CG Drives & Automation,01-5326-01r5
173
Communication information
Digital Input 2 [522] to Digital Input
8 [528]
Same function as “DigIn 1[521]”. Default function for
DigIn 8 is Reset. For DigIn 3 to 7 the default function is
Off.
Communication information
Reset 9
Reset command. To reset a Trip condition
and to enable the Autoreset function.
Preset Ctrl1 10 To select the Preset Reference.
Preset Ctrl2 11 To select the Preset Reference.
Preset Ctrl3 12 To select the Preset Reference.
MotPot Up 13
Increases the internal reference value
according to the set AccMotPot time
[333]. Has the same function as a “real”
motor potentiometer, see Fig. 110.
MotPot
Down
14
Decreases the internal reference value
according to the set DecMotPot time
[334]. See MotPot Up.
Pump1
Feedb
15
Feedback input pump1 for Pump/Fan
control and informs about the status of the
auxiliary connected pump/fan.
Pump2
Feedb
16
Feedback input pump 2 for Pump/Fan
control and informs about the status of the
auxiliary connected pump/fan.
Pump3
Feedb
17
Feedback input pump3 for Pump/Fan
control and informs about the status of the
auxiliary connected pump/fan.
Pump4
Feedb
18
Feedback input pump 4 for Pump/Fan
control and informs about the status of the
auxiliary connected pump/fan.
Pump5
Feedb
19
Feedback input pump5 for Pump/Fan
control and informs about the status of the
auxiliary connected pump/fan.
Pump6
Feedb
20
Feedback input pump 6 for Pump/Fan
control and informs about the status of the
auxiliary connected pump/fan.
Timer 1
21
Timer 1 Delay [643] will be activated on
the rising edge of this signal.
Timer 2
22
Timer 2 Delay [653] will be activated on
the rising edge of this signal.
Set Ctrl 1
23
Activates other parameter set. See Table
37 for selection possibilities.
Set Ctrl 2
24
Activates other parameter set. See Table
37 for selection possibilities.
Mot
PreMag
25
Pre-magnetises the motor. Used for faster
motor start.
Jog 26
To activate the Jog function. Gives a Run
command with the set Jog speed and
Direction, page 138.
Ext Mot
Temp
27
Be aware that if there is nothing
connected to the input, the AC drive will
trip at
“External Motor Temp” immediately.
NOTE: The External Motor Temp is active
low.
Loc/Rem
28
Activate local mode defined in [2171] and
[2172].
AnIn select
29
Activate/deactivate analogue inputs
defined in [513A], [516A], [519A] and
[51CA]
LC Level
30
Liquid cooling low level signal.
NOTE: The Liquid Cooling Level is active
low.
Brk Ackn
31
Brake acknowledge input for Brake Fault
control. Function is activated via this
selection see menu [33H] page 133
Sleep
32
Possible to enter sleep mode through
DigIn
NOTE: For bipol function, input RunR and RunL
needs to be active and “Rotation [219]” must be set
to “R+L”.
Modbus Instance no/DeviceNet no:
43241
Profibus slot/index
169/145
EtherCAT and CANopen index (hex)
4ca9
Profinet IO index
19625
Fieldbus format
UInt
Modbus format
UInt
Table 37
Parameter Set
Set Ctrl 1
Set Ctrl 2
A
0
0
B
1
0
C
0
1
D
1
1
NOTE: To activate the parameter set selection, menu
241 must be set to DigIn.
522
DigIn 2
Default:
RunR
Selection:
Same as in menu
[
521
]
Modbus Instance no/DeviceNet no:
43242 – 43248
Profibus slot/index
169/146 – 169/152
EtherCAT and CANopen index (hex)
4caa - 4cb0
Profinet IO index
19626 - 19632
Fieldbus format
UInt
Modbus format
UInt
Содержание Emotron VFX Series
Страница 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 5326 01r5...
Страница 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Страница 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Страница 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Страница 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Страница 218: ...216 CG Drives Automation 01 5326 01r5...
Страница 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Страница 236: ...234 Options CG Drives Automation 01 5326 01r5...
Страница 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Страница 267: ......