Hybrid
Vertical
Stack
–
Installation
Operation
Maintenance
Manual
OPERATION
‐
DETAILED
R090303
Installation
Operation
Maintenance
Manual
is
subject
to
change
without
notice
Page
12
start
‐
up.
If
the
switch
does
not
remake
within
the
5
minute
ignore
period,
the
compressor
will
be
immediately
stopped.
e.
Air
Temperature
Sensor
Ta
–
Sensor
Ta
will
prevent
compressor
operation
if
the
air
flowing
through
the
unit
is
below
60
°
F
(15
°
C).
f.
Water
Temperature
Sensor
Tw
–
Sensor
Tw
will
prevent
compressor
operation
if
the
outgoing
system
fluid
temperature
is
above
140
°
F
(60
°
C).
g.
Refrigerant
Temperature
Sensor
Tr
–
Sensor
Tr
will
prevent
compressor
operation
if
the
coil
temperature
is
below
35
°
F
(2
°
C).
h.
Any
of
the
above
faults
will
be
indicated
with
the
Diagnostic
Code
described
under
DIAGNOSTICS
COOL
OPERATION
2.
Monitoring
of
the
refrigerant
cycle
continues
during
operation
of
the
compressor.
The
following
malfunctions
will
cause
the
compressor
to
shutdown:
a.
If
the
head
pressure
exceeds
the
set
point
of
the
high
pressure
switch,
it
will
open,
and
the
control
board
will
terminate
the
compressor
operation
within
10
seconds.
At
this
time
the
flash
code
6
will
be
initiated
on
the
red
diagnostic
LED.
Compressor
operation
will
be
restored
in
accordance
with
the
“Intelligent
Reset”
algorithm.
b.
If
the
suction
pressure
drops
below
the
set
point
of
the
low
pressure
switch,
the
switch
will
open
and
if
it
remains
open
beyond
the
5
minute
ignore
period
after
start
up,
compressor
operation
will
be
terminated
within
10
seconds.
Compressor
operation
will
be
restored
in
accordance
with
the
“Intelligent
Reset”
algorithm.
A
flash
code
of
5
on
the
red
diagnostic
LED
will
be
initiated
at
this
time.
c.
Intelligent
Reset
Algorithm
–
If
a
low
or
high
pressure
switch
opens,
the
compressor
will
be
shut
down.
There
is
a
20
minute
delay
before
the
system
is
automatically
reset,
after
which
if
there
is
a
cool
call
in
place
and
all
other
enablers
are
within
the
start
parameters,
the
compressor
will
again
be
put
into
operation.
Should
either
of
the
pressure
switches
open
again,
the
shutdown
procedure
will
cycle
again,
followed
by
a
restart.
The
intelligent
reset
will
allow
two
open
switch
shutdowns
and
restarts
in
a
24
hour
period,
but
a
third
shutdown
within
24
hours
will
put
the
refrigeration
system
into
a
full
and
hard
lockout
requiring
a
power
down
to
reset.
If
two
or
less
switch
open
shutdowns
occur
within
a
24
hour
period,
they
will
be
erased
from
memory
and
will
not
contribute
to
a
future
hard
lockout.
(A
hard
lockout
will
prevent
compressor