins as shown fig 14 After completling adjustments replace rubber cover and refit outer casing C10 C10 C...

Страница 11: ...selector switch 19 fig 18 to On position I Turn the boiler thermostat to maximum 21 fig 18 The boiler will light Allow the boiler to heat system Check the inlet gas pressure working pressure while boiler is operating in hot water mode Refer to technical data Check the operation of the boiler controls and safety devices see separate servicing leaflet for details Set the by pass Refer to system guid...

Страница 12: ...atment products such as Betz Dearborn Ltd Foundry Lane Widnes Cheshire WA8 8UD Tel 0151 424 5351 Fernox Manufacturing Britannica Works Clavering Essex CB11 4QZ Tel 01799 550811 System Controls The boiler is electrically controlled and is suitable for most modern electronic time and temperature controls The addition of such external controls can be beneficial to the efficient operation of the syste...

Страница 13: ...e burner on indicator will light 24 and the water will become hot Heating 1 Turn main switch 19 to on position I The green power on indicator will light 23 Turn the CH thermostat clockwise 20 The CH indicator will light 29 3 If the room thermostat if fitted the boiler temperature control and the clock if fitted are all calling for heat the orange burner on indicator will light and the heating will...

Страница 14: ...m and 18 6 00 pm ON periods are set by sliding all tappets between the ON time and the OFF time to the outer edge of the dial The tappets remaining at the centre of the dial are the OFF periods 4 To select function mode Put the selector switch B to symbol to control the boiler by the clock Put the switch B to I to select permanent operation or to 0 to turn heating off permanently Fig 25 1 1 2 2 3 ...

Страница 15: ...water thermistor faulty open circuit m m m m l l m m l l m m Domestic hot water thermistor faulty short circuit m m m m l l m m l l l l Central heating thermistor flow faulty open circuit m m m m l l l l m m m m Central heating thermistor flow faulty short circuit m m l l m m m m m m l l Low water pressure in the Central Heating circuit m m l l m m l l m m l l Fan on but does not activate air pres...

Страница 16: ...d in this document This appliance is suitable for Natural gas or LPG A gas conversion must be made by a competent person Manufacturer Chaffoteaux Maury France Commercial subsidiary MTS GB Limited MTS Building Hughenden Avenue High Wycombe Bucks HP13 5FT Telephone 01494 755600 Fax 01494 459775 Internet www chaffoteaux co uk E mail info uk mtsgroup com Technical Support Help Line 0870 241 8180 Custo...

Отзывы: