4.2 Installation of the Connection Pipe 

Connecting piping for 

the 

indoor unit and outdoor unit are in 

the 

manifold mode

 

 (see the figure below).

Fig 6 

4.2.1 Piping between the Indoor and Outdoor Units 

(1)  If  the  liquid  and  gas  stop  valves

,

  which  have  the  sign  A  ,  B,  C,  D  or  E

 ,

  have  not  been  connected  to  the 

indoor units, turn off the screw cap with the spanner airproof. 

(2) Refer to Fig.7 for the 

appropriate amount

 of torque 

to tighten the

 screws. 

(3) 

Point

 the flare end of the copper pipe at the screw and tighten the screw by hand. 

(4) 

Next

, tighten the screw 

with

 the torque wrench 

until

 it 

emits a sound

 (as shown in Fig.7). 

(5)  The  bending  degree  of  the  pipe  can  not  be  too  small;  otherwise  it  will  crack. 

Use

  a  pipe  tube 

bender to bend the pipe. 

(6) Wrap the exposed refrigerant pipe and the joints by sponge and then tighten them with the plastic tape.

 

P ip e

F la re N u t

S p a n n e r

                            Fid 7 

1)

 

During the connection of the indoor unit and the refrigerant pipe, never pull 

the

 

indoor unit joints

 

forcefully, 

otherwise the capillary or other 

pipes

 may crack, which would result in leakage.  

2)

 

The refrigerant pipe should be supported by brackets

.

 

Do not allow the

 unit 

to support the weight of the refrigerant pipe. 

3) If  the  piping  connection  size  of 

the 

outdoor  unit  does  not  match  the  piping  connection  size  of 

the 

indoor  unit,  use  the 

piping  connection  dimension  of 

the 

indoor  unit. 

Use

  different-diameter  joints  which  is  installing  on  the  place  of 

the piping connection to connect the indoor unit. 

4) For  the  Free  Match  system,  each  pipe  should  be  labeled  to 

indicate

  which  system  it  belongs  to  avoid  mistaken 

inaccurate piping. 

4.2.2 Allowable pipe length and drop height among indoor and outdoor units  

If  the  total  refrigerant  pipe  length  (liquid  pipe)  is 

shorter

  than  that  listed  in  the  table  below,  no  additional 

refrigerant will be charged. 

Table 6 

Model

Total Liquid Pipe 

Length

 (a+b+c+d+e) 

131.2ft 

131.2ft 

131.2ft 

Pipe 
diameter

 

Thickness of 
copper tube

 

Tightening 
torque 

ĭ

1/4 inch

•

0315 inch

11

̚

22 ft·lbf

ĭ

3/8 inch

•

0315 inch

26

̚

29 ft·lbf

ĭ

1/2 inch

•

0315 inch

33

̚

37 ft·lbf

ĭ

5/8 inch

•

0.0394 inch

44

̚

48 ft·lbf

 

36K

 

42K

1

1

Specifications are subject to change without notice.

3

0

K

Содержание GWHD(30)ND3EO

Страница 1: ...Models GWHD 30 ND3EO GWHD 36 ND3EO GWHD 42 ND3EO MULTI DUCTLESS INVERTER HEAT PUMP Installation manual OUTDOOR UNIT...

Страница 2: ...TY CONSIDERATIONS 2 INDOOR UNITS COMBINATIONS 3 PREFACE 4 PRODUCT INTRODUCTION 5 PREPARATION BEFORE INSTALLATION 8 INSTALLATION 10 TROUBLESHOOTING 17 THE CONDITIONS LISTED BELOW ARE NOT CLASSIFIED INT...

Страница 3: ...leak testing or operating refrigerant compressors Pressurized mixtures of air or gases containing oxygen can lead to an explosion WARNING CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this cautio...

Страница 4: ...3 INDOOR UNITS COMBINATIONS Specifications are subject to change without notice...

Страница 5: ...indoor unit receives the signal to make full use of the after heat function for the next operation 5 When the running modes of the indoor and outdoor units conflict the conflict appears on the wired c...

Страница 6: ...20 can be realized V arious product lineup is provided with capacity range from 30KBtu to 42KBtu which can be widely used in a boarding house a working area and especially applicable in a location wit...

Страница 7: ...Level and Capacity Code of the Indoor 6 Specifications are subject to change without notice Indoor Unit Nominal Unit Btuh Indoor Model Number Outdoor Model Number 9 000 GWH09QC D3DNA1D I 12 000 GWH12Q...

Страница 8: ...parameters below are tested under a rated working condition If there is any change to them please refer to the nameplate 3 The heating capacity parameters of the heat pump indoor unit excludes the au...

Страница 9: ...lace free of dust typhoons and earthquakes 3 Try to keep the unit away from combustible inflammable and corrosive or exhaust gases 4 Leave some space for heat exchanging and servising to guarantee the...

Страница 10: ...is the more the cooling and heating capacity will decrease 9 Specifications are subject to change without notice Outdoor Unit System size 30 36 42 Piping Min Piping Length ft 9 84 9 84 9 84 Standard...

Страница 11: ...tline dimension and mounting holes Unit inch 38 3 7 36 2 9 17 1 3 14 4 7 31 24 15 5 7 Fig 4 3 3 38GJQG36 3 42K Outline dimension and mounting holes Fig 5 36K 10 40 42 1 2 24 5 6 17 1 3 14 1 4 15 3 4 4...

Страница 12: ...forcefully otherwise the capillary or other pipes may crack whichwould result in leakage 2 The refrigerant pipe should be supported by brackets Do not allow the unit to support the weight of the refri...

Страница 13: ...ft H3 Height difference between indoor units m 24 6ft 24 6ft H2 b a e d c L4 L3 L2 L5 L1 Outdoor uni t Height difference between indoor unit and outdoor unit H1 Height difference between indoor units...

Страница 14: ...erant pipe and electric wire together with tape and separate them from the drain pipe to prevent the condensate water from overflowing b Wrap the pipe from the bottom of the outdoor unit to the top of...

Страница 15: ...ge in the Outdoor Unit before Shipment NOTICE 1 The outdoor unit has been charged with refrigerant prior to delivery The refrigerant charge is not included and is an additional charge for the indoor u...

Страница 16: ...nd overload Table 8 Models Power Supply Capacity of the breaker A 208 230V 60Hz 30 208 230V 60Hz 30 208 230V 60Hz 30 30K 36K 42K 15 Specifications are subject to change without notice GWHD 30 ND3EO IN...

Страница 17: ...ng and connection line of each indoor unit should connectwell according to the instruction 3 The electric installation should be carried out by a technician instructed in the local laws regulations an...

Страница 18: ...acity Does the unit have proper thermal insulation It may causecondensation and dripping Does the unit drain well It may causecondensation and dripping Is the voltage in accordance with the rated volt...

Страница 19: ...absorbed in are blown out again NOTICE If problem can not be solved after checking the above items please contact C H service center and show phenomena and models Following circumstance are not malfu...

Страница 20: ...conflicts with that of outdoor unit indoor fault indicator will flash and conflict will be shown on the wired controller after 5 minutes Indoor unit stops to run and meanwhile change outdoor operatin...

Страница 21: ...Over burden Flash 3 times Outdoor ambient sensor malfunction Flash 6 times Outdoor tube sensor malfunction Flash 5 times Exhaust sensor malfunction Flash 7 times Attain the temperature of switch on F...

Страница 22: ...ced 4 Check if the filter screen has been set correctly 5 After a long period of nonuse open the main power switch 8 hours before re operating the unit to preheat the compressor crankcase 6 Check if t...

Страница 23: ...Add West Jinji Rd Qianshan Zhuhai Guangdong China 519070 MANUFACTURER GREE ELECTRIC APPLIANCES INC OF ZHUHAI www cooperandhunter us...

Отзывы: