background image

 

Revision Date: October 26, 2020

 

     

 

       

     

 

                    3P4W, Direct Connection, 3CTs

 

              3P4W, 3PTs, 3CTs

 

          3P3W, Direct Connection, 3CTs

         

     

 

 

 

 

        3P3W, Direct Connection, 2CTs

 

                                    3P3W, 2PTs, 3CTs

 

                                                    3P3W, 2PTs, 2CTs

 

         

       

     

 

 

    1P3W, Direct Connection, 2CTs

 

          1P2W L-N, Direct Connection, 1CT                        1P2W L-L, Direct Connection, 1CT                                       

Basic Setup Parameters

 

Menu

 

Parameters

 

Description

 

Options/Range

 

Default

 

Password Setup

 

/

 

Password

 

0 to 9999

 

0

 

System Setup

 

Wiring Mode

 

The Wiring Connection of the meter

 

DEMO/1P2W L-N/1P2W L-L/

 

1P3W L-L-N/3P3W/3P4W

 

3P4W

 

PT Primary

 

Primary PT Ratio

 

1 to 1,000,000 (V)

 

100V

 

PT Secondary 

 

Secondary PT Ratio

 

1 to 690 (V)

 

100V

 

CT Primary

 

Primary CT Ratio

 

1 to 30,000 (A)

 

5A

 

CT Secondary

 

Secondary CT Ratio

 

1 to 5 (A)

 

5A

 

PF Convention

 

Set PF Convention

 

IEC/IEEE/-IEEE

 

IEC

 

kVA Calculation

 

Set kVA Calculation Method

 

V/S (V=Vector, S=Scalar)

 

Vector

 

I1 REV

 

Reverse Phase A CT Polarity

 

YES/NO

 

NO

 

I2 REV

 

Reverse Phase B CT Polarity

 

YES/NO

 

NO

 

I3 REV

 

Reverse Phase C CT Polarity

 

YES/NO

 

NO

 

Communication Setup

 

Unit ID

 

Set the Modbus Address 

1 to 247

 

100

 

Baud Rate

 

Data rate in bits per second 

1200/2400/4800/9600/19200/38400 bps

 

9600

 

Config.

 

Data Format 

8N2/8O1/8E1/8N1/8O2/8E2

 

8E1

 

Energy Setup

 

LED Energy Pulsing

 

Enable kWh and kvarh LED Energy Pulsing

 

OFF/P/Q

 

 

Pulse Constant

 

Pulse Constant

 

1000/3200

 

1000

 

 
 

 

 