CGS CGS TGC Скачать руководство пользователя страница 3

C

GS TGC Installation, Operation & Maintenance

C

GS TGC v2 220322 

Important Warning Statements

Before any installation, use or maintenance read this manual carefully. 
The information contained within this manual should be referenced for typical installation and operation only. 
For site specific requirements that may deviate from the information in this guide 

 contact your supplier. 

If this product is used in a manner not specified by the manufacturer, the safety provided by the product may 
be impaired. 
This product is designed for indoor operation only unless used in conjunction with a weatherproof cover. 
Cables must be protected against mechanical damage. 
The internal fuse should be replaced only with the same type. Anti-surge fuse 3.15A 250Vac 5x20. 
This product is not designed to detect smoke, fire or other gases and should NOT be used as such. 
This device requires a continual supply of electrical power 

 it will not work without power. 

A switch or circuit breaker must be fitted, it must be accessible and marked as the disconnecting device! 
This device should not be used to substitute proper installation, use and / or maintenance of fuel burning 
appliances including appropriate ventilation and exhaust systems. 
Seek fresh air supply and contact your local gas emergency service should you suspect a gas leak. 
This device may not fully safeguard individuals with specific medical conditions. If in doubt, consult a doctor / 
physician. 
Any parts that form part of the connections/installation must have a minimum fire-retardant rating of UL 94V-2! 
Use with a low-profile surface mount or flush cover available from 

C

GS! 

Your product should reach you in perfect condition, if you suspect it is damaged, contact your supplier

Manufacturer’s 

Warranty Statement

 

Warranty coverage:

 The manufacturer warrants to the original consumer purchaser, that this product will be free of defects in 

material and workmanship for a period of twelve months (1 year) from date of purchase. 

The manufacturer’s liability hereunder is limited to replacement of the product with repaired product at the discretion of th

manufacturer. This warranty is void if the product has been damaged by accident, unreasonable use, neglect, tampering or other 
causes not arising from defects in material or workmanship. This warranty extends to the original consumer purchaser of the product 
only.  

Warranty disclaimers:

 Any implied warranties arising out of this sale, including but not limited to the implied warranties of 

description, merchantability and intended operational purpose, are limited in duration to the above warranty period. In no event shall 
the manufacturer be liable for loss of use of this product or for any indirect, special, incidental, or consequential damages, or costs, 
or expenses incurred by the consumer or any other user of this product, whether due to a breach of contract, negligence, strict 
liability in tort or otherwise. The manufacturer shall have no liability for any personal injury, property damage or any special, 
incidental, contingent or consequential damage of any kind resulting from gas leakage, fire, or explosion. This warranty does not 
affect your statutory rights.  

Warranty Performance:

 During the above warranty period, your product will be replaced with a comparable product if the defective 

product is returned together with proof of purchase date. The replacement product will be in warranty for the remainder of the 
original warranty period or for six months 

 whichever is the greatest. 

Information on waste disposal for consumers of electrical & electronic equipment.

 

When this product reaches the end of its life it must be treated as Waste Electrical & Electronics Equipment (WEEE).  
WEEE marked products must not be mixed with general household waste, but kept separate for the treatment, recovery and 
recycling of the materials used. Please contact your supplier or local authority for details of recycling schemes in your area. 

Содержание CGS TGC

Страница 1: ...ntroller Model CGS TGC Installation Operation Maintenance Manual Please read this manual carefully and retain for future use For specific requirements that may deviate from the information in this gui...

Страница 2: ...rning Statements 3 Installation 4 Typical Application Location 4 Mounting Cabling 4 Circuit Board Terminals 5 Wiring Power Inputs 5 Wiring Gas Valve Outputs 6 Wiring Remote Emergency Stop 6 Selectable...

Страница 3: ...be free of defects in material and workmanship for a period of twelve months 1 year from date of purchase The manufacturer s liability hereunder is limited to replacement of the product with repaired...

Страница 4: ...status observation if intended for public use and is designed for indoor operation unless used in conjunction with a weatherproof cover sold separately Mounting Cabling If mounting direct to wall ensu...

Страница 5: ...onnections to high voltage connectors Any damage attempting to remove the circuit board may void any warranty All Class 2 wiring is to be installed within flexible tubing to maintain segregation betwe...

Страница 6: ...oller can be connected to remote devices with an open close circuit via the EM STOP volt free switch terminal This terminal has a factory fitted link installed normally closed circuit and when open wi...

Страница 7: ...gas shut off timeout is reached and when five 5 minutes remain the buzzer will beep and the yellow LED will then intermittently flash After this time the gas will automatically shut off until reactiv...

Страница 8: ...Not Formally Evaluated Operating 20 50 C 14 122 F 20 95 RH non condensing Storage 25 50 C 13 122F up to 95 RH non condensing Altitude Rating 2000m Wiring Typical Min 18AWG 75 C min Tinned copper Pre A...

Отзывы: