CET Electric Technology
73
41031
RW
Order of Harmonic Calculation
UINT16
2 to 63*
41032~41033
RW
Reserved
41035
RW
CT Clamp Specification
UINT16
0*=5A (50A) @10mV/A
1=20A@10mV/A
2=200A@1mV/A
3=500A @1mV/A
4=500A(550A) @1mV/A
5=5kA @0.1mV/A
41036
RW
Frequency
UINT16
0=50Hz*, 1=60Hz
*Default
Table 5-43 Basic Setup Parameters
Notes:
1)
The
CT Polarity
register defines the polarity for the Current Inputs as illustrated in the following table.
Bit 15~Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reserved
I4
Ic
Ib
Ia
Table 5-44 CT Polarity Register
2)
P.F. Convention: -IEEE is the same as IEEE but with the opposite sign.
Figure 5-1 Power Factor Definitions
3)
There are two ways to calculate kVA:
Mode V
(Vector method
):
2
total
2
total
total
KVAR
KW
KVA
Mode S
(Scalar method
):
c
KVA
KVA
KVA
KVA
b
a
total
5.8.3 SMTP Setup
Register
Property
Description
Format
Range/Options
40900
RW
SMTP Event Classification
1
Bitmap
Note 1)
40902
RW
SMTP IP Port
UINT16
1 to 65535 (Default=25)
40903
RW
IP Address of SMTP Server
2
UINT32
Default=0.0.0.0
40905
RW
Source Email Address
3
CHAR
Note 2)
40925
RW
Source Username
4
CHAR
40945
RW
Login Password
5
CHAR
Note 3)
40955
RW
Destination Email Address
6
CHAR
Note 4)
Table 5-45 SMTP Setup Parameters
Notes:
1)
SMTP Event Classification
register determines if a newly generated Device/SOE LOG is sent out by email. The following table
illustrates the Bitmap definition of this register. When a particular bit is set to 1, its corresponding events will be sent out by
email.
Bit
Classification
Event Type
Bit
Classification
Event Type
Bit 0
1=System Events See Appendix B
Device
Bit 16
0x81=Dip/Swell Disturbance
SOE Log
Bit 1
2=Standard Setpoints Events
Bit 17
0x82=Transient Disturbance
Содержание PMC-690
Страница 1: ...PMC 690 Hand Held Power Quality Analyzer User Manual Version V1 0A Aug 27 2018...
Страница 21: ...CET Electric Technology 21 Energy Demand Harmonics Spectrum Table Power...
Страница 23: ...CET Electric Technology 23 Max Min Setup Basic Device Storage...
Страница 24: ...CET Electric Technology 24 Advanced...
Страница 25: ...CET Electric Technology 25 Site New Site Switch Site Delete Site Rename Site Import Template Export Template...
Страница 26: ...CET Electric Technology 26 Monitoring History Table 3 2 Description of each Hierarchy...