AnIn1 Operation [5138]
Communication information
AnIn1 Filter [5139]
If the input signal is unstable (e.g. fluctuation reference
value), the filter can be used to stabilize the signal. A change
of the input signal will reach 63% on AnIn1 within the set
AnIn1 Filter time. After 5 times the set time, AnIn1 will
have reached 100% of the input change. See Fig. 130.
Communication information
Fig. 130
AnIn1 Enable [513A]
Parameter for enable/disable analogue input selection via
digital inputs (DigIn set to function AnIn Select).
Communication information
AnIn2 Function [514]
Parameter for setting the function of Analogue Input 2.
Same function as “AnIn1 Fc [511]”.
Communication information
AnIn2 Setup [515]
Parameter for setting the function of Analogue Input 2.
Same functions as “AnIn1 Setup [512]”.
Communication information
5138
AnIn1 Oper
Default:
Add+
Add+
0
Analogue signal is added to selected
function in menu
[
511
].
Sub-
1
Analogue signal is subtracted from
selected function in menu
[
511
].
Modbus Instance no/DeviceNet no:
43208
Profibus slot/index
169/112
EtherCAT and CANopen index (hex)
4c88
Profinet IO index
19592
Fieldbus format
UInt
Modbus format
UInt
5139
AnIn1 Filt
Default:
0.1 s
Range:
0.001 – 10.0 s
Modbus Instance no/DeviceNet no:
43209
Profibus slot/index
169/113
EtherCAT and CANopen index (hex)
4c89
Profinet IO index
19593
Fieldbus format
Long, 1=0.001 s
Modbus format
EInt
AnIn change
100%
63%
Original input signal
Filtered AnIn signal
T
5 X T
513A
AnIn1 Enabl
Default:
On
On
0
AnIn1 is always active
!DigIn
1
AnIn1 is only active if the digital input is low.
DigIn
2
AnIn1 is only active if the digital input is
high.
Modbus Instance no/DeviceNet no:
43210
Profibus slot/index
169/114
EtherCAT and CANopen index (hex)
4c8a
Profinet IO index
19594
Fieldbus format
UInt
Modbus format
UInt
514
AnIn2 Fc
Default:
Off
Selection:
Same as in menu
[
511
]
Modbus Instance no/DeviceNet no:
43211
Profibus slot/index
169/115
EtherCAT and CANopen index (hex)
4c8b
Profinet IO index
19595
Fieldbus format
UInt
Modbus format
UInt
515
AnIn2 Setup
Default:
4 – 20 mA
Dependent on
Setting of switch S2
Selection:
Same as in menu
[
512
].
Modbus Instance no/DeviceNet no:
43212
Profibus slot/index
169/116
EtherCAT and CANopen index (hex)
4c8c
Profinet IO index
19596
Fieldbus format
UInt
Modbus format
UInt
Содержание Emotron VFX Series
Страница 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 5326 01r5...
Страница 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Страница 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Страница 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Страница 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Страница 218: ...216 CG Drives Automation 01 5326 01r5...
Страница 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Страница 236: ...234 Options CG Drives Automation 01 5326 01r5...
Страница 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Страница 267: ......