3.5.3 Configuration
The Setup Configuration mode provides access to the following setup parameters:
Label
Parameters
Description
Range
Default
Menu
Main
Sub
PROG
Programming
Setup Configuration
Mode
/
/
PASS
Password
Enter Password
0 to 9999
“0”
PASS SET
Change Password
NEW PASS
New Password
Change Password
0000 to 9999
“0”
SYS SET
Setup System Parameters
Un
Unominal
Set nominal Voltage
1 to 1000V
750
I E
Inominal
Set nominal Current
1 to 10000A
100
SH
Shunt Output
Set Shunt Nom. Output
1 to 100mV
75
BLTO
Backlight Time-
Out
Set Backlight Time-out
0 to 60 mins
3
COM SET
Setup Comm. Parameters
ID
Meter Address
Set Modbus Unit ID
1-247
100
BAUD
Baud rate
Set Data rate in bits per
second
1200/2400/4800/
9600/19200bps
9600
CFG
Data Format
Set Comm. Port
Configuration
8N2/8O1/8E1/8N1/
8O2/ 8E2
8E1
ENGY SET
Setup Energy Outputs Parameters and Preset kWh Import/Export.
ENGY PULS
Energy Pulsing
Enable Energy Pulsing
YES/NO
YES
ENGY CNST
Pulse Constant
Pulse Constant
25/100/400/1000/
3200 imp/kWh
100
kWh Import
kWh Import
Preset kWh Import
0 to 99,999,999.9
0
kWh Export
kWh Export
Preset kWh Export
0 to 99,999,999.9
0
IO SET
1
Specifies the minimum duration the
DI
must remain in the Active or Inactive
state before a state change is considered to be valid.
DI1
DI1 Debounce
DI1 Debounce
1 to 9999ms
20
DI2
DI2 Debounce
DI2 Debounce
1 to 9999ms
20
CLR
ENEY
Clear Energy
Clear Energy Registers
YES/NO
NO
SOE CLR
Clear SOE
Clear SOE Log
YES/NO
NO
ALL CLR Clear All Records
Clear Energy Registers
and SOE Log
YES/NO
NO
TM SET
Setup Date and Clock
DATE
Date
Enter the Current Date
YYYY-MM-DD
/
CLK
Clock
Enter the Current Time
HH:MM:SS
/
INFO
Check meter information
FW
Firmware
Version
Firmware Version
e.g. 1.00.00 means
V1.00.00
/
PROT VER Protocol Version
Protocol Version
e.g. 1.0 means V1.0
/
UPDT
Update Date
Firmware Update Date
e.g. 20130603
/
Table 3-4 Setup Parameters
Notes:
1)
The I/O setup parameters are only displayed when the PMC-D721MD is equipped with this option.