Ceiec Electric Technology
30
Option
Description
Setting
New
Add a new mapping relationship by clicking
New.
Remove
Remove the selected mapping relationship.
No.
Modbus Gateway number
Channel
Channel P3 to P6.
Unit ID (Local)
Serial Device’s Unit ID, each of channel’s unit ID
must be unique.
1~247
Map ID (Remote)
Ethernet Mapping ID, each of Map ID must be
unique, no matter it belongs to same channel or
not.
1~247
Notes:
1)
The default port number of Modbus Gateway is 502.
4.3.2.5 Serial Port
This option is only available in the T model.
Click on
Serial
Port
under
Channel Management
on the left-hand pane and the following screen
appears.
Option
Description
Setting
Baudrate
Select the Baudrate
300, 600, 1200, 2400,
4800, 9600*, 19200,
38400, 57600, 115200
Data Bits
Select the number of Data Bits
5, 6, 7, 8*
Parity
Select the Parity setting
None, Odd, Even*,
Mark, Space
Stop Bits
Select the number of Stop Bits
1*, 2
Packet Timeout (ms)
The maximum waiting time for a response packet
0 to 60000 ms
Default = 1000
Byte Timeout (ms)
Specify the maximum amount of time between the
reception of two consecutive bytes before a packet
frame is considered to have ended
0 to 60000 ms
Default = 20
Notes:
1)
PMC-1304-3 supports up to 16 TCP connections for Client access over Ethernet.