CG Drives & Automation, 01-5326-01r5
Operation via the Control Panel
81
*) The status shown in Area D on the control panel can be
read via a fieldbus or serial communication, e.g. using
Modbus address nr 30053.
It is also possible to read all status indications, not just the
highest prioritized one, via a fieldbus or serial
communication, e.g. using Modbus address nr 30180 and
30182. This information is also shown in EmoSoftCom
PC-tool (optional) see menu “Area D stat [72B]”.
Area E:Shows active parameter set and if it is a motor
parameter.
Area F:Shows the setting or selection in the active menu.
This area is empty at the 1st level and 2nd level
menu. This area also shows warnings and alarm
messages. In some situations this area could
indicate “+++” or ” - - -” please see further
information in Chapter 10.3.2 page 81
Fig. 84 Example 1st level menu
Fig. 85 Example 2nd level menu
Fig. 86 Example 3d level menu
Fig. 87 Example 4th level menu
10.3.2 Indications on the display
The display can indicate “+++” or “- - -” if a parameter is out
of range. In the AC drive there are parameters which are
dependent on other parameters. For example, if the speed
reference is 500 and the maximum speed value is set to a
value below 500, this will be indicated with “+++” on the
display. If the minimum speed value is set over 500, “- - -”
is displayed.
10.3.3 LED indicators
The symbols on the control panel have the following
functions:
Fig. 88 LED indications
10.3.4 Control keys
The control keys are used to give the Run, Stop or Reset
commands directly. As default these keys are disabled, set for
remote control. Activate the control keys by selecting
Keyboard in the menus “Ref Control [214]”,
“Run/Stop Control [215]” and “Reset Ctrl [216]”.
If the Enable function is programmed on one of the digital
inputs, this input must be active to allow Run/Stop
commands from the control panel
.
TL
Operating at torque limit
9
OT
Operating at temperature limit
10
I
2
t
Active I
2
t protection
11
LV
Operating at low voltage
12
Sby
Operating from Standby power supply
13
LCL
Operating with low cooling liquid level
14
Slp
Sleep mode
15
SPS Spin start active
16
Digits
Description
Bit*
300 Process
Stp
221 Motor Volt
Stp M1:
400V
15%
Table 30
LED indication
Symbol
Function
ON
FLASHING
OFF
POWER
(green)
Power on
----------------
Power off
TRIP
(red)
AC drive
tripped
Warning/Limit
No warning
or trip
RUN
(green)
Motor shaft
rotates
Motor speed
increase/
decrease
Motor
stopped
Table 31
Control keys
RUN L:
gives a start with
left rotation
STOP/RESET:
stops the motor or resets
the AC drive after a trip
RUN R:
gives a start with
right rotation
NOTE: It is not possible to simultaneously activate
the Run/Stop commands from the keyboard and
remotely from the terminal strip (terminals 1-22).
Exception is the JOG-function which can give start
command, see “ Jog Speed [348]” on page 138.
Run
Green
Trip
Red
Power
Green
Содержание Emotron VFX Series
Страница 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 5326 01r5...
Страница 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Страница 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Страница 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Страница 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Страница 218: ...216 CG Drives Automation 01 5326 01r5...
Страница 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Страница 236: ...234 Options CG Drives Automation 01 5326 01r5...
Страница 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Страница 267: ......