CG Drives & Automation, 01-5980-01r2
Main features
51
7.2
Working with parameter
sets
Parameter sets can be used to set the softstarter up for
different applications such as different motors used and
connected, start and stop methods, alarm settings, control
sources, etc.
With the four parameter sets different control options can
be configured with respect to quickly changing the
behaviour of the softstarter. It is possible to adapt the
softstarter online to altered behaviour. This is based on the
fact that at any desired moment any one of the four
parameter sets can be activated during operation; via the
digital inputs or the control panel.
A parameter set consists of virtually all changeable menus in
the menu system. Exceptions are some menus that can only
have one and the same value, regardless of the selected
parameter set:
[211] Language, [2171] Function Key, [2173]Local run
control, [218] Lock Code, [220] Motor data,[241] Select
Set, [260] Serial Communication and [740] Real time clock.
These menu settings are global, i.e. valid throughout the
menu system.
The menus for parameter set handling are found in section
8.2.5, page 80, starting with menu [240].
The active parameter set is shown in the display to the lower
left, and can also be viewed in menu [721] TSA Status. The
detailed configuration for each set can be written down in
the menu list that can be found in the end of this manual
alternatively, you can download an excel parameter list to fill
in from the web at www.cgglobal.com or
www.emotron.com. Another solution for copying settings
and data between different softstarter units is via PC, using
the EmoSoftCom PC tool (option). See section 12.2, page
155.
7.2.1 Selection of parameter sets
The parameter sets can be selected via the control panel, via
digital inputs or via serial communication. This is decided in
menu [241] Select Set.
All digital and virtual inputs can be configured to select
parameter sets. Fig. 37 shows the way the parameter sets
could be activated via digital input, where for instance DigIn
3 [523] is set to “Set Ctrl 1” and DigIn 4 [524] is set to “Set
Ctrl 2”.
Fig. 37 Selecting the parameter sets via digital input
When the parameter sets are selected via digital inputs, they
are activated as in Table 22. Activate the parameter changes
via digital input by setting menu [241] to “DigIn”.
Example: Manual and automatic control
In an application manual control is used to prepare for
service position. After service the process is switched to
automatic control mode. This can be solved by using one set
of parameters to activate manual control mode (i.e. control
signals via I/O), and a second set of parameters to activate
running in automatic control mode (i.e. control signals from
PLC, e.g. via fieldbus).
NOTE: Actual timer [630] values are common for all sets.
When a set is changed the timer functionality will
change according to the new set, but the timer value will
stay unchanged.
Table 22
Parameter set
Parameter set
Set Ctrl 1
Set Ctrl 2
A
0
0
B
1
0
C
0
1
D
1
1
NOTE: The selection via the digital inputs is immediately
activated.
NOTE: The default parameter set is parameter set A.
{
Parameter Set A
B
C
D
DI3
DI4
Set Ctrl1
Set Ctrl2
+24 V
Run/Stop
Jog Control
Braking Method
Motor Protection
Load Monitor
Содержание emotron TSA Series
Страница 1: ...Emotron TSA Softstarter Instruction manual English Valid from Software version 1 27...
Страница 2: ......
Страница 4: ......
Страница 6: ...2 CG Drives Automation 01 5980 01r2...
Страница 12: ...8 Introduction CG Drives Automation 01 5980 01r2...
Страница 18: ...14 Mounting CG Drives Automation 01 5980 01r2...
Страница 42: ...38 Application guidelines CG Drives Automation 01 5980 01r2...
Страница 46: ...42 Getting started CG Drives Automation 01 5980 01r2...
Страница 70: ...66 Main features CG Drives Automation 01 5980 01r2...
Страница 142: ...138 Functionality CG Drives Automation 01 5980 01r2...
Страница 158: ...154 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5980 01r2...
Страница 160: ...156 Options CG Drives Automation 01 5980 01r2...
Страница 168: ...164 Technical data CG Drives Automation 01 5980 01r2...
Страница 202: ...CG Drives Automation 01 5980 01r2 198...
Страница 203: ......