CAUTION

No field repair of the detectors should be attempted.

The detectors are factory repairable only.

COMPATIBLE CONTROL EQUIPMENT

Refer to the 

MXL/MXLV OPERATION, INSTALLATION,

AND MAINTENANCE MANUAL,

 P/N 315-092036, or the

MXL-IQ OPERATION, INSTALLATION, AND MAINTE-

NANCE MANUAL,

 P/N 315-093624. The ILP-2 is only

compatible with MXL/MXLV Rev. 8.0 or greater firmware

and MXL-IQ Rev. 3.0 or greater firmware.

P/N 315-095028-3

Содержание ILP-2

Страница 1: ...st or humidity DETECTOR PLACEMENT Although no specific spacings are set for the detectors used for the 0 to 4000 ft min clean air velocity applica tion use 30 foot center spacing 900 sq ft from NFPA S...

Страница 2: ...n ics extensive experience in the design of the system assures the best detector placement Sound engineer ing judgment by qualified personnel must be followed DB 3S DB X3RS DB 3S DB X3RS To avoid nuis...

Страница 3: ...warehouses auditoriums etc do affect detector response and should be considered SPECIAL CEILING CONSTRUCTION FACTORS Ceiling obstructions can change the natural movement of air and combustion product...

Страница 4: ...the nameplate is 2 5 ft For application sensitivity setting refer to the MXL MXLV OPERATION INSTALLATION AND MAINTENANCE MANUAL P N 315 092036 or the MXL IQ OPERATION INSTALLATION AND MAINTENANCE MANU...

Страница 5: ...is sealed against air leaks Open the shield cutouts only as much as required INSTALLATION OF DETECTOR HEAD 1 Align notch in detector cover to raised surface on outer ring of base refer to Figure 2 2 P...

Страница 6: ...detector in the wrong base DETECTOR SYSTEM CONFIGURATION ILP 2 with MXL Control Panels When the ILP 2 is used with MXL MXLV MXL IQ systems it can be programmed to optimize environmen tal response usin...

Страница 7: ...T Only qualified service personnel should test The minimum test schedule may be found in the current edition of NFPA 72 Chapter 7 ILP 2 with MXL Family Control Panels The MXL Control Panel must be pla...

Страница 8: ...I 32 Programmer Tester Refer to the OPERA TIONS MANUAL P N 315 090077 DETECTOR CLEANING System MXL automatically indicates the trouble mes sage INPUT DEVICE REQUIRES SERVICE for any detector whose smo...

Страница 9: ...t 5 Use a small soft brush to loosen dust in the crevices Vacuum any dust from the lower photochamber Do not use cleaners or solvents on the lower photochamber Another method for cleaning the photocha...

Страница 10: ...positioning the visible LED correctly Replace the detector in the base 9 Clean all other Model ILP 2 detectors following Steps 2 through 8 10 Recheck the sensitivity of the detector 11 If the sensiti...

Страница 11: ...IBLE CONTROL EQUIPMENT Refer to the MXL MXLV OPERATION INSTALLATION AND MAINTENANCE MANUAL P N 315 092036 or the MXL IQ OPERATION INSTALLATION AND MAINTE NANCE MANUAL P N 315 093624 The ILP 2 is only...